CS1140 Gateway CK1142 and CK1143 Interface Description SW Ver. 8.0x Copy no.
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2009 Copyright by Siemens Switzerland Ltd Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor.
1 Overview ..................................................................................................7 2 CS11 Hardware architecture ..................................................................7 3 3.1 3.2 3.3 CS11 Information architecture...............................................................8 Logical tree................................................................................................9 Physical tree....................................................................
5.8.3 5.8.4 5.8.5 5.8.8 5.8.9 5.9 5.9.1 5.9.2 5.9.3 5.9.4 5.9.5 5.9.6 5.9.7 5.9.8 5.9.9 5.10 5.10.1 5.10.2 5.10.3 5.10.4 5.10.5 5.10.6 5.10.7 5.10.8 5.10.9 5.10.10 5.10.11 5.10.12 5.10.13 5.10.14 5.10.15 5.10.16 5.10.17 5.11 5.11.1 5.11.2 5.11.3 5.11.4 5.12 5.12.1 5.12.2 5.13 Structure 1560: Internal horn element ....................................................70 Structure 1561: External horn element ...................................................
6.3 6.3.1 6.3.2 6.3.3 Others ...................................................................................................119 Organization changeover......................................................................119 Switching a detection zone ...................................................................119 Switching a detection zone to TEST .....................................................120 7 Terminology and abbreviations.........................................................
Changes in the documentation Errors in document 009897_c_en V7.8x / V7.9x The page numbers refer to the respective document. Page --- Correction --- Changes since document 009897_c_en V7.8x / V7.9x StrucNr 1501 Structure name Status DS11i detector parameterset telegram added. New datapoint 1501/PARAMSET added ADDED 6 Building Technologies Fire Safety & Security Products 019_DMS_CS1140_Interface_Spec_CK1142_V8.0x_A6V10089060_a_en.doc 3.
Overview 1 Overview The AlgoRex CS11 fire detection system represents the current generation of the SIEMENS fire detection technology. This system offers the following features: – – – – High detection intelligence. Excellent communications capability High configuration flexibility High system availability CS11 systems can be integrated into a DMS7000 network via a gateway and thus connected to a SIEMENS monitoring system or an external system.
CS11 Information architecture 3 CS11 Information architecture The information within the CS 11 system is arranged hierarchically. The logical / geographical structure is represented by the logical tree, the physical (hardware) structure by the physical tree. These two trees are interconnected. Logical Tree AREA SECTION ZONE ELEMENT Low DEVICE High Low FUNCTION UNIT High STATION Physical Tree 8 Building Technologies Fire Safety & Security Products 019_DMS_CS1140_Interface_Spec_CK1142_V8.
CS11 Information architecture 3.1 Logical tree The logical tree represents the logical/geographical data image of a station. Area The Area comprises lower ranking nodes (sections, zones, elements) that are linked to a common alarm organization. The alarm organization can be set either to: z DAY (Day mode, manned operation) A danger event can be investigated by the on-site security personnel before external intervention squads (fire department) are summoned.
CS11 Information architecture 3.2 Physical tree The physical tree represents the installed hardware components of a station. Station The term Station refers to individual nodes on the C-Bus. Stations supply primarily information on faults in the connected hardware. Currently the following stations exist: CC11, CI11, CT11 and CK11. System limit: 16 stations per CS11. Function unit The term function unit refers to modules connected to the internal I-bus of the stations.
Integration of the CS11 architecture into the DMS7000 4 Integration of the CS11 architecture into the DMS7000 A CS11 system can be integrated into a DMS7000 network via a CK11 gateway. Due to the dissimilarity of the systems special measures must be taken. 4.1 Basis for integration The telegram functionality of the CS11 is oriented toward the already existing fire detection systems. Existing telegrams are re-used as far as possible.
Integration of the CS11 architecture into the DMS7000 z Addressing of the CS11 areas The ADF1 field contains hexadecimal “A” followed by the hexadecimal CSX number of the area. Example: A1 = area 1, A4 = area 4. The ADF2 field contains a fixed, 2-digit value that corresponds to the function of the datapoint. Example: EF for the organization datapoint, CD for the General alarm datapoint, etc. z Addressing of the CS11 stations The ADF1 field contains a fixed number of “00”.
Integration of the CS11 architecture into the DMS7000 4.3.2 Syntax EBNF symbols: . End of sentence “x” Terminal symbol {} 0..n repetitions [] optional part () precedence | exclusive OR ‘ ‘ descriptive definition Common: file = Record{Record}. Record = Field{“;”Field”} Newline. Field = “““Text”””. Newline = ‘Line Delimiter (e.g. DOS: )’. Syntax description: Configfile = Record { Record }. Record = RecordNr “;” (Record1 | Record2) Newline. RecordNr = DecNumber.
Integration of the CS11 architecture into the DMS7000 4.3.3 Semantics The semantics describe the valid contents and significance of the fields within the configuration file. RecordNr This field contains the line number of the entry in the configuration file. RecordType This field contains the type of entry.
Integration of the CS11 architecture into the DMS7000 DMSSector This field describes the affiliated danger sector. Valid entries are: A = Fire B = Extinguishing C = Intrusion D = Gas E = Plant monitoring 0 (Null) = Basic sector X = Dummy entry. The whole record does not provide datapoints and is for structure purposes only DMSAdf12 This field contains the ADF1/2 number which is derived from the SeqNr. From the viewpoint of the DMS7000 the ADF1/2 number is the address of the CC11 datapoint.
Integration of the CS11 architecture into the DMS7000 4.4 Information depth The information depth of the individual datapoints is determined by the (limited) functionality of the DMS7000 network. z Parallel information must be mapped to unique states or to separate datapoints. z No differentiation between the subtypes within the same hierarchical levels ZONE, ELEMENT and IBD. z Example: Single detector zone and multi-detector zone are both detector zones within the DMS7000.
CS11 Behavior in the DMS7000 5 CS11 Behavior in the DMS7000 5.1 Description of the data structures The same description scheme is used for each data structure: – – – – Quick-reference description Valid states State transition diagram Telegram repertoire In order to make the structure description identifiable also across several pages, the corresponding structure number is shown in front of the headings.
CS11 Behavior in the DMS7000 5.1.4 Telegram repertoire Table that represents the telegram repertoire for MESSAGES and COMMANDS The Priority field in the MESSAGES table shows the classification of the corresponding messages based on the following scale: – – – – NORMAL ANOMALY FAULT ALARM (low priority) (high priority) Based on the priority also the acknowledgment command telegram can be determined. The Text A and Text B fields contain the standard texts introduced in the DMS7000 network.
