Specification

Interchangeable Hubs
Conduit hubs are available for
Type 3R, 12 and 4/4X applications.
30-200A Type 3R Switches are
provided with a conduit hub provision
and a removable hub plate on their top
rainsheds.
Hubs
Type 3R
Compression Lug
Neutral Barrier Kit
All Heavy Duty Switches are field con-
vertible for crimp type lugs. When
compression lugs are required for 30-
100A switches, a neutral barrier kit is
required for 1-Phase, 3W or 3-Phase,
4W applications. When compression
lugs are required on 400-1200A
switches, lug mounting kits are
required.
Lugs
30-100A Switches are suitable
for use with 60ºC or 75ºC wire.
100-1200A are suitable for use
with 75ºC rated wire.
Switch Wire Range with
Ampere Wire-Bending Space
Rating Per NEC Table 373-6 Lug Range
30GD #14-8 AWG (Cu/Al)
#14-8 AWG (Cu/Al)
30HD #12-6 AWG (Al) or #14-6 AWG (Cu/Al) #14-2 AWG (Cu/Al)
30A HD #14-2 AWG(Cu/AI) #14-2 AWG (Cu/AI)
oversized
60
#12-2 AWG (Al) or #14-3 AWG (Cu/Al) #14-2 AWG (Cu/Al)
60A HD #14-1/0 AWG (Cu/Al) #14-1/0 AWG (Cu/Al)
oversized
100 #14-1/0 AWG (Cu/Al) #14-1/0 AWG (Cu/Al)
200
#6 AWG-250 Kcmil (Cu/Al) #6 AWG-300 Kcmil (Cu/Al)
400
1/0 AWG-750 Kcmil (Cu/Al) or (1) 1/0 AWG-750 Kcmil (Cu/Al) or
(2) 1/0 AWG-250 Kcmil (Cu/Al) (2) 1/0 AWG-250 Kcmil (Cu/Al)
600
(2) 1/0 AWG-750 Kcmil (Cu/Al) or (2) 1/0 AWG-750 Kcmil (Cu/Al) or
(4) 1/0-250 Kcmil (Cu/Al) (4) 1/0 AWG-250 Kcmil (Cu/Al)
800 (3) 1/0-750 kcmil (Cu/Al) Line and Load or (3) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
(6) 1/0-250 kcmil (Cu/Al) (4) 1/0 AWG-600 Kcmil (Cu/Al) neutral
(4) 1/0-250 kcmil (Cu/Al) neutral
1200 (4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load (4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
(4) 1/0 AWG-600 Kcmil (Cu/Al) neutral (4) 1/0 AWG-600 Kcmil (Cu/Al) neutral
Wire Ranges (Line, Load and Standard Neutral)
Conduit
Size Catalog
(inches) Number Used On
Switch
Ampere Catalog
Rating Number Kit Description
30 HCL612 Neutral Barrier Kit
60 & 100 HCL623 Neutral Barrier Kit
400
HCL65 1 Pole, Compression
Lug Mounting Kit
400 HCL65678 1 Pole, Compression
& 600
Lug Mounting Kit
800 Factory Installed Only
& 1200
Compression Lug Mounting
and Neutral Barrier Kits
SSH150
SL0420
ECHV300
ECHS200
General and Heavy Duty
Hub and Lug Data
3/4 ECHA075
1 ECHA100 30A GD Only
1 1/4 ECHA125
3/4 ECHS075
1 ECHS100
1 1/4 ECHS125 60-200A GD
1 1/2 ECHS150 30-200A HD
2 ECHS200
2 1/2 ECHS250
2 1/2 ECHV250
3 ECHV300 400-1200A
3 1/2 ECHV350
4 ECHV400
NOTE: 30-200A. Type 3R Switches have
removable hub plates on rainsheds. 400A and
larger Type 3R Switches have no provisions
for mounting hubs. Drill or punch hole in the
field to accommodate hub size desired.
3/4 SSH075
1 SSH100
1 1/4 SSH125
1 1/2 SSH150 30-200A
2 SSH200
25
Type 4 / 4X
Hubs suitable for 3R Switches.
Neutral Barrier kits are required on 30-100A switch only and only with 1-Phase, 3W or 3-Phase and 4W loads.
Compression lugs mounting kits are required on 400-1200A switches only.
Provides mounting for a single line or load lug.
Provides mounting for two compression lugs per phase on line or load one per pole required.
Line lugs have wire-bending space and are UL approved for #14-6 conductors.
Max. wire size for height reduced switches is 500 Kcmil (Cu/Al).
All but 60A GD & Compact HD NF switches are also UL approved for #2 Cu/Al conductors.
All 200A Heavy Duty Switches have a wire range & wire bending space for one # 6-300 Kcmil (Cu/Al).
Multiple Padlock Accessory
A tamperproof device to provide for
multiple padlocking to meet OSHA or
plant requirements. Accepts up to six
padlocks. Catalog number SL0420.
Standard Carton-12.
Kirk-Key Interlocks
Kirk-Key Interlocks are factory installed
only on Type VII Heavy Duty and Double
Throw Safety Switches.
Interlocks are used to prevent the
authorized operator from making an
unauthorized operation. The interlock
system is a simple method of applying
key interlocks to safety switches so as to
require operation in a predetermined
sequence.
Before consulting the factory, the
following information is required:
User name and address
Key number from lock assemblies
on any existing locks to be inter-
locked with
Complete locking scheme
Consult factory for delivery.