MM8000 MP2.
Data and design subject to change without notice. / Supply subject to availability. © 2004 Copyright by Siemens Building Technologies AG We reserve all rights in this document and in the subject thereof.
1 Introduction .............................................................................................3 2 2.1 What’s new in MP2.31.............................................................................4 New networks & subsystems supported...................................................4 2.1.1 Networks & connectivity supported......................................4 2.1.2 Subsystems supported ........................................................4 Changes to functionality and features ....
Introduction 1 Introduction These release notes provide information on the latest MM8000 MP2.31 software delivery. In this release, MM8000 has been further enhanced to provide a higher level of functionality, performance, and reliability. This document covers the following topics: Differences between MP2.31 and the previous market package.......................... p. 4 Information about how to migrate to MP2.31 from the previous release ............ p.
What’s new in MP2.31 2 What’s new in MP2.31 This section details the differences between the new MM8000 MP2.31 and the previous MP2.30. 2.1 New networks & subsystems supported This section lists the entire set of network and subsystem devices that can be connected to MM8000 MP2.31. 2.1.1 Networks & connectivity supported The following network configuration types are supported: – – – Cerloop – same as 2.30. CDI-Net – same as 2.30. NK8000 (CDI-WAN) – New features in MP2.31 see p.5.
What’s new in MP2.31 2.2 Changes to functionality and features This section presents the new features in MP2.31 that can have the most beneficial impact on the market. Further detailed improvements and resolved issues are given in the form of a technical report in chapter 4 at p.18. 2.2.1 General improvements Product reliability The long-term reliability of MM8000 has been improved addressing various defects related to memory management.
What’s new in MP2.31 2.2.4 Subsystems Philips/Burle CCTV MM8000 MP2.31 can now support the LTC8000 family of switchers via NK8000 MP2.11 networks. Note that the MM8000 connectivity solution to Philips/Burle applies only to NK822x MP2.11 and it is technically not compatible with older Burle solutions for LMS over CDI-NET network. In other words: Old CDI-NET options for Philips/Burle are compatible with LMSmodular only. New NK8000 options for Philips/Burle are compatible with MM8000 and MK8000 only.
What’s new in MP2.31 2.2.5 History Browser History report printouts Printing out the reports resulting from archive queries is now possible. See 006798 MM8000 MP2.31 Operation Manual. Preferred column setting in the report view A preferred column-width setting can now be quickly selected for best data visibility of the report lists. See 006798 MM8000 MP2.31 Operation Manual. 2.2.6 Printing More journaling layouts New journaling templates are now available (ref. #5240).
What’s new in MP2.31 2.2.8 Licensing License PAKs MM8000 MP2.31 requires the PAK codes 2.3. Older licenses should be upgraded to 2.3. Please be aware that, unlike previous MP2.
What’s new in MP2.31 For more details on the MM8000 license options, please refer to the DMS price policy document and to the related MM8000 Project Sheet (see intranet site: http://www.cdi.cerberus.ch/products/salespolicies/prod-sale-curr.asp, password required). See key installation notes at p.10. See 007083 DMS8000 Connectivity Configuration Guide.
What’s new in MP2.31 2.3 Changes to installation / configuration procedures 2.3.1 Installation Windows 2000 version Window 2000 requires service pack 4 (SP4). Also, security patches provided by Microsoft (e.g. KB823980) are recommended. See links to Microsoft web site in section 7.2 at p.29. Hardware key (dongle) driver MP2.31 includes new drivers for the Sentinel keys. However, there are a few important issues that you need to be aware of: 1.
What’s new in MP2.31 2.3.2 Configuration Composer version MM8000 MP2.31 comes with Composer version 2.03-01. This version of Composer can be used to configure MK8000 MP1.31 and MT8000 MP1.20 projects as well (plug-ins are obviously required), but not to download MT8001/MT8002 terminals. Download Incremental download is much faster and should always be used after the first complete download. The improvements concern both the modifications to points and maps.