CS11 Behavior in the DMS7000 5.2 Hierarchical level: AREA 5.2.1 Structure 1801: FIRE area Abstract representation of a FIRE area. The area contains the datapoints: – – – – – – ORGANIZATION GENERAL ALARM ALARM RT DELAY (RT = Remote transmission) PART OF SYSTEM OFF FAULT RT-DEVICE (datapoint formerly presented in structure 1563) Datapoint ORGANIZATION (ORG) This datapoint relates to the alarm organization (CAC) within the area.
CS11 Behavior in the DMS7000 Datapoint ALARM (ALM) This datapoint contains the alarm level of the corresponding area. 1801/ALM: Addressing Sector: FIRE ADF1/2: aaCD (aa = “A” + , example: A2CD = alarm in area 2) 1801/ALM: Valid states State RESET LOCAL ALARM Description The area is not in the alarm state. Cause: In Day mode an alarm of an automatic detector has been detected. GENERAL ALARM Cause: In Day mode an alarm triggered by a manual callpoint has been detected.
CS11 Behavior in the DMS7000 Datapoint: ALARM RT DELAY (ARD) This datapoint represents the state of the “Alarm Remote Transmission Delay” within the area. If the Alarm Remote Transmission Delay is switched off while an alarm event with RT requirements is pending, the current monitoring times are bypassed and the remote transmission is activated immediately.
CS11 Behavior in the DMS7000 Datapoint: PART OF SYSTEM OFF (PSO) This datapoint becomes active when one or more parts of the system have been switched off in the corresponding area. 1801/PSO: Addressing Sector: FIRE ADF1/2: aaEC (aa = “A” + , example: A4EC = Datapoint ‘Part of system Off’ in area 4) 1801/PSO: Valid states State INACTIVE ACTIVE Description No system parts are switched off in the corresponding area. Parts of the system are switched off in the corresponding area.
CS11 Behavior in the DMS7000 Datapoint: FAULT (FLT) This datapoint becomes active if one or several faults exist in the corresponding area. 1801/FLT: Addressing Sector: FIRE ADF1/2: aaED (aa = “A” + , example: A1ED = datapoint ‘Fault’ in area 1) 1801/FLT: Valid states State INACTIVE ACTIVE Description No faults exist in the corresponding area. Faults exist in the corresponding area.
CS11 Behavior in the DMS7000 Datapoint: RT-DEVICE (RTD) This datapoint reflects the current state of the remote transmission device associated to this area. 1801/RTD: Addressing Sector: FIRE ADF1/2: aaEA (aa = “A” + , example: A2EA = datapoint ‘RT-Device’ in area 2) 1801/RTD: Valid states State INACTIVE DISABLED Description Valid commands The affiliated remote transmission device is in the quiescent state.
CS11 Behavior in the DMS7000 5.3 Hierarchical level: SECTION (detection) The hierarchical level SECTION basically summarizes the states of the affiliated zones. In special cases (example: extinguishing section) additional, section-specific datapoints exist. 5.3.1 Structure 1701: FIRE Section The FIRE section has no own functionality but contains collective information of the affiliated detection zones.
CS11 Behavior in the DMS7000 1701: Telegram repertoire COMMANDS (ZONE commands from SECTION level) It is valid to use selected ZONE level commands on SECTION level. The command is then propagated to ALL zones belonging to the respective section. These command telegrams always contain the ADF1/2 of the respective section! Sector W W W W W W W 5.3.
CS11 Behavior in the DMS7000 1702/EAL: State transition diagram To From EXTING. ALARM MAN. RELEASE EXTING. ALARM MAN. ACTIVATION --- EXTING. ALARM AUTOM. DETECTOR --- EXTING. ALARM MAN. DETECTOR PREALARM FIRE ALARM RESET --- --- --- È Extinguishing EXTING. ALARM AUTOM. DETECTOR --- --- --- --- --- EXTING. ALARM MAN.
CS11 Behavior in the DMS7000 Datapoint RELEASE (REL) This datapoint contains the state of the extinguishing release system. 1702/REL: Addressing Sector: EXTINGUISHING ADF1/2: bbAE (bb = “B” + , example: B8AE = Release in section 8) 1702/REL: Valid states State ENABLED Description Valid commands The activation of the extinguishing system (if alarm criteria are DISABLE met) is enabled. DISABLE AUTOM.
CS11 Behavior in the DMS7000 1702: Telegram repertoire COMMANDS (ZONE commands from SECTION level) It is valid to use selected ZONE level commands on SECTION level. The command is then propagated to ALL zones belonging to the respective section.
CS11 Behavior in the DMS7000 5.4 Hierarchical level: SECTION (control) The hierarchical level SECTION basically summarizes the states of the affiliated control zones. 5.4.1 Structure 1751: Control Section Abstract representation of a CS11 control section. The control section does not provide DMS7000-relevant data. 5.
CS11 Behavior in the DMS7000 1601: State transition diagram To WARNING ALARM OFF TEST REVISION From WARNING --- Ç Alarm ---------------N 03 3B U 01 01 Ç Off -------------N 03 3B Q 64 56 Ç Test -------------N 03 3B Q 64 57 È WARNING ALARM --- --- Ç Off -------------N 01 85 Q 64 56 Ç Test -------------N 01 85 Q 64 57 OFF --- --- --- Ç Test -------------Q 64 57 TEST --- --- Ç Off -------------Q 64 56 --- REVISION ÇWARNING RENOVATION ----------------U 03 3A ÇWARNING ---------------
CS11 Behavior in the DMS7000 5.5.2 Structure 1602: Multi-Logic zone FIRE sector (A) In a multi-logic zone the alarm decision is based on the response of multiple detection devices affiliated with the zone. The conditions can be parameterized within the CC11. 1602/A: Sector: ADF1/2: Addressing FIRE Based on sequence number 1602/A: Valid states State NORMAL WARNING ALARM OFF TEST RENOVATION REVISION NOT READY Description Valid commands The zone is in the ON state.
