6 Examples
The following examples show typical events and how they are processed.
6.1 Alarms
6.1.1 Local alarm in DAY mode
Assumptions: CC11 with DMS address 111, organization DAY MODE, Operation be-
fore expiration CAC
CC11 Telegram Management system
Detector generates danger level = 2
(Pre-alarm state)
W1110B33U033A
W1110B6BQ674F
(Warning)
(Element active)
(Command acknowledgment warn-
ing)
W1110B33R0389
Warning is acknowledged by operator
‘Warning’ state is acknowledged
W1110B33Q033A
Detector generates danger level = 3
(Alarm-State). CAC-V1 starts.
W1110B33N033B
W1110B33U0101
W1110B30Q0101
W111A1CDQ0500
W1110279U7A4F
(Warning end)
(Autom. detector alarm)
(Collective alarm, Section)
(Local alarm area 1)
(Internal horn Active)
(Command acknowledgment alarm)
W1110B33R0180
Alarm is acknowledged by the operator (before
expiration of CAC V1).
‘Alarm’ state is acknowledged.
CAC-V1 stops, CAC-V2 starts.
W1110B33Q0101
W1110279Q7A4F
W1110279N7A4D
(Alarm acknowledged)
(Internal horn acknowledged)
(Internal horn inactive)
Cause of alarm is being investigated and reme-
died.
(Command reset alarm)
W1110B33R0183
Alarm is reset by operator (before expiration of
CAC-V2).
Alarm reset. Detector and zone in
normal state, CAC-V2 stops.
W1110B33N0185
W1110B30Q0185
W111A1CDQ0585
W1110B33N643C
W1110B6BN673C
(Alarm reset)
(Collective section alarm reset)
(Local alarm area 1 reset)
(Zone normal)
(detection device normal)