Migrating from previous releases to MP2.31 3 Migrating from previous releases to MP2.31 3.1 Migrating from MP2.10/MP2.20 The migration from release MP2.10 and MP2.20 is possible as described in this chapter. You will need to follow this procedure: 1. Before starting any activity, check the installation requirements and the necessary license for MP2.31. See document 006799 “MM8000 Installation Configuration & Commissioning guide”. 4 Project Administrators 3 Backup Operators 2.
Migrating from previous releases to MP2.31 4. Restart the computer. 5. Verify that the folder (by default C:\MM8000) has been deleted as well. If not, manually delete it. 6. Follow the installation instructions detailed in the document 006799 “MM8000 Installation Configuration & Commissioning guide”. 7. If required, install the translated texts as described in 007875 “MM8000 Localisation Guide”. If you need to migrate MP2.30 texts, see 3.3.1 at p.16. 8.
Migrating from previous releases to MP2.31 15. After that, using the form prepared at step 0 above, check and possibly correct the “Client settings” associated to each user group. 16. If the projects include graphic maps, you will need to update their format. Select the node “Graphic maps” and click ‘Update’ 17. The update procedure will proceed for some minutes, depending on the size of the project. Wait for the procedure to complete. 18. Close Composer. 19.
Migrating from previous releases to MP2.31 3.3 Migrating from MP2.30 The migration from release MP2.30 is possible as described in this chapter. You will need to follow this procedure: 1. Before starting any activity, check the installation requirements and the necessary license for MP2.31. See document 006799 “MM8000 Installation Configuration & Commissioning guide”. 2. Uninstall the previous MM8000 program using standard Windows procedure. 3. Restart the computer. 4.
Migrating from previous releases to MP2.31 3.3.1 Migrating localized text from MP2.30 to MP2.31 Referring to the Catalyst translation environment for MM8000 (see 007875 “MM8000 Localisation Guide”), the list below contains the strings that have been modified in MP2.31 in comparison with MP2.30. +---MM8000 | +---Client | | AMResource.dll | | DialerResources.dll | | EBRResources.dll | | ETRepRes.dll | | ETResources.dll | | EventDescRes.dll | | FWResource.dll | | | | | | | | HBResource.dll MapResources.
Migrating from previous releases to MP2.31 | | | | | | | | | | | | | | | | | | | | | | | | | | | | CF9000Res.DLL | | CF9000systemRes.DLL | | CK11EP7Res.DLL | | CK11Res.DLL | | CS11EP7Res.DLL | | CS11Res.DLL | | CS440Res.DLL | | CS4Res.DLL | | CZ10Res.DLL | | CZ12Res.DLL | | DMS7000Res.DLL | | GuartoRes.DLL | | SimatrixRes.DLL | | SK11Res.DLL | | STT11Res.DLL | | STT11SystemRes.DLL \---System DixieMainResources.DLL GenericNodeSTRes.DLL HistorianSTRes.DLL JSTRes.DLL PrinterSTRes.DLL StationSTRes.
Corrections and improvements in MP2.31 4 Corrections and improvements in MP2.31 This chapter provides a detailed report on the issues resolved as well as on detailed improvements in MP2.31. Be aware that the most severe issues in MP2.30 have been already addressed by specific service releases (fixes #2.30-01 and #2.30--02), which are now fully integrated into MP2.31 software. However, MP2.
Corrections and improvements in MP2.31 # 4597 4876 4056 4981 5043 5077 5086 Function User interface (Symbol colour) User interface (Audio) User interface (NK822x anomaly) User interface Error (as it was before MP2.31) or improvement description Point symbols might appear with a wrong colour (e.g. acknowledged alarm in blue). The sound frequency for very-high priority events has been modified for easier recognition. The “Not configured” condition of NK822x lines was erroneously propagated as anomaly.
