User Manual

87
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
6.1.4 Extinguishing sequence
Assumptions: CC11 with DMS address 111, extinguishing system triggered by auto-
matic detectors
CC11 Telegram Management system
1st detector generates danger level =
2
L11103B1U033A
L11103B4Q674F
(Warning)
(Detection device active)
1st detector generates danger level =
3
L11103B1N033B
L11103B1U0401
W111A4CDQ0500
W111027EU7A4F
(Warning end)
(Pre-alarm autom. detector)
(Local alarm area 4)
(Internal horn active)
2nd detector generates danger level
= 3
L11103B5Q674F
L11103B1U0801
L111B6EBU0801
W111A4CDQ0600
W111029FU734F
W1110294Q094F
(Detection device active)
(Extinguishing alarm autom. detector, zone)
(Extinguishing alarm autom. detector, section)
(General alarm area 4)
(External horn active)
(Remote transmission alarm active)
State = Evacuation. The delay before
the extinguishing valve opens is
counted down. To ensure that suffi-
cient time remains for evacuation, the
emergency stop button is pressed.
The delay timer is interrupted.
W111A4ECQ753A
L111B6AEU4D5D
(Part of system off, area 4)
(Release inhibited, extinguishing section 6)
The personnel is evacuated. The
emergency stop button is released.
Countdown of the delay for opening
the extinguishing valve continues.
L111B6AEN4D5A
W111A4ECN753B
(Release not inhibited, exting. section 6)
(Part of system off ended, area 4)
Delay expires. Extinguishing valve
opens.
L111B6AEQ4D4F
(Release active, extinguishing section 6)
W111A4CDR0680
Acknowledge alarms (via area)
All alarms are acknowledged.
L11103B1Q0801
L111B6EBQ0801
W111027EQ7A4F
W111027EN7A4D
W111029FQ734F
(Extinguishing alarm exting. zone acknowl-
edged)
(Extinguishing alarm extinguishing zone
acknowledged)
(Internal horn acknowledged)
(Internal horn Inactive)
(External horn acknowledged)
W111A4CDR0683
Reset alarms (via area)
L11103B4N674D
L11103B5N674D
L11103B1N0885
L11103B1N643C
L111B6EBN0885
L111B6AEN4D5A
W111A4CDN0685
W111029FN734N
W1110294N094D
(Detection device normal)
(Detection device normal)
(Extinguishing alarm exting. zone reset)
(Zone normal)
(Extinguishing alarm exting. section reset)
(Releasenot inhibited, exting. section 6)
(General alarm area 4 reset
(External horn Inactive)
(Remote transmission alarm inactive
Extinguishing system not ready
(extinguishing valve, extinguishant
supply)
W111A4EDQ743A
L111B6EDU3A3A
W111A4ECQ753A
L111B6AEQ4D5D
(Collective fault area 4) Sector 4)
(Fault extinguishing section 6)
(Collective switch-off area 4)
(Release inhibited, exting. section 6)
L111B6EDR3A86
(Acknowledge fault ext. section 6)
Fault is acknowledged.
L111B6EDQ3A3A
(Fault exting. section 6 acknowledged)
Extinguishing ready again (valve
armed, extinguishant replenished)
W111A4EDN743B
L111B6EDN3A3N
W111A4ECN753B
L111B6AEN4D5A
(Collective fault end, area 4)
(Fault end, exting. section 6)
(Collective switch-off area 4)
(Release inhibited, exting. section 6)