MM8000 OPC Connectivity Configuration Guide
Fire Safety & Security Products
06.2007
2 Configuration of generic OPC subsystem
2.1 Overview
The entire configuration related to control units connected to MM8000 via an OPC
server is defined in Composer.
The OPC configuration in MM8000 includes 3 main logical steps:
1. Definition OPC items provided by the OPC server
In Composer, MM8000 can support an OPC Driver (NS8019) that can connect
to one or more OPC servers.
For each server, the NS8019 driver can handle a set of OPC items, defined in
Composer by importing a CSV file (recommended), or browsing in the Server
address space and selecting the required items, or entering the list of OPC
items manually.
2. Definition of the subsystem(s) and related points
The subsystem representing the OPC control unit can be added in the
Composer tree in the same way as other types of units.
In the subsystem, you can then add the required number of data points, repre-
senting in MM8000 the physical and logical entities provided by the OPC items.
Composer can support typical safety and security objects (e.g.: zones, doors)
and well as general purpose objects (e.g. inputs, outputs, generic objects).
Note that the use of system templates can remarkably help you in performing
this step whenever the same structure of points and folders can be used more
than once. Once a reusable structure is built up, you can save as template and
add it again with a simple mouse click. The template is stored in the local Com-
poser and applicable on any other project.
3. Link between subsystems points and OPC items
OPC items and the subsystem points are finally linked in order to enable
the communication mechanism. In the link, you have to set the logical rule that
applies to the actual value or information when it is moved from OPC into
MM8000. A number of Item classes are available for this purpose and main-
tained by a dedicated engineering tool (OPCXMLeditor).
Each item class deals with data types and format and defines the way states,
commands, and transactions are interpreted in the OPC items and then handled
by MM8000.