5.10.4 Structure 1210: CI11 Compact control unit
Abstract representation of a CI11 compact control unit. See structure 1201 for details.
5.10.5 Structure 1211: CC11 Control unit (Remote)
Abstract representation of the connection status of a remote CC11 control unit. Each
CC11 may have up to 3 instances of structure 1211 representing the connection status
to the other CC11 stations on the same C-Bus. These connection information is re-
quired if the different CC11s depend on a centralized remote transmission device or
include distributed controls. The structure contains the datapoint CONNECTION.
1211/CON: Addressing
Sector: BASIC
ADF1/2: Based on sequence number
1211/CON: Valid states
State Description Valid commands
NORMAL
Normal connection to remote CC11.
FAULTY
Connection to remote CC11 failed. ACKNOWLEDGE
1211/CON: State transition diagram
To
From
FAULTY NORMAL
FAULTY
---
Fault
--------------
N 38 3C
NORMAL Fault
--------------
U 38 46
---
1211/CON: Telegram repertoire MESSAGES
Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B
Z <CCaddr> <adf12> N 38 3C NORMAL Data network normal
Z <CCaddr> <adf12> U/Q 38 46 FAULT Data network Faulty
1211/CON: Telegram repertoire COMMANDS
Sector DMS Adr ADF1/2 Sep Data A Data B Text A Text B
Z <CCaddr> <adf12> R 38 86 Data network Acknowledgment (fault)