6.1.2 General alarm in day mode
Assumptions: CC11 with DMS address 111, organization DAY mode, operation before
expiration of CAC.
CC11 Telegram Management system
Detector generates danger level = 2
(Pre-alarm state)
W1110B33U033A
W1110B6BQ674F
(Warning)
(Element active)
(Command acknowledgment warn-
ing)
W1110B33R0389
Warning is acknowledged by operator.
‘Warning’ state is acknowledged
W1110B33Q033A
Detector generates danger level = 3
(alarm state). CAC-V1 starts.
W1110B33N033B
W1110B33U0101
W1110B30Q0101
W111A1CDQ0500
W1110277U7A4F
(Warning end)
(Autom. detector alarm)
(Collective alarm Section)
(Local alarm Sector 1)
(Internal horn active)
(Command acknowledgment alarm)
W1110B33R0180
Alarm is acknowledged by operator (before
expiration of CAC-V1).
‘Alarm’ state is acknowledged.
CAC-V1 stops, CAC-V2 starts.
W1110B33Q0101
W1110277Q7A4F
W1110277N7A4D
(Alarm acknowledged)
(Internal horn acknowledged)
(Internal horn inactive)
The cause of the alarm is being investigated.
The situation proves to be so seri-
ous that the fire brigade has to be
summoned immediately. Manual
manual callpoint is pressed.
W1110B40U0102
W1110B41Q674F
W111A1CDQ0600
W1110277U7A4F
W1110278U734F
W111027EQ094F
(Man. detector alarm)
(Detection device active)
(General alarm Sector 1)
(Internal horn active)
(External horn active)
(Remote transmission alarm active)
Fire fighting in progress.
(Command acknowledgment alarm)
W1110B40R0180
Alarm is acknowledged by the operator
W1110B40Q0102
W1110277Q7A4F
W1110277N7A4D
W1110278Q734F
(Alarm acknowledged)
(Internal horn acknowledged)
(Internal horn inactive)
(External horn acknowledged)
(External horn inactive command)
W1110278R734D
External horn is switched off by the operator.
External horn switched off
W1110278N734D
(External horn inactive)
(Command reset alarm)
W111A1CDR0683
Fire extinguished. Alarm reset by the operator
(via the Sector)
Alarms reset. Everything back in
normal condition.
W1110B33N0185
W1110B40N0185
W1110B30Q0185
W111A1CDQ0585
W111027EN094D
W1110B33N643C
W1110B6BN673C
W1110B40N643C
W1110B41N673C
(Autom. detector alarm reset)
(Man. detector alarm reset)
(Collective section alarm reset)
(General alarm Sector 1 reset)
(Remote transmission alarm inactive)
(Zone normal)
(Detection device normal)
(Zone normal)
(Detection device normal)