MM8000 MP4.
Data and design subject to change without notice. / Supply subject to availability. © 2008 Copyright by Siemens Switzerland Ltd We reserve all rights in this document and in the subject thereof.
Introduction 1 1.1 1.2 Introduction .............................................................................................4 MP4.10-01 at a glance ..............................................................................4 MP4.10 at a glance ...................................................................................4 2 2.1 2.2 2.3 2.3.1 2.3.2 What’s new in MP4.10 releases .............................................................6 MP4.10-01 bug correction............................
Introduction 1 Introduction The new MM8000 software release MP4.10-01 is available. These release notes provide the characteristics of the new software, including bug corrections and known issues. We recommend that users carefully read this document before installing and using the software. This document includes and replaces the release notes published for MP4.10. 1.1 MP4.10-01 at a glance MM8000 MP4.10-01 is a bug-correction service release for latest complete setup (MP4.10).
Introduction Visibility and command permissions associated to user groups have been reor- ganized and make consistent between treatment and plant browser. Composer MP4.10 provides a structured toolbar and allows configuring both 3.20 and 4.10 projects. An import command is available to recreate the DMS7000 tree in Composer automatically. Improved support of redundant server configuration with station fault events. Transactions (e.g.
What’s new in MP4.10 releases 2 What’s new in MP4.10 releases This section presents the enhancements provided in the new MM8000 software, starting from MP4.10, compared with previous MP3.20-xx. 2.1 MP4.10-01 bug correction ID Description Notes 8154 Problems in CC11 imported texts could occur, e.g. position of brackets. Also corrected in MM8000 MP4.10 Hotfix #01 8560 NK822x line diagnostic messages could be missing in MM8000.
What’s new in MP4.10 releases assisted treatment procedure to block (select the grid view and double click the event icon to enter the advanced treatment). MM8000 MP4.10 Hotfix #05 8677 In dual screen settings, starting the History browser erroneously resulted in the Event List being minimized. 8680 The thick border frame (new in MP4.10), which indicates the alarmed point on the screen, was not properly represented on the alarm printouts (still in MP3.20 style).
What’s new in MP4.10 releases 2.2 MP4.10 features PC client functions DMS8000 used to provide an OPC server option (MK8000). OPC client functions are available for connecting to OPC servers and communicating with control units via OPC protocol. Both a “light” and a “full” integration are possible. “Light” integration comes with the standard product, and requires a more careful engineering than typical MM8000 subsystems but no software code development.
What’s new in MP4.10 releases Transactions and VB scripts in reactions and sequences Transactions can be included in reaction triggers and in sequence programs. When occurring (instantaneously), the transaction is evaluated during a programmable period of time (Transaction time) that allows other conditions (e.g. alarm states or other transactions) to happen and be tested along with the transaction. Organization modes can be included in triggers + effects of reactions and in sequence programs.
What’s new in MP4.10 releases SI410/420 Sintony upload via NK882x Configuration upload from SI410/420 Sintony used to be available only via a direct serial link to the control unit. Starting from MP4.10,. this is also possible through the NK882x connection line. Motion Detection (MD) events from SISTORE CX MD should be consistently configured in CX Config and MM8000 Composer (motion and sabotage detection in the CX camera nodes).
What’s new in MP4.10 releases 2.3 Summary of connectivity options Network Notes Further info.
What’s new in MP4.10 releases Control units Notes about latest version supported EP7F Z2.1 (V7.8x) CS11 AlgoRex® EP5 and EP7 FC700A CS1115 Phase 4 FC330A Phase 4 SIGMASYS D100 STT11 Connectivity and configuration notes Direct link, Cerloop, and NK8000 Direct link CISxx8.86 SIGMASYS V40-2 D100 V3.
What’s new in MP4.10 releases 2.3.1 SiPass The following table shows the compatibility between MM8000 and SiPass versions: Compatibility matrix: MM8000 SiPass 2.2 SiPass 2.3 SiPass 2.3 SiPass 2.35 SiPass 2.35 SiPass 2.35 Build 18 Build 21 Build 31 Build 38 Build 41 MP3.15 Yes No No No No No MP3.15-01 No Yes No No No No No No Contact support (*) No No No MP3.20 No No Yes No No No MP3.20-01/-02 No No No Yes Yes Not tested MP3.20-03/-04 No No No Yes Yes Yes MP4.