CS11 Behavior in the DMS7000 1602a: State transition diagram To WARNING ALARM OFF TEST REVISION From WARNING --- Ç Alarm ---------------N 03 3B U 01 01 Ç Off -------------N 03 3B Q 64 56 Ç Test -------------N 03 3B Q 64 57 È WARNING ALARM --- --- Ç Off -------------N 01 85 Q 64 56 Ç Test -------------N 01 85 Q 64 57 OFF --- --- --- Ç Test -------------Q 64 57 TEST --- --- Ç Off -------------Q 64 56 --- REVISION ÇWARNING RENOVATION ----------------U 03 3A ÇWARNING --------------
CS11 Behavior in the DMS7000 5.5.3 Structure 1602: Multi-Logic zone EXTINGUISHING sector (B) In a multi-logic zone the alarm decision is based on the response of several detection devices affiliated with the zone. The conditions can be parameterized within the CC11. 1602/B: Sector: ADF1/2: Addressing EXTINGUISHING Based on sequence number 1602/B: Valid states State NORMAL WARNING PRE-ALARM EXTINGUISHING OFF TEST RENOVATION Description Valid commands The zone is in the ON state.
CS11 Behavior in the DMS7000 1602/B: State transition diagram To WARNING PRE-ALARM --- Ç Pre-alarm From WARNING EXTINGUISHING ALARM --- ---------------N 03 3B U 04 01 Ç Extinguish- OFF TEST REVISION RENOVATION NOT READY NORMAL Ç Off -------------N 03 3B Q 64 56 Ç Test -------------N 03 3B Q 64 57 È WARNING Ç Test -------------N 04 85 Q 64 57 È Warn.
CS11 Behavior in the DMS7000 1602/B: Telegram repertoire MESSAGES Sector L L L L L L L L L L L L DMS Adr ADF1/2 Sep U/Q N U/Q N U/Q N Q Q Q Q Q N Data A 03 03 04 04 08 08 64 64 64 64 64 64 Data B 3A 3B 01 85 01 85 3E 3F 56 57 5F 3C Priority ANOMALY NORMAL ALARM NORMAL ALARM NORMAL ANOMALY ANOMALY ANOM
CS11 Behavior in the DMS7000 5.5.4 Structure 1605: Manual callpoint zone In a manual callpoint zone only one detection device assigned to the zone needs to respond in order to reach the ALARM state. 1605: Sector: ADF1/2: Addressing FIRE Based on sequence number 1605: Valid states State NORMAL ALARM OFF TEST NOT READY Description Valid commands The zone is in the ON state. Incoming danger levels are processed. OFF TEST An affiliated detection device has reached danger level 3 (alarm).
CS11 Behavior in the DMS7000 5.5.5 Structure 1610: Digital zone Digital zones process binary information or danger levels. A logical TRUE signal or a dangerlevel > 1of an individual detection device affiliated with the zone suffices to reach either the WARNING or ALARM state. 1610: Sector: ADF1/2: Addressing EXTINGUISHING or PLANT MONITORING Based on sequence number 1610: Valid states State NORMAL WARNING Description The Zone is in the ON state. Incoming binary signals are processed.
CS11 Behavior in the DMS7000 1610: Telegram repertoire MESSAGES Sector LP LP LP LP LP DMS Adr ADF1/2 Sep U/Q N U/Q N Q Data A 01 01 03 03 64 Data B 01 85 3A 3B 3F Priority ALARM NORMAL ANOMALY NORMAL ANOMALY Text A Alarm Alarm Warning Warning Zone LP LP LP LP Q Q Q N 64 64 64 64 56 57 5F 3C ANOMALY ANOMALY ANOMALY NORMAL Zone Zone Zone Zone
CS11 Behavior in the DMS7000 5.5.6 Structure 1611: Single-detector zone (AUSTRALIA) In a single-detector zone only one detection device assigned to the zone needs to respond in order to reach the ALARM state. 1611: Sector: ADF1/2: Addressing FIRE Based on sequence number 1611: Valid states State NORMAL Description The zone is in the ON state. Incoming danger levels are processed. WARNING An affiliated detection device has reached danger level 2 (prealarm).
CS11 Behavior in the DMS7000 1611: State transition diagram To From WARNING WARNING ALARM --- Ç Alarm ALARM --- -------------N 03 3B U 01 01 --- ISOLATED ALARM --- FAULT Ç Warning Ç Alarm OFF -------------U 03 3A --- -------------U 01 01 --- TEST REVISION RENOV A-TION NOT READY NORMAL ISOLATED ALARM --- --- Ç Warning --- --- --- --- --- FAULT OFF TEST REVISION È Warning Ç Off Ç Test È Warning & pending faults --------------N 03 3B U 64 46 È Alarm & pending faults --------
CS11 Behavior in the DMS7000 1611: Telegram repertoire MESSAGES Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B W U/Q 01 01 ALARM Alarm Autom. detector W N 01 85 NORMAL Alarm Reset W U/Q 03 3A ANOMALY Warning --- W N 03 3B NORMAL Warning End W U/Q 0E 01 ALARM Isolated Alarm Autom.
CS11 Behavior in the DMS7000 5.5.7 Structure 1612: Multi-Logic zone (AUSTRALIA), FIRE sector (A) In a multi-logic zone the alarm decision is based on the response of multiple detection devices affiliated with the zone. The conditions can be parameterized within the CC11. 1612: Sector: ADF1/2: Addressing FIRE Based on sequence number 1612/A: Valid states State NORMAL Description The zone is in the ON state. Incoming danger levels are processed.
CS11 Behavior in the DMS7000 1612/A: State transition diagram To From WARNING WARNING ALARM --- Ç Alarm --------------N 03 3B U 01 01 ALARM --- --- --- ISOLATED ALARM --- --- --- FAULT Ç Warning OFF -------------U 03 3A --- Ç Alarm ------------U 01 01 --- ISOLATED ALARM Ç Isol.
CS11 Behavior in the DMS7000 1612/A: Telegram repertoire MESSAGES Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B W U/Q 01 01 ALARM Alarm Autom. detector W N 01 85 NORMAL Alarm Reset W U/Q 03 3A ANOMALY Warning --- W N 03 3B NORMAL Warning End W U/Q 0E 01 ALARM Isolated Alarm Autom.
CS11 Behavior in the DMS7000 5.5.8 Structure 1615: Manual callpoint zone (AUSTRALIA) In a manual callpoint zone only one detection device assigned to the zone needs to activate in order to reach the ALARM state. 1615: Sector: ADF1/2: Addressing FIRE Based on sequence number 1615: Valid states State NORMAL Description The zone is in the ON state. Incoming danger levels are processed. ALARM An affiliated detection device has reached danger level 3 (alarm).
