MK8000 OPC Server Interface Specification for STT11CPU Building Technologies Fire Safety & Security Products
Building Technologies Fire Safety & Security Products Data and design subject to change without notice. / Supply subject to availability. © Copyright by Siemens Switzerland Ltd We reserve all rights in this document and in the subject thereof.
Building Technologies Fire Safety & Security Products STT11CPU STT11 CPU is the main unit of the STT11 system, designed for performing automatic actions (called `fire actuations`) following the detection of a fire alarm. It is made up of a physical and logical tree. The physical component list includes the physical control unit with power supply, the I/O boards, and the local operating terminal. The fire system is logically organised in a 4-level structure similar to the one used by AlgoRex.
Building Technologies Fire Safety & Security Products STT11 Application - ( GSNOAPMN ) The `STT11 Application` object represents the entire STT11 and the geographical area covered by the fire protection. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Unidentified event - ( SYNOUDGE ) The `unindentified event` indicates the conditions which could not be associated with any known object in the current structure.
Building Technologies Fire Safety & Security Products Control unit - ( HWNOCCUD ) The `Control unit` object presents the possible faulty conditions related to the STT11 control unit and to the general health of the physical subsystem. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present.
Building Technologies Fire Safety & Security Products Power supply - ( HWNOPSGE ) The `Power supply` object represents the possible faulty conditions of the battery-backed up power supply unit. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1999 Fault Ack A faulty condition has been detected in the power supply module and has been acknowledged.
Building Technologies Fire Safety & Security Products I/O Board - ( HWNOIBGE ) The `Power supply` object represents the possible faulty conditions of the input/output boards. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1999 Fault Ack A faulty condition has been detected in the STT11 Input/Output board and has been acknowledged.
Building Technologies Fire Safety & Security Products Terminal - ( HWNOCTGE ) The `Terminal` object represents the conditions of the local panel. Multistate Commands 1-Ack 1000 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Quiet No abnormal condition present. 1999 Fault Ack A faulty condition has been detected in the STT11 terminal and has been acknowledged.
Building Technologies Fire Safety & Security Products Area - ( GSDEARGE ) The `Area` object represents the geographical area covered by the fire protection. The area is divided into a number of sections.
Building Technologies Fire Safety & Security Products Security function - ( GSDEZOGE ) The `Function` object represents a set of control actions to be performed on a physical device, e.g. closing a door, opening a valve, etc. The functions are logically made up of a number of elements.
Building Technologies Fire Safety & Security Products 1999 Fault Ack A faulty condition has been detected in one of physical components involved in the function; a fault can be detected internally in the STT11 and via the missing/erroneous start/finish activation feedback; the event has been acknowledged.
Building Technologies Fire Safety & Security Products Element - ( GSDEDEGE ) The `Element` object represents the conditions related to a the control outputs and state inputs of a physical device, such as a door, a valve, etc.
Building Technologies Fire Safety & Security Products Input element - ( IOCOINGE ) The `Input element` object represents the conditions of a single sensor in a function object (such as a sensor in a fire door). Multistate Commands 1-Ack 950 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active The element is active. 1000 Quiet The element is not active.
Building Technologies Fire Safety & Security Products Output element - ( IOCOOUGE ) The `Output element` object represents the conditions of a single actuator for a function object (such as automatic closing of a fire door). Multistate Commands 1-Ack 950 2-Reset 4-Arm 8-Disarm 16-Test 32-Active 64-Quiet 128-Disc 256-Conn 512-Block 1024-Man 2048-Status Active The element is active. 1000 Quiet The element is not active.
Building Technologies Fire Safety & Security Products Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. 007081_d Edition STT11CPU - Version 01.