Datapoint: VDS_FSK (FSK)
This datapoint covers the states of the fire brigade key (FSK).
1393/FSK: Addressing
Sector: FIRE
ADF1/2: sequence number based
1393/FSK: Valid states
State Description Valid commands
NORMAL
The key box (FSK) is ready and in the quiescent state.
SABOTAGE
The FSK is tampered. ACKNOWLEDGE
RESET
FSK MANUALLY
UNLOCKED
the FSK is manually unlocked via switch on the VDS interface
board
FSK UNLOCKED
FSK door is unlocked due to fire alarm
FSK OPEN
FSK door is open
FSK KEY MISSING
the key in the FSK key box is missing
FAULTY
One or more faults exist in the FSK part of the function unit:
- Processor failure
- others
ACKNOWLEDGE
1393/FSK: State transition diagram
To
From
SABOTAGE KEY MISSING MANUALLY
UNLOCKED
UNLOCKED OPEN FAULTY NORMAL
SABOTAGE
--- --- --- --- --- ---
Reset
--------------
N 0C 85
N 34 3C
KEY MISSING
--- --- --- --- --- ---
Key missing
-------------
N 34 3C
MANUALLY
UNLOCKED
--- --- --- --- ---
Faulty
--------------
U 34 46
M.unlocked
-------------
N 34 3C
UNLOCKED
--- --- --- --- Alarm AND
Open
--------------
U 34 27
Faulty
--------------
U 34 46
Unlocked
-------------
N 34 3C
OPEN
--- Alarm Reset
AND
Key missing
-------------------
U 34 28
--- --- ---
Faulty
--------------
U 34 46
Open
-------------
N 34 3C
FAULTY
---
Key missing
-------------------
U 34 28
--- --- --- ---
Faulty
-------------
N 34 3C
NORMAL Sabotage
--------------
U 0C 00
---
Man.unlocked
--------------------
U 34 25
Alarm AND
Unlocked
--------------
U 34 26
---
Faulty
--------------
U 34 46
---