CS11 Behavior in the DMS7000 1615: State transition diagram To From ALARM ALARM --- ISOLATED ALARM --- FAULT OFF TEST NOT READY NORMAL È Alarm Ç Off -------------N 01 85 Q 64 56 Ç Test -------------N 01 85 Q 64 57 --- Ç Reset & Danger = 0 -------------N 01 85 N 64 3C Ç Reset & Danger = 0 -------------N 0E 85 N 64 3C È Fault ----------------N 64 3C & pending faults -----------------N 01 85 U 64 46 ISOLATED ALARM FAULT OFF --- --- --- Ç Off -------------N 0E 85 Q 64 56 Ç Test ------------
CS11 Behavior in the DMS7000 1615: Telegram repertoire MESSAGES Sector DMS Adr ADF1/2 Sep Data A Data B Priority Text A Text B W U/Q 01 02 ALARM Alarm Autom. detector W N 01 85 NORMAL Alarm Reset W U/Q 0E 02 ALARM Isolated Alarm Autom.
CS11 Behavior in the DMS7000 5.5.9 Structure 1620: Digital zone (AUSTRALIA) Digital zones process binary information rather than danger levels. A logical TRUE signal of an individual detection device affiliated with the zone suffices to reach the ALARM state. 1620: Sector: ADF1/2: Addressing EXTINGUISHING or PLANT MONITORING Based on sequence number 1620: Valid states State NORMAL WARNING Description The Zone is in the ON state. Incoming binary signals are processed.
CS11 Behavior in the DMS7000 1620: State transition diagram WARNING ALARM ISOLATED ALARM FAULT OFF TEST NOT READY NORMAL Ç Alarm ---------------N 03 3B U 01 01 Ç Alarm ---------------N 03 3B U 0E 01 È Alarm Ç Off -------------N 01 85 Q 64 56 Ç Test -------------N 01 85 Q 64 57 --- Ç Reset & Danger = 0 -------------N 01 85 N 64 3C ALARM --- --- Ç Off -------------N 01 85 Q 64 56 Ç Test -------------N 01 85 Q 64 57 --- Ç Reset & Danger = 0 -------------N 01 85 N 64 3C ISOLATED ALARM ---
CS11 Behavior in the DMS7000 5.6 Hierarchical level: ZONE (controls) The CONTROL ZONE level is responsible for activating the affiliated control elements based on predetermined decision criteria. The term ‘Zone’ (controls) corresponds to the term Control zone in the DMS7000. 5.6.1 Structure 1651: Switching zone Based on the evaluation of the affiliated digital detection devices the affiliated control elements are activated. This zone type is principally used in the local area of the CC11.
CS11 Behavior in the DMS7000 5.6.2 Structure 1654/1656: Programmable control zone With programmable control zones any state combinations of datapoints within a CC11 control unit can be used for control purposes. 1654/1656: Addressing Sector: PLANT MONITORING ADF1/2: Based on sequence number 1654/1656: Valid states State INACTIVE Description Valid commands The zone is in the quiescent state. The evaluation logic is switched ACTIVE on. OFF ACTIVE The evaluation logic signals a TRUE state.
CS11 Behavior in the DMS7000 5.7 Hierarchical level: ELEMENT (detection) The detection devices evaluate the information supplied by detectors (danger levels) and digital inputs, and transmit the results to the higher ranking zones. 5.7.1 Structure 1501: Interactive detector element Abstract representation of an interactive series DS11-I detector.
CS11 Behavior in the DMS7000 1501/STATE: State transition diagram To ACTIVE OFF TEST ALARM ZONE = TEST DRIFT FAULTY IMPAIRED NORMAL (PARAMSET = NONDEFAULT) NORMAL ACTIVE --- Ç Off -------------Q 67 56 --- È Active & Drift ------------U 67 48 È Active & Faulty -------------U 67 46 È Active & Impaired -------------U 67 45 Ç Zone Reset & Danger = 0 -------------N 67 40 Ç Zone Reset & Danger = 0 -------------N 67 3C OFF --- --- --- Ç On & Drift -------------U 67 48 Ç On & Faulty ---------
CS11 Behavior in the DMS7000 Datapoint PARAMSET 1501: Addressing Sector: BASIC ADF1/2: Based on sequence number 1501/ PARAMSET: Valid values value PARAM.SET Description The respective detector has been set to parameterset . Valid commands Æ For valid parameterset values for specific detectors please refer to the DS11 application guidelines document 1225. The parameterset value represents the hexadecimal value of APS IDs (Algo parameterset Identifications) in document 1225. PARAM.
CS11 Behavior in the DMS7000 5.7.2 Structure 1502: FD20/DS11-I/A+ manual callpoint element Abstract representation of a FD20/DS11-I/A+ manual callpoint. 1502: Sector: ADF1/2: Addressing FIRE Based on sequence number 1502: Valid states State NORMAL IMPAIRED Description The element is in the ON state (connected to the circuit). Incoming danger levels are transmitted to the higher ranking zone.
CS11 Behavior in the DMS7000 1502: Telegram repertoire MESSAGES Sector W W WL W W W W DMS Adr ADF1/2 Sep Q N U/Q U/Q Q Q U/Q Data A 67 67 67 67 67 67 67 Data B 0B 3C 45 46 4F 56 5F Priority ANOMALY NORMAL ANOMALY FAULT ANOMALY ANOMALY FAULT Text A Detection device Detection device Detection device Detection device Detection device Detection device Detection device Text B Test Alarm
CS11 Behavior in the DMS7000 5.7.3 Structure 1503: Collective manual callpoint element Abstract representation of a collective series DS11-C manual callpoint. 1503: Sector: ADF1/2: Addressing FIRE Based on sequence number 1503: Valid states State NORMAL Description The element is in the ON state (connected to the circuit). Incoming danger levels are transmitted to the higher ranking zone. The affiliated detector has reached a danger level > 1.
CS11 Behavior in the DMS7000 5.7.4 Structure 1504: FD20 detector element Abstract representation of an FD20 series detector 1504: Sector: ADF1/2: Addressing FIRE or EXTINGUISHING Based on sequence number 1504: Valid states State NORMAL IMPAIRED ACTIVE TEST ALARM OFF DRIFT FAULTY Description The element is in the ON state (connected into the circuit). Incoming danger levels are transmitted to the higher ranking zone.
