2.2.8 Licensing
License PAKs
MM8000 MP2.31 requires the PAK codes 2.3. Older licenses should be upgraded
to 2.3.
Please be aware that, unlike previous MP2.30, the new software necessarily needs
the complete set of MM8000 PAK codes, which can enable the following functions:
License Function Notes
WW8000 Composer Composer tool -
NS8010 Cerloop Driver ISO1745 serial connections License indicates the number of ports
NS8012 CDI-net Driver CMSDL serial connections License indicates the number of ports
NS8210 CDI-WAN driver NK8000 LAN connection License indicates the max. number of
NK822x and the Encryption option
MM8000 core
- # Subsystems
- # Physical devices
Subsystem and point support in
MM8000 server
License indicates the max. number of
subsystems and physical devices.
MM8000 core
- Dialler
Dialler option in event treatment -
MM8000 core
- #Maps
Graphic map support in event treat-
ment and plant navigation
License indicates the max. number of
maps.
MM8000 core
- #Additional clients
Client station support (floating license) License indicates the max. number of
client stations that can connect at the
same time to the MM8000 server.
MM8000 core
- #Assisted treatment
Assisted treatment support on MM8000
clients (floating license)
License indicates the max. number of
client stations enabled to assisted
treatment at the same time.
MM8000 core
- #History Browser
History application support on MM8000
clients
License indicates the max. number of
client stations enabled to open the His-
tory Browser.
MM8000 core
- #Open mode support
Open mode (access to Windows while
MM8000 is active).
License indicates the max. number of
client stations enabled to the open
mode.
MM8000 core
- #Dual monitor
Support for double monitor on MM8000
client
License indicates the number of client
stations equipped with two monitors.
On an existing MP2.30, there might be an incomplete set of codes that is detected
by MP2.31, whereas MP2.30 could tolerate it. This is likely to occur on earlier
MP2.3 licenses release: carefully check your license codes before updating to
MP2.31.
This verification should concern the “MM8000 core” license; as an example, please
see the following case: