User Manual

Configuring MK8000
4
Setting vitality
58
Building Technologies A6V10062407_a_en
Fire Safety & Security Products 30.06.2013
3. Select the serial Channel node (by default
Channel
).
4. Add the required drivers by clicking the corresponding icon on the left.
-
NS8010 Cerloop/ISO1745
-
NS8012 CDI-Net
-
NS8210 NK8000
-
NS8015 CNDL
-
NS8014 SI410
-
NS8011 BACnet
-
NS8013 SPC
On the MK8000 FEP station you can also add serial drivers as previously described
and then connect them (drag & drop) to the Channel node of the Stand-alone station.
Dragging the FEP driver to the Channel node
4.4 Setting vitality
The vitality timer defines the maximum time between telegrams received from the
subsystem. Recommended vitality is 50 seconds (maximum 90 seconds). Setting the
vitality is recommended when using GW20 or GW21. It is mandatory when connecting
a CS11 directly to the MK8000.
Note: Setting the vitality timer is mandatory when connecting a CS11 directly to
MK8000, while it needs to be ‘0’ when a CS11 is connected via MK7022 to the
MK8000.