Corrections and improvements in MP2.31 # 4612 Function Graphics 4753 Graphics 4883 Graphics 5010 Graphics 5020 Graphics 5042 Graphics 5050 Graphics 5079 Graphics 5108 Graphics 5183 Graphics 5253 Graphics 3852 History (Property tool) History (Backup/restore) History (User interface) History (Backup/restore) Printed journaling (Network printers) Printed journaling (Date format) Printed journaling (Tech.
Corrections and improvements in MP2.31 # 5155 Function Import Error (as it was before MP2.31) or improvement description Importing files from floppy disk used to create problems after the import procedure. Failures occurring during backup procedure were not properly reported to the user interface. This could result in a corrupted backup file being generated. A specific error has been corrected in the graphic tool.
Known issues in MP2.31 5 Known issues in MP2.31 This is a list of known limitations, problems and bugs in MP2.31. For more troubleshooting information, see the document 008080 Maintenance & Troubleshooting guide and the intranet support guide, see 7.1 at p.29. 5.1 Installation Do not forget MSDE SQL Server 2000 data engine (MSDE) + SP3 must be installed before initiating the MM8000 installation. Note: MM8000 MP2.31 requires MSDE V8 (also labelled MSDE 2000).
Known issues in MP2.31 That clears the database (still empty anyway) and can solve the installation problem. Installing localised text files After the MM8000 installation, the installation of a national language kit requires a separate procedure (see 007875 “MM8000 Localisation Guide”). The command to launch is the following: MM8000 MP 2.31 - Localized Files Installation.bat Please be aware of the following: The command batch has been renamed from the previous “MM8000 MP 2.3 - Localization Procedure.bat”.
Known issues in MP2.31 FDMNG server troubles If any of the MM8000 folders are selected /open in the Windows Explorer during download, it can cause problems related to the file distributor process ‘FDMNG’. If this occurs, FDMNG server task may not start up properly (red icon in the system supervisor browser), or the map pages may not display properly after logging in to the MM8000. Should this happen, you need to run the “Empty_DB.bat” procedure and then download again. See 006799 MM8000 MP2.31 ICC manual.
Known issues in MP2.31 Changing to a completely new configurations When a new project is downloaded and it includes a complete new network configuration in comparison with the earlier download, the use of the Empty_DB.bat command is recommended. See 006799 MM8000 ICC manual. “Move” function in AlgoRex tool The AlgoWork “move” function, which allows CC11 objects to be moved in the tree structure, is not fully supported in MM8000 tools (ref. #5521).
Known issues in MP2.31 - Depending on the specific configuration and on the PC hardware characteristics, MM8000 software may use up the memory resources in Windows and cause the “Low virtual memory” error message to display. Should that occur, you could adjust the virtual memory size (it actually refers to the size of the paging file where the operating system swaps on disk the active memory areas).
Documentation 6 Documentation This section provides an overview of what information is included in each of the documents that accompany MM8000 MP2.30. General changes For all new and updated documents, the release number on the title page will reflect the major release number (for example, 2.30 instead of 2.10, 2.20, etc.). The “About this document” section still provides information about when the document was last updated. 6.
Documentation 6.2 Technical documentation MM8000 Operation Manual This manual is an operation guide, meant for final users. Note: This document has been updated to reflect the new features (given at p.5) included in MP2.31. MM8000 Installation, Configuration and Commissioning (ICC) This guide is meant for commissioning engineers and technicians. The ICC guide contains information about system limits, and hardware and software requirements.
Customer support links & resources 7 Customer support links & resources 7.1 MM8000 CD-IT support provides information on the Intranet site http://www.cdi.cerberus.ch/support/supp-lmsn.asp. A software troubleshooting guide is available at: http://www.cdi.cerberus.ch/support/supp-trou.asp (password required) or deliverable upon request. Please note the new support mailbox: support-dms.it.sbt@siemens.com. 7.2 Microsoft 7.2.
Siemens Building Technologies AG Alte Landstr. 411 CH-8708 Männedorf Tel. +41 1 - 922 6111 Fax +41 1 - 922 6450 www.sibt.com Document no. 008091_a_en_-- Edition 02.