User Manual

2
Modbus Interface Specifications
Modbus Data Model
42
A6V10316242_a_en
31.05.2019
UGA
Unité de Gestion d’Alarme
(evacuation control unit)
WT_UGA (Input register, default base address: 7000)
Bit
Information
Notes
0 (lsb)
Non-default mode
Abnormal mode resulting in a reduced safety
1-5
-
Not used
6
Evacuation activated
7
-
Not used
8
Non-default value
Evacuation activated without fault
9-12
-
Not used
13
Fault
14
-
Not used
15
Alarm
Alarm received
BOP Evacuation Mode
WT_BOPEvacuationMode (Input registers, default base address: 7500)
Bit
Information
Notes
0 (lsb)
Non-default mode
Abnormal mode resulting in a reduced safety
1-4
-
Not used
5
Manual (OnManual)
Manual mode
6-7
-
Not used
8
Non-default value
Manual mode
9-15
-
Not used
Horn
WT_Horn (Input registers, default base address: 7700)
Bit
Information
Notes
0 (lsb)
Non-default mode
Abnormal mode resulting in a reduced safety
1-6
-
Not used
7
Disabled
8
Non-default value
Disabled
9-15
-
Not used
Element Standard / Power supply elements
WT_Element (Input registers, default base address: 8200)
Bit
Information
Notes
0 (lsb)
Non-default mode
Abnormal mode resulting in a reduced safety
1-7
-
Not used
8
Non-default value
Abnormal condition resulting in a reduced safety
9-11
-
Not used