# Function Error (as it was before MP2.31) or improvement description Notes
4597 User interface
(Symbol colour)
Point symbols might appear with a wrong colour (e.g. acknowledged
alarm in blue).
4876 User interface
(Audio)
The sound frequency for very-high priority events has been modified for
easier recognition.
4056 User interface
(NK822x anomaly)
The “Not configured” condition of NK822x lines was erroneously propa-
gated as anomaly.
4981 User interface In client/server systems, client operation status (user login/logout) was
not properly refreshed after downloading.
5043
5077
User interface
(Refreshing maps)
Peaks of message acquisition while refreshing a graphic map used to
affect the proper display of AutoCAD backgrounds and point symbols.
Corrected
in 2.30-01
5086 User interface
(Point properties)
Point property windows could display without the proper information
when selected from graphic map.
Corrected
in 2.30-01
5103 NS8210
CDIWAN driver
An incorrect CS11structure used to be shown when connected via
NK822x. This could also result in a wrong communication diagnostics.
Corrected
in 2.30-01
5105
5339
NS8210
CDIWAN driver
Difficulties in re-establishing the communication link between NS8210
and NK822x have been removed.
Corrected
in 2.30-01
5120 User interface
(Comm. Feedback)
Improvement: command feedback allows now for immediate reporting
of command execution failure.
5159 User interface
(Event filters)
Even filter by discipline did not work properly.
5250 User interface
(Geographic tree)
Improvement: geographic nodes include now new properties, namely
“Exclusion”, “Disconnection”, “Test”
5090 CS11 EP7 Wrong information shown in the technical text field of CC11 EP7 physi-
cal tree points.
5150 CS11 EP7 Extinguishing “Pre-alarm” did not reset when escalating to “Alarm”.
4560
5104
5133
CS11
Vitality in NK822x
Although required for CS11 systems, the vitality check could not be
enabled in the NK822x tool.
Corrected
in 2.30-02
5139 CC60
“Pre-alarm” and “warning” conditions were not properly reset. Corrected
in 2.30-02
5360 CS6 Guarto CS6 day mode message did not generate an event.
4959 Event treatment
(Ext. applications)
In assisted event treatment, external Windows applications could not
be launched twice even when set as repeatable step.
5018 Event treatment
(Automatic mode)
Occasionally, the operator switchover did not work properly when the
automatic mode was selected.
5029 Event treatment
(Automatic mode)
New incoming events did not cause the temporary suspension of the
current treatment.
5057 Event treatment
(Auto-Ack)
Upon selecting an event, the automatic acknowledgment did not work
even if selected in the configuration.
Corrected
in 2.30-01
5158 Event treatment
(Dialler)
In certain conditions, related to close-mode users and new users, dial-
ling assistant did not work properly.
5255 Event treatment
(Access rights)
Some settings could result in users being enabled to enter the assisted
treatment but not to execute any step.
3503 Graphics Improvement: when a page is displayed, the first point in the graphics is
now automatically selected
3508 Graphics In certain conditions, maps used to be refreshed with a wrong zoom
factor and somehow misplaced.
3533 Graphics Point grouping has been disabled on the graphic maps in order to cor-
rect errors in the automatic assignment
Corrected
in 2.30-02
19
Fire & Security Products 008091_a_en MM8000 MP2.31 Release Notes.doc