CS11 Behavior in the DMS7000 1504: State transition diagram To ACTIVE OFF TEST ALARM ZONE = TEST DRIFT FAULTY IMPAIRED NORMAL ACTIVE --- Ç Off -------------Q 67 56 --- È Active & Drift ------------U 67 48 È Active & Faulty -------------U 67 46 È Active & Impaired -------------U 67 45 Ç Zone Reset & Danger = 0 -------------N 67 3C OFF --- --- --- Ç On & Drift -------------U 67 48 Ç On & Faulty -------------U 67 46 Ç On & Impaired -------------U 67 45 Ç On -------------N 67 3C TEST ALA
CS11 Behavior in the DMS7000 5.7.5 Structure 1508: AnalogPlus element Abstract representation of a series DS11-A (AnalogPlus) detector. 1508: Sector: ADF1/2: Addressing FIRE or EXTINGUISHING Based on sequence number 1508: Valid states State NORMAL IMPAIRED ACTIVE TEST ALARM OFF DRIFT FAULTY Description The element is in the ON state (connected to the circuit). Incoming danger levels are transmitted to the higher ranking zone. The element reports a deviated parameter. The detector is still operational.
CS11 Behavior in the DMS7000 1508: Telegram repertoire MESSAGES Sector WL WL WL WL WL WL WL DMS Adr ADF1/2 Sep Q N U/Q U/Q U/Q Q Q Data A 67 67 67 67 67 67 67 Data B 0B 3C 45 46 48 4F 56 Priority ANOMALY NORMAL ANOMALY FAULT ANOMALY ANOMALY ANOMALY Text A Detection device Detection device Detection device Detection device Detection device Detection device Detection device Text B Tes
CS11 Behavior in the DMS7000 5.7.6 Structure 1510...1512: Collective line element Abstract representation of a series DS11-C collective line. Elements 1510 .. 1512 have different internal characteristics (pulse memory, delays), however, these do not appear on the DMS7000 side. 1510: Sector: ADF1/2: Addressing FIRE or EXTINGUISHING or PLANT MONITORING Based on sequence number 1510: Valid states State NORMAL Description The element is in the ON state (connected to the circuit).
CS11 Behavior in the DMS7000 5.7.7 Structure 1520: Digital detection device Abstract representation of digital transmitters (contacts, etc.) whose binary states are translated into danger levels: Log. 0 = Danger level 0 Log. 1 = Danger level 3 1520: Sector: ADF1/2: Addressing FIRE Based on sequence number 1520: Valid states State NORMAL ACTIVE TEST ALARM OFF FAULTY Description The element is in the ON state (connected into the circuit). Incoming danger levels are transmitted to the higher ranking zone.
CS11 Behavior in the DMS7000 5.7.8 Structure 1521: Digital manual callpoint element Abstract representation of digital transmitters (contacts, etc.) whose binary states are translated into danger levels and which are used as manual callpoints: Log. 0 = Danger level 0 Log. 1 = Danger level 3 1521: Sector: ADF1/2: Addressing FIRE Based on sequence number 1521: Valid states State NORMAL IMPAIRED ACTIVE TEST ALARM OFF NOT READY FAULTY Description The element is in the ON state (connected into the circuit).
CS11 Behavior in the DMS7000 1521: Telegram repertoire MESSAGES Sector W W W W W W W DMS Adr ADF1/2 Sector W W W W DMS Adr ADF1/2 Sep Q N U/Q U/Q Q Q U/Q Data A 67 67 67 67 67 67 67 Data B 0B 3C 45 46 4F 56 5F Priority ANOMALY NORMAL ANOMALY FAULT ANOMALY ANOMALY FAULT Text A Detection device Detection device Dete
CS11 Behavior in the DMS7000 5.7.9 Structure 1525: Digital element Abstract representation of digital transmitters (contact, etc.). 1525: Sector: ADF1/2: Addressing EXTINGUISHING or PLANT MONITORING Based on sequence number 1525: Valid states State NORMAL Description The element is in the ON state (connected into the circuit). Incoming danger levels are transmitted to the higher ranking zone. The affiliated transmitter signals Log.
CS11 Behavior in the DMS7000 5.8 Hierarchical level: ELEMENT (controls) Control devices receive control commands from higher ranking instances and transmit these to the physical devices. 5.8.1 Structure 1551: Output element without feedback Abstract representation of a digital output. Activation of the peripheral devices is not monitored.
CS11 Behavior in the DMS7000 5.8.2 Structure 1552: Output element with feedback Abstract representation of a digital output. Activation of the peripheral device is monitored via a separate digital input. 1552: Sector: ADF1/2: Addressing PLANT MONITORING Based on sequence number 1552: Valid states State INACTIVE INACTIVE – FEEDBACK ACTIVE ACTIVE ACTIVE – FEEDBACK INACTIVE OFF FAULTY Description The element is in the ON state (connected into the circuit).
CS11 Behavior in the DMS7000 5.8.3 Structure 1560: Internal horn element Abstract representation of an internal horn output. Internal horn elements receive their control commands directly from the higher ranking AREA. Typically the internal horn is activated simultaneously with the buzzer on the CT11. 1560: Sector: ADF1/2: Addressing FIRE Based on sequence number 1560: Valid states State INACTIVE Description The element is in the ON state (connected into the circuit).
CS11 Behavior in the DMS7000 5.8.4 Structure 1561: External horn element Abstract representation of an external horn output. External horn elements receive their commands directly from the higher ranking AREA. Typically the external horn is activated in accordance with the Cerberus Alarm Concept (CAC) after expiration of the presence monitoring time V1 or alarm investigation time V2.
CS11 Behavior in the DMS7000 1561: State transition diagram To From ACTIVE ACTIVE OFF FAULTY INACTIVE --- Ç Off -------------Q 73 56 È Active & Ç Inactive Faulty -------------U 73 46 Ç On & Faulty -------------U 73 46 --- -------------N 73 4D OFF --- --- FAULTY --- Ç Off -------------Q 73 56 Ç Off -------------Q 73 56 Ç Active -------------U 73 4F INACTIVE Ç Faulty -------------U 73 46 Ç On -------------N 73 4D È Faulty ------------N 73 4D --- 1561: Telegram repertoire: MESSAGES Sector
CS11 Behavior in the DMS7000 5.8.5 Structure 1562 (attr = RTFIRE): ALARM remote transmission channel element Abstract representation of a remote transmission output for ALARMS. Remote transmission channels receive their control commands directly from the higher ranking AREA. Typically it is activated in accordance with the CERBERUS Alarm Concept (CAC), after expiration of the presence monitoring time V1 or alarm investigation time V2.
