User Manual

68
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
Datapoint: VDS_FUE (FUE)
This datapoint covers the state of the alarm remote transmission (FUE).
1392/FUE: Addressing
Sector: FIRE
ADF1/2: sequence number based
1392/FUE: Valid states
State Description Valid commands
INACTIVE
The remote transmission (FUE) is ready and in the quiescent state.
ACTIVE
The FUE is activated.
OFF
The FUE is switched-off. ACKNOWLEDGE
FAULTY
One or more faults exist in the FUE part of the function unit:
- Processor failure
- line fault
- Activation error
- Deactivation error
ACKNOWLEDGE
1392/FUE: State transition diagram
To
From
ACTIVE OFF FAULTY INACTIVE
ACTIVE
---
Off
--------------
U 09 56
Active &
Faulty
--------------
U 09 46
Inactive
--------------
N 09 4D
OFF
--- ---
On &
Faulty
--------------
U 09 46
On
--------------
N 09 4D
FAULTY
---
Off
--------------
U 09 56
---
Faulty
-------------
N 09 4D
INACTIVE Active
--------------
U 09 4F
Off
--------------
U 09 56
Faulty
--------------
U 09 46
---
1392/FUE: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
W <CCaddr> <adf12> U/Q 09 46 FAULT Remote transmission ALARM Faulty
W <CCaddr> <adf12> N 09 4D NORMAL Remote transmission ALARM Inactive
W <CCaddr> <adf12> Q 09 4F ANOMALY Remote transmission ALARM Active
W <CCaddr> <adf12> U/Q 09 56 ANOMALY Remote transmission ALARM Off
1392/FUE: Telegram repertoire: COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
W <CCaddr> <adf12> R 09 86 Remote transmission ALARM Acknowledgment (fault)
W <CCaddr> <adf12> R 09 89 Remote transmission ALARM Acknowledgment (anomaly)