5.9.9 Structure 1392: CC11 VDS Interface Part 1
Datapoint: VDS_FBF (FBF)
This datapoint covers the fault signals of the FBF (fire brigade operating panel) and the
basic function unit.
1392/FBF: Addressing
Sector: BASIC
ADF1/2: sequence number based
1392/FBF: Valid states
State Description Valid commands
NORMAL
No faults in the FBF or function unit.
FAULTY
One of the following faults exists:
- Processor failure
- Emergency operation monitoring defective
- Configuration error
- FBF faulty
- FBF Power Supply faulty
ACKNOWLEDGE
1392/FBF: State transition diagram
To
From
FAULTY NORMAL
FAULTY
---
Fault
--------------
N 34 3C
NORMAL Fault
--------------
U 34 46
---
1392/FBF: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
Z <CCaddr> <adf12> N 34 3C NORMAL Function unit Normal
Z <CCaddr> <adf12> U/Q 34 46 FAULT Function unit Faulty
1392/FBF: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
Z <CCaddr> <adf12> R 34 86 Function unit Acknowledgment (fault)