CS11 Behavior in the DMS7000 5.8.6 Structure 1562 (attr = RTFAULT): FAULT remote transmission channel element Abstract representation of a remote transmission output for FAULTS. Remote transmission channels receive their control commands directly from the higher ranking AREA. Typically it is activated in accordance with the CERBERUS Alarm Concept (CAC), after expiration of the presence monitoring time V1.
CS11 Behavior in the DMS7000 5.8.7 Structure 1562 (attr = RTOTHER): OTHER remote transmission channel element Abstract representation of a remote transmission output for OTHER (selectable) events. Remote transmission channels receive their control commands directly from the higher ranking AREA. Typically it is activated in accordance with the CERBERUS Alarm Concept (CAC), after expiration of the presence monitoring time V1.
CS11 Behavior in the DMS7000 5.8.8 Structure 1564: Alarmhorn (under area CAC control) Abstract representation of an alarmhorn whose activation / deactivation is controlled by the area CAC. The behavior is identical to structure 1561 (External horn). 5.8.9 Structure 1565: Alarmhorn Abstract representation of an alarmhorn whose activation / deactivation can be userprogrammed. The behavior is identical to structure 1561 (External horn).
CS11 Behavior in the DMS7000 5.9 Hierarchical level: DEVICE (Field-) Devices are connected to a detector bus (D-bus) or a field bus (LON) of a CC11 /CI11 control unit. Typical devices are: – TeleRex gateway – AnalogPlus multi device – LON devices 5.9.1 Structure 1404: DS11-I multi device Abstract representation of a DS11-I digital I/O module, horn output module, collective input module or wireless gateway (TeleRex) module.
CS11 Behavior in the DMS7000 5.9.2 Structure 1411: MS9 multi device Abstract representation of a digital I/O module on an MS9i line. See structure 1404 for details. 5.9.3 Structure 1412: AnalogPlus multi device Abstract representation of an AnalogPlus digital I/O module, horn output module, collective input module or one part of a T-Tap device. See structure 1404 for details. 5.9.
CS11 Behavior in the DMS7000 5.10 Hierarchical level: FUNCTION UNIT Function units are devices on the internal bus (I-bus) of a CC11 control unit. Typical function units are: – Line modules – Digital I/O modules – Power supply monitoring units Function units contain parallel information that cannot be combined into one unique state. For this reason the information is mapped to two datapoints (ALARM and STATE). 5.10.
CS11 Behavior in the DMS7000 1301/ALM: Telegram repertoire MESSAGES Sector W W DMS Adr ADF1/2 Sep U/Q N Data A 01 01 Data B 00 85 Priority ALARM NORMAL Text A Alarm Alarm Text B --Reset 1301/ALM: Telegram repertoire COMMANDS Sector W W DMS Adr ADF1/2 Sep R R Data A 01 01 Data B 80 83 Text A Alarm Alarm Text B Acknowledgment (Alarm) Reset Datapoint STATE (STA) 1301/STA: Addressing Sector: BASIC ADF1/2: Based on sequence numb
CS11 Behavior in the DMS7000 5.10.2 Structure 1302: Function unit MS9I Line Abstract representation of an MS9I line. The function unit contains the two datapoints ALARM and STATE. The datapoints appear under the same ADF1/2 address, but with different sector ID. Together this results in a unique datapoint address. Datapoint ALARM (ALM) 1302/ALM: Addressing Sector: FIRE ADF1/2: Based on sequence number 1302/ALM: Valid states State RESET ALARM Description The function unit is not in the alarm state.
CS11 Behavior in the DMS7000 Datapoint STATE (STA) 1302/STA: Addressing Sector: BASIC ADF1/2: Based on sequence number 1302/STA: Valid states State NORMAL FAULTY Description No fault in the function unit. One of the following faults exists in the function unit: - Processor failure - Emergency operation monitoring defective - Line faulty - Line does not respond - Configuration error The detector line has been switched-off.
CS11 Behavior in the DMS7000 5.10.3 Structure 1304: Function unit DS11-A Module Abstract representation of the DS11-A (AnalogPlus) module hardware Datapoint FAULT (FLT) 1304/FLT: Addressing Sector: BASIC ADF1/2: Based on sequence number 1304/FLT: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.4 Structure 1305: Function unit DS11-A Line Abstract representation of a DS11-A (AnalogPlus) detector line. The function unit contains the two datapoints ALARM and STATE. The datapoints appear under the same ADF1/2 address, but with different sector ID. Together this results in a unique datapoint address.
CS11 Behavior in the DMS7000 Datapoint STATE (STA) 1305/FLT: Addressing Sector: BASIC ADF1/2: Based on sequence number 1305/STA: Valid states State NORMAL FAULTY Description No fault in the function unit. One of the following faults exists in the function unit: - Processor failure - Emergency operation monitoring defective - Line faulty - Line does not respond - Configuration error The detector line has been switched-off.
CS11 Behavior in the DMS7000 5.10.5 Structure 1306: Function unit CBA Module Abstract representation of the CBA (scandinavian detector technology) module hardware Datapoint FAULT (FLT) 1306/FLT: Addressing Sector: BASIC ADF1/2: Based on sequence number 1306/FLT: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.6 Structure 1307: Function unit CBA Line Abstract representation of a CBA detector line. The function unit contains the two datapoints ALARM and STATE. The datapoints appear under the same ADF1/2 address, but with different sector ID. Together this results in a unique datapoint address. Datapoint ALARM (ALM) 1307/ALM: Addressing Sector: FIRE ADF1/2: Based on sequence number 1307/ALM: Valid states State RESET ALARM Description The function unit is not in the alarm state.
CS11 Behavior in the DMS7000 Datapoint STATE (STA) 1307/STA: Addressing Sector: BASIC ADF1/2: Based on sequence number 1307/STA: Valid states State NORMAL FAULTY Description No fault in the function unit. One of the following faults exists in the function unit: - Processor failure - Emergency operation monitoring defective - Line faulty - Line does not respond - Configuration error The detector line has been switched-off.
CS11 Behavior in the DMS7000 5.10.7 Structure 1308: Function unit FD20 Line Abstract representation of a FD20 detector line. The function unit contains the two datapoints ALARM and STATE. The datapoints appear under the same ADF1/2 address, but with different sector ID. Together this results in a unique datapoint address.
