User Manual

88
Fire & Security Products
Siemens Building Technologies Group
1964_a_en_--.doc
07.2001
6.2 Faults
6.2.1 Detector fault
Assumptions: CC11 with DMS address 111, organization DAY mode, operation before
expiration of fault CAC.
CC11 Telegram Management system
Detector faulty
W1110B6BU6746
W111A1EDQ743A
(Detection device faulty)
(Collective fault area 1)
(Fault acknowledgment command)
W1110B6BR6786
Fault is acknowledged by the operator
‘Fault’ state is acknowledged
W1110B6BQ6746
The cause of the fault is being investigated
and remedied.
Detector in normal state
W1110B6BN673C
W111A1EDN743B
(Detection device normal)
(Collective fault area 1 ended)
6.3 Others
6.3.1 Organization changeover
Assumptions: CC11 with DMS address 111, organization DAY mode
CC11 Telegram Management system
(Night) command
W111A1EFR5555
Area 1 is switched to Night mode by the
operator.
Area 1 is switched to Night mode.
W111A1EFN5560
Assumptions: CC11 with DMS address 111, organization NIGHT mode.
CC11 Telegram Management system
(Day command)
W111A1EFR5556
Area 1 is switched to Day mode by the opera-
tor.
Area 1 is switched to Day mode.
W111A1EFN5561
6.3.2 Switching a detection zone
Assumptions: CC11 with DMS address 111
CC11 Telegram Management system
(Off command)
W1110B33R6456
Zone x is switched off by the operator.
Zone x is switched off.
W1110B33Q6456
W111A1ECQ753A
(Zone Off)
(Collective switch-off area 1)
(On command)
W1110B33R6455
Zone x is switched on by the operator.
Zone x is switched on.
W1110B33Q643C
W111A1ECN753B
(Zone in normal operation)
(Collective switch-off area 1 ended)