What’s new in MP4.10 releases 2.3.2 Video All models of the SISTORE Digital Video Recorders are supported in various software versions: please refer to the compatibility matrix provided below and to the corresponding known issues described on page 25. Video device model Video device version MM8000 Version / type SISTORE AX V2.4.0 MP3.15, 3.15-01/-02, 3.20, 3.20-01/02/-03/-04, 4.10, 4.10-01 V2.5.0 MP3.15, 3.15-01/-02, 3.20, 3.20-01/02/-03/-04, 4.10, 4.10-01 V2.6.0 MP3.15, 3.15-01/-02, 3.20, 3.
Installation and configuration procedures 3 Installation and configuration procedures 3.1 Software installation MM8000 MP4.10 is distributed with a complete and assisted setup procedure. For detailed information about the installation procedure, refer to the MM8000 ICC manual (document no. A6V10062413_a_en). 3.1.1 New systems: installing MP4.10 and then 4.10-01 Assuming a stand-alone MM8000 station, the MP4.10 installation procedure includes the following steps: 1. Check system requirements.
Installation and configuration procedures – – Make sure that no MM8000 client applications (including Composer and Simulation tools) are active. Copy the MP4.10-01 setup on a local drive, e.g. in the folder: C:\MM8000_MP4.10-01\... – Launch the command: Fix_MM8000 MP4.10.01.exe that upgrades all the software components. 8. Install the hardware key and enter the license code using the PAK Manager tool. Note that SiPass also requires a license option (Management Station Integration).
Updating from older releases 4 Updating from older releases 4.1 Software License All previous Composer and MM8000 licenses must be updated to MP4.10. Also, note that Service Keys whose contract expired in 2006 or earlier will not work with MP4.10 software. Those keys can no longer be used and need to be replaced by new service keys to be obtained opening new Composer contracts through standard sales channels. 4.
Updating from older releases 11.If SiPass is used, align the access control configuration. Different procedures are required depending on the database versions: – [Database 3.15-01 and earlier only] the SiPass node in the Composer tree must be deleted and then created again (note that the deletion will force you to reconfigure the access control points in maps, reactions, sequences, etc.). – [Database 3.15-02 and later] the alignment of the access control configuration is required.
Known issues in MP4.10 5 Known issues in MP4.10 This is a list of known limitations, problems, bugs and recommended practises at the time this software was released. Compared with previous Release Notes, new and updated points are marked by a side label for easier identification. 5.1 Installation MS Windows Vista Vista is not supported, yet (planned for MP4.15 in 2008). New in MP4.
Known issues in MP4.10 Clear History DB Rare cases of difficulties in the history functions have been reported after installation. In such cases, the FS-DMS support may recommend the use of the program: \Utilities\ToolsUtilities\EngineeringTools.exe This can clear (and optionally also resize) the database and solve the problem. Video applications Video applications require specific software (viewers and other utilities) to be installed before MM8000.
Known issues in MP4.10 5.2 Configuration Download failures Repetitive download attempts may cause failures. In this case, close Composer after each download and then reopen it. Also try the ‘Empty_DB’ procedure (see \Utilities\ToolsUtilities\EngineeringTools.exe). Opening previous release projects – – MM8000 MP3.15 projects: when opening a large (e.g.: 13,000 or more Composer nodes) MP3.15 project in Composer for the first time, please allow up to 50 minutes. MK8000 MP3.
Known issues in MP4.10 – – – – – – – 1552 - Digital output supervised; 1560 - Internal horn; 1561, 1564, 1565 - External horn; 1562 attribute = RTFIRE - “Alarm” remote transmission channel; 1562 attribute = RTFAULT - “Fault” remote transmission channel; 1562 attribute = RTOTHER - “Other” remote transmission channel. “Move” function in AlgoRex tool: the AlgoWorks “move” function, which allows CC11 objects to be moved in the tree structure, is not fully supported in MM8000 tools (ref. defect #5521).
Known issues in MP4.10 “Low virtual memory” error message to display. Should that occur, you can adjust the virtual memory size (i.e. the size of the paging file where Windows swaps the active memory areas on disk). Using the Administrator login, proceed as follows: – – Start Settings Control Panel System Advanced tab Performance Options Virtual memory “change” button.
Known issues in MP4.
