Specification

Description & Application
Double throw safety switches are
intended to transfer loads from one
power source to another. All two- and
three pole double throw switches are
suitable for use as service equipment.
All are UL listed. Switches are rated for
use on systems up to 10,000A when
protected with Class H fuses or
100,000A when protected with Class R
or Class T fuses¡. They can also be used
to connect a single source of power to
either of two loads. In this application it
is necessary to field modify fusible
switches so that the fuses are on the
load side of the switching mechanism.
A cover interlock is provided on all
ampere ratings. The operating handle
may be padlocked in the OFF position.
Fuse Capabilities of