User Manual

Modbus Interface Specifications
2
Modbus Data Model
35
A6V10316242_a_en
31.05.2019
tables are word input registers containing a simplified status representation. In
fact, each representation is made up of 4-bit status for functions or 2-bit status
for elements. This results in 4 or even 8 objects being packet in a single word
register, thus allowing a faster acquisition whenever communication
performances have priority than status details.
The compact tables list includes:
Functions
Elements
Bit status tables
For extremely simple applications, a set of bit input registers is also provided
for specific objects and events that are combined in very basic 1-bit (on/off)
status report. The list of bit input registers includes:
Panel Fault
Activation Mode Fault
Activation Mode Abnormal
Communication Link Fault
Mains Fault
Battery Fault
Function Safety Position Failed
Function In Command
Function Wait Position Failed
Function Fault
UGA Alarm
UGA Activated Evacuation
UGA Fault
BOP Evacuation Mode On Manual
Command tables
The output command tables (read/write holding registers) enables Modbus
master/client stations to initiate control commands to the fire control panels.
Note that, depending on a configuration setting, certain commands may not be
available.
The command tables list includes:
Panel acknowledgement
Panel reset
Buzzer acknowledgement
Buzzer reset
Function activation command
Evacuation command
Date and Time
See Summary Table [➙ 18].
Gateway Unit Representation
A dedicated register sub-map is used for the NK823x unit, including one status
table.
Status table
This is a word input register reporting the conditions of the gateway. Each word
corresponds with one object and is organized in two bytes: bits 0-7 are used to
represent the object operating modes, for example the on/off
(inclusion/exclusion) conditions, whereas bits 8-15 contain the abnormal event
conditions, such as alarms, fault, and so on.
The gateway table includes the following:
NK823x Points
Power Supply