Specification

30 HF321NX 3 7
1
/2
—— 5
60 HF322NX 7
1
/2
15 10
30 HF361NX 3 7
1
/2
5157
1
/2
20 5 15
60 HF362NX 7
1
/2
15 15 30 15 50 10 30
100 HF363NX 15 30 25 60 30 75 20 50
200 HF364NX 25 60 50 125 60 150 40 50
30 HNF361X 7
1
/2
—20 30 515
60 HNF362X 15 50 60 10 30
100 HNF363X 30 75 100 20 50
200 HNF364X 60 125 150 40 50
operating temperatures and is supplied
with a continuous memory retaining
gasket for a superior seal against entry
of water, dust and other contaminants.
The excellent insulating properties of
fiberglass virtually eliminate problems
caused by internal condensation.
All switches are load break rated and
are provided with an equipment ground
kit as standard. Class R fuse clip kits and
auxiliary switch kits are also available.
Number Maximum Enclosure Enclosure
Molded Case of Current Catalog Wgt. lb./Ship.
Switch Type Poles Rating Number Package
ED2, ED4, ED6
15-60
EA 27
HED4, HED6 2-3 70-100 EB 32
FXD6, FD6, HFD6, HFXD6, CFD6 2-3 250 EC2 85
JXD2(A), JXD6(A), JD6(A), SJD6(A) 2-3 200-350 EC4 85
HJD6(A), HJXD6(A), HHJD6, HHJXD6, SHJD6 2-3 300-400 EE 93
LXD6(A), LD6(A), SLD6(A), SLD6(A) 2-3 600 ED6 190
HLD6(A), HLXD6(A), HHLD6, HLXD6(A) 2-3 600 ED6 190
HHLD6, HHLXD6, SHLD6 2-3 600 ED6 190
Type 7 and 9 Enclosed Molded Case Switches ➀➁
Application
Siemens Non-Metallic Safety Switches
have fiberglass reinforced polyester
enclosures, which are extremely
resistant to a wide range of corrosive
atmospheres that can be encountered
in waste-water treatment plants and
certain other industrial applications.
Description
30-200A, 600V Max, fusible and non-
fusible switches are available in Type 4X
enclosures. The fiberglass-reinforced
enclosure allows a wide range of
Non-Metallic Features
30, 60, 100 and 200
amp switches
240 and 600 volts fusible
600 volts non-fusible
Rated 10,000 AIC with
Class H fuses
Rated 200,000 AIC with
Class J or R fuses
UL-Listed, File E4776
Horsepower rated
Suitable for use as
service equipment
Quick-make, quick-break
mechanism
Visible blade construction
Padlock-off handle feature
Field installable auxiliary
contacts
Field replaceable line and
load bases
Factory installed ground lug
supplied as standard
Line terminal shields
Neutrals installed as standard
on fusible switches
3-Pole, 4-Wire, 600 Volts Fusible
3-Pole, 3-Wire, 600 Volts Non-Fusible
3-Pole, 4
--
Wire, 240 Volts Fusible
Horsepower Rating - 3-Phase 250 600
Ampere Catalog 240 Volt AC 480 Volt AC 600 Volt AC Volts Volts
System Rating Number Std. Max. Std. Max. Std. Max. DC DC
Neutrals not included. Order neutral kit when required.
Order molded case switch and enclosure separately.
600V DC rating and 600V DC HP ratings require (2) poles to be connected in series.
Heavy Duty
Special Application Switches / Non-Metallic
21