Known issues in MP4.10 From MM8000, select ‘Change Server’ in the Composer Properties Management window, and select the SiPass server to connect. USB Printers If a USB printer reports a fault condition in MM8000, try to remove the Bidirectional Control option in the printer properties page. Please follow this procedure: 1. Open the USB printer properties window (see picture below). 2. Select the "Ports" tab. 3. Uncheck the option "Enable bidirectional support". 4.
Known issues in MP4.10 1. The SISTORE MX 2.55 must be used with the remote player of SISTORE MX 2.57 or later. 2. The archive player shows the control buttons (e.g. Play, Stop, Rewind, etc.) on the very right of the screen and therefore they are not visible most of the time. Note: The Replay Toolbar (WC1) in SISTORE MX 2.
Documentation 6 Documentation All documents were updated to include the new features added in MP4.10. Note the document numbers related to the new STEP numbering. STEP documentation repository On the Siemens intranet, the product documentation can be found in the STEP Documentation Repository. The STEP Web Client interface is available at the following address: https://intranet.sbt.siemens.com/dbcom/en/db_porta/client.asp The following describes one way to search and find a document: 1.
Documentation Tender Specifications (document no. A6V10062419_a_en) This document is in the standard Siemens format, but it is designed for use and adaptation(s) by independent contractors responsible for selecting and managing the installation and upgrades of a security system for the final customer. Offer Template (document no. A6V10062429_a_en) This is intended as an aid for sales people in the preparation of initial and final offers. 6.
Documentation – – Graphical maps (document no. 008906_b_en) Composer Configuration (document no. A6V10067783_a_en) Release Notes (document no. A6V10062509_b_en) This document. It includes all information concerning MP4.10-01. 29 Building Technologies Fire Safety & Security Products 073_DMS_MM8000_Release_Notes_MP4.10-01_A6V10062509_a_en.doc 01.
Documentation 6.2.1 MP4.10 documentation errata Network, Fire, and Intrusion Connectivity Guide (A6V10062425_a_en) Section 3.3.3.2, pag.51, Connecting NK822x to the DMS. In case of BACnet link, please note that the connection is made between the main NK8225 node (and not the Ethernet node) and the NS8011 driver. Also, in this case, the BACnet parameters shown in the node tab of the NS8011 (and not documented) must be configured as follows: New in MP4.
Documentation Section 3.3.3.2, pag.52, Connecting NK822x to additional DMS hosts. In comparison with NK8222/NK8223, the new NK8225 requires a different technique in Composer to configure the connections to multiple management station hosts. Specific nodes, representing the host systems, can be added from the Network menu (see picture below). In the menu, select the option DMS8000 host (BACnet). New in MP4.
Documentation New in MP4.10-01 (MM8000 ICC, Printer folder) New in MP4.10-01 (Datasheet, License information) MM8000 Installation, Configuration, and Commissioning Manual (A6V10062415_a_en) Section 4.3.1, pag.39, fig 56: Setting up printers In step 2, the procedure indicates to select a “print folder” that no longer exists. Please ignore this step. MM8000 Datasheet (A6V10062415_a_en) “Details for ordering" section, pag.9, Option list The option list in the Note no.
Customer support links & resources 7 Customer support links & resources 7.1 Siemens BT FS Updated in MP4.10-01 7.2 Our Customer Support Center intranet site at: https://intranet10.sbt.siemens.com/about_bt/Business_Units/fs/Customer+Support+ Center/?languagecode=en provides useful information and links. In the Online Support section of this intranet page, software downloads and known product issues can be found in the PSP (password-protected Product Support Platform). The support mailbox is: fs.
Appendix A: NICE support 8 Appendix A: NICE support 8.1 Introduction NICE DVR units are supported in MM8000 MP4.10-01 by means of an Add-on package. Supported features include the motion alarm detection as well as the video integration in event treatment, plan navigation, and history search. Supported models and limitations Current limitations: Supported NICE models: Alto, Pro, NVSat, NVR9000 Maximum number of connectable DVR units is 150. Maximum number of AMS Server is 4.
Appendix A: NICE support However, you can also safely install MM8000 first and then NICE software. In this case, however, use the Init_CCTV utility to customize the NICE files afterwards. For information about about Init_CCTV, refer to section 3.4.10.1 (Program utilities) of the MM8000 ICC, doc.no. A6V10062413_a_en. Add-on installation procedure 1. Make sure that no MM8000 client applications are active. (including Composer and Simulation tools). 2. Copy the Add-on setup files on a local drive, e.g.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. Edition A6V10062509_b_en 01.