Datapoint PRINTER (PRT)
1201/PRT: Addressing
Sector: BASIC
ADF1/2: 000D
1201/PRT: Valid states
State Description Valid commands
NORMAL
The printer is switched on and there is no fault.
OFF
The printer is switched off.
FAULTY
One of the following faults exists in the printer:
- XOFF or DTR Timeout
- End of paper
- Printing mechanism blocked.
ACKNOWLEDGE
1201/PRT: State transition diagram
To
From
OFF FAULTY NORMAL
OFF
---
On & Fault
--------------------
U 36 46
On
--------------
N 36 3C
FAULTY Off
--------------
Q 36 56
---
Fault
--------------
N 36 3C
NORMAL Off
--------------
Q 36 56
Fault
--------------
U 36 46
---
1201/PRT: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
Z <CCaddr> <adf12> N 36 3C NORMAL Printer Normal
Z <CCaddr> <adf12> U/Q 36 46 FAULT Printer Faulty
Z <CCaddr> <adf12> Q 36 56 ANOMALY Printer Off
1201/PRT: Telegram repertoire COMMAND
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
Z <CCaddr> <adf12> R 36 86 Printer Acknowledgment (fault)