CS11 Behavior in the DMS7000 Datapoint STATE (STA) 1308/STA: Addressing Sector: BASIC ADF1/2: Based on sequence number 1308/STA: Valid states State NORMAL FAULTY Description No fault in the function unit. One of the following faults exists in the function unit: - Processor failure - Emergency operation monitoring defective - Line faulty - Line does not respond - Configuration error The detector line has been switched-off.
CS11 Behavior in the DMS7000 5.10.8 Structure 1310: Function unit DS11-C line Abstract representation of a DS11-C (collective) line. The function unit contains the two datapoints ALARM and STATE. The datapoints appear under the same ADF1/2 address, but with different sector ID. Together this results in a unique datapoint address.
CS11 Behavior in the DMS7000 Datapoint STATE (STA) 1310/STA: Addressing Sector: BASIC ADF1/2: Based on sequence number 1310/STA: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.9 Structure 1311: Function unit FD20 Module Abstract representation of an FD20 module hardware Datapoint FAULT (FLT) 1311/FLT: Addressing Sector: BASIC ADF1/2: Based on sequence number 1311/FLT: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.10 Structure 1320: Function unit Digital I/O interface Abstract representation of a digital I/O module. 1320: Addressing Sector: BASIC ADF1/2: Based on sequence number 1320: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.11 Structure 1340: Function unit Supply monitoring Abstract representation of a power supply monitoring module. 1340: Sector: ADF1/2: Addressing BASIC Based on sequence number 1340: Valid states State NORMAL FAULTY EMERGENCY POWER OPERATION Description Valid commands No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.12 Structure 1390: Function unit display panel (CI11 only) Abstract representation of a CI11 display panel. This structure is only visible in CI11 control panels. 1390: Sector: ADF1/2: Addressing BASIC Based on sequence number 1390: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.13 Structure 1391: Function unit FBA panel (CI11 only) Abstract representation of a FBA panel (fire brigade control panel). This structure is only visible in CI11 control panels. 1391: Sector: ADF1/2: Addressing BASIC Based on sequence number 1391: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.14 Structure 1392: CC11 VDS Interface Part 1 Datapoint: VDS_FBF (FBF) This datapoint covers the fault signals of the FBF (fire brigade operating panel) and the basic function unit. 1392/FBF: Addressing Sector: BASIC ADF1/2: sequence number based 1392/FBF: Valid states State NORMAL FAULTY Description No faults in the FBF or function unit.
CS11 Behavior in the DMS7000 Datapoint: VDS_FUE (FUE) This datapoint covers the state of the alarm remote transmission (FUE). 1392/FUE: Addressing Sector: FIRE ADF1/2: sequence number based 1392/FUE: Valid states State INACTIVE ACTIVE OFF OFF FAULTY Description The remote transmission (FUE) is ready and in the quiescent state. The FUE is activated. The FUE is switched to test. The FUE is switched-off.
CS11 Behavior in the DMS7000 5.10.15 Structure 1393: CC11 VDS Interface Part 2 Datapoint: VDS_LSE (LSE) This datapoint covers the states of the extinguishing interface (LSE). 1393/LSE: Addressing Sector: EXTINGUISHING ADF1/2: sequence number based 1393/LSE: Valid states State ENABLED ALARM Description Valid commands The extinguishing system (LSE) is ready and in the quiescent state. The LSE is activated. ACKNOWLEDGE RESET The LSE is disabled.
CS11 Behavior in the DMS7000 Datapoint: VDS_FSK (FSK) This datapoint covers the states of the fire brigade key (FSK). 1393/FSK: Addressing Sector: FIRE ADF1/2: sequence number based 1393/FSK: Valid states State NORMAL SABOTAGE Description The key box (FSK) is ready and in the quiescent state. The FSK is tampered.
CS11 Behavior in the DMS7000 5.10.16 Structure 1395: Function unit EXTINGUISHING control module Abstract representation of an EXTINGUISHING control module. 1395: Sector: ADF1/2: Addressing BASIC Based on sequence number 1395: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.10.17 Structure 1396: Function unit LON interface Abstract representation of a LON network module 1396: Sector: ADF1/2: Addressing BASIC Based on sequence number 1396: Valid states State NORMAL FAULTY Description No fault in the function unit.
CS11 Behavior in the DMS7000 5.11 Hierarchical level: STATION The following devices are Stations on the C-bus: – – – – CC11 Control units CI11 Compact control units (CC11 and CT11 integrated on the same hardware) CT11 Display terminals CK11 DMS7000 Gateway Stations contain parallel information that cannot be combined into a unique state. For this reason the information is mapped to several datapoints. 5.11.1 Structure 1201: CC11 Control unit Abstract representation of a CC11 control unit.
CS11 Behavior in the DMS7000 Datapoint CONTROL UNIT (CTP) 1201/CTP: Addressing Sector: BASIC ADF1/2: 0003 1201/CTP: Valid states State NORMAL FAULTY Description No fault exists in the station One of the following faults exists in the station: - Emergency operation monitoring defective - C-Bus fault - I-Bus fault - Configuration error Valid commands ACKNOWLEDGE 1201/CTP: State transition diagram To From FAULTY FAULTY NORMAL --- È Fault -------------N 33 3C --- Ç Fault -------------U 33 46 NORMAL 12
CS11 Behavior in the DMS7000 Datapoint PRINTER (PRT) 1201/PRT: Addressing Sector: BASIC ADF1/2: 000D 1201/PRT: Valid states State NORMAL OFF FAULTY Description The printer is switched on and there is no fault. The printer is switched off. One of the following faults exists in the printer: - XOFF or DTR Timeout - End of paper - Printing mechanism blocked.
CS11 Behavior in the DMS7000 Datapoint DEVICE CONFIGURATION (DVC) 1201/DVC: Addressing Sector: BASIC ADF1/2: 000E 1201/DVC: Valid states State NORMAL Description No detection device configuration is in progress. Valid commands --- IN_PROGRESS - Detection device configuration is in progress. The configured application parameter sets are downoaded to the detectors. - --- 1201/DVC: State transition diagram FAULTY NORMAL --- È Device config. Ç Device config.
CS11 Behavior in the DMS7000 5.11.2 Structure 1205: CS11 Connection Abstract representation of a CT11 or a CK11 connection to the local CK11.
CS11 Behavior in the DMS7000 5.11.4 Structure 1213: CK1142 Gateway Abstract representation of a CK11 gateway. The station contains the datapoints: – – – – ALARM GATEWAY DMS7000 NETWORK C-BUS Datapoint ALARM (ALM) 1213/ALM: Addressing Sector: FIRE ADF1/2: Based on sequence number 1213/ALM: Valid states State RESET ALARM Description Valid commands The function unit is not in the alarm state. Emergency operation alarm. An alarm has been signalled via the ACKNOWLEDGE emergency operation system.
CS11 Behavior in the DMS7000 Datapoint GATEWAY (GWY) 1213/GWY: Sector: ADF1/2: Addressing BASIC 0003 1213/GWY: Valid states State NORMAL FAULTY Description No fault exists in the station One of the following faults exists in the station: - Emergency operation monitoring defective - I-Bus fault - Configuration error Valid commands ACKNOWLEDGE 1213/ GWY: State transition diagram To From FAULTY FAULTY NORMAL --- È Fault -------------N 33 3C --- Ç Fault -------------U 33 46 NORMAL 1213/ GWY: Telegra
CS11 Behavior in the DMS7000 Datapoint DMS7000 NETWORK (NET) This datapoint relates to the DMS7000 communication interface of the CK11. 1213/NET: Addressing Sector: BASIC ADF1/2: 0008 1213/NET: Valid states State NORMAL FAULTY Description No DMS7000 network fault exists in the station. The station has detected the failure of a data link of the DMS7000 (CERLOOP) network.
CS11 Behavior in the DMS7000 Datapoint C-BUS (BUS) This datapoint relates to the C-BUS interface of the CK11. 1213/BUS: Addressing Sector: BASIC ADF1/2: 0009 1213/BUS: Valid states State NORMAL FAULTY Description No C-Bus network fault exists in the station. The station detected a fault in the C-Bus network.
CS11 Behavior in the DMS7000 5.12 Polling Procedure To initialize the process image in the management system after a communications failure, the individual CC11 control units must be polled. Rules: z A special set of telegrams has been defined for the polling sequence. z The polling sequence is typically used when a control unit is signalled signed back onto the network, or when the management system is started.
CS11 Behavior in the DMS7000 Polling sequence Management system Polling CK11, Sector Z Telegram CS11 station Z8600000R5355Î Z8600000R5352Î Polling CC11 No.1, Sector Z Polling CC11 No.1, Sector W Polling CC11 No.1, Sector P Polling CC11 No. 2, Sector Z Polling CC11 No.
Examples 6 Examples The following examples show typical events and how they are processed. 6.1 Alarms 6.1.
Examples 6.1.2 General alarm in day mode Assumptions: CC11 with DMS address 111, organization DAY mode, operation before expiration of CAC. CC11 Telegram Detector generates danger level = 2 W1110B33U033AÎ (Pre-alarm state) W1110B6BQ674FÎ (Command acknowledgment warn- ÍW1110B33R0389 ing) ‘Warning’ state is acknowledged W1110B33Q033AÎ Management system (Warning) (Element active) Warning is acknowledged by operator. Detector generates danger level = 3 (alarm state). CAC-V1 starts.
Examples 6.1.3 General alarm in night mode Assumptions: CC11 with DMS address 111, organization NIGHT mode. CC11 Detector generates danger level = 3 (Alarm-State) Telegram W1110B33U033AÎ W1110B6BQ674FÎ W1110B33N033BÎ W1110B33U0101Î W1110B30Q0101Î W111A1CDQ0500Î W111A1CDQ0600Î W1110277U7A4FÎ W1110278U734FÎ W111027EQ094FÎ Management system (Warning) (Element active) (Warning end) (Autom.
Examples 6.1.4 Extinguishing sequence Assumptions: CC11 with DMS address 111, extinguishing system triggered by automatic detectors CC11 1st detector generates danger level = 2 Telegram L11103B1U033AÎ L11103B4Q674FÎ Management system (Warning) (Detection device active) 1st detector generates danger level = 3 L11103B1N033BÎ L11103B1U0401Î L111B6EBU0400Î W111A4CDQ0500Î W111027EU7A4FÎ (Warning end) (Pre-alarm autom.
Examples 6.2 Faults 6.2.1 Detector fault Assumptions: CC11 with DMS address 111, organization DAY mode, operation before expiration of fault CAC. CC11 Detector faulty (Fault acknowledgment command) Telegram Management system W1110B6BU6746Î (Detection device faulty) W111A1EDQ743AÎ (Collective fault area 1) ÍW1110B6BR6786 Fault is acknowledged by the operator ‘Fault’ state is acknowledged W1110B6BQ6746Î W1110B6BN673CÎ W111A1EDN743BÎ Detector in normal state 6.3 Others 6.3.
Examples 6.3.3 Switching a detection zone to TEST Assumptions: CC11 with DMS address 111 CC11 (Off Command) Telegram Zone x in test state. Affiliated detector is activated = Test Alarm on element level. Affiliated detector automatically returns to the normal state. (On Command) Zone x is switched on. ÍW1110B33R6457 W1110B33Q6457Î W111A1ECQ753AÎ W1110B6BQ670BÎ Management system Zone x is switched to test by the operator.
Terminology and abbreviations 7 Terminology and abbreviations AlgoRex® Area C-Bus CAC CBD CC11 CK11 CT11 D-Bus DBD Device DMS7000 network Element Function unit I-Bus IBD Logical tree Physical tree Section SeqNr Station StrucNr Zone 8 Registered trade name for the CS11 fire detection system The system behaviour is determined by the two alarm organizations “Day” and “Night”. All system components that are controlled by a common alarm organization belong to the same Area.
Keyword index CK11 gateway, 11, 109, 113, 114 configuration file, 11, 12, 14, 15, 73, 74, 75, 113 CSXLevel, 14 CSXNumber, 15 D data structure, 17 Device, 10 DMSAdf12, 15 DMSSector, 15 E Element, 9 EXCEL, 12 F FplanNr, 15 Function unit, 10 I R RecordNr, 14 RecordType, 14 S Section, 9 SECTION, 25, 30 Sector field, 11 SeqNr, 14 sequence number, 10, 11, 14, 25, 30, 32, 34, 37, 38, 40, 43, 46, 49, 51, 52, 53, 55, 56, 58, 59, 61, 63, 64, 65, 67, 68, 69, 70, 71, 73, 74, 75, 77, 79, 80, 81, 82, 83, 84, 85, 86
Siemens Switzerland Ltd Industry Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 11 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. A6V10089060_a_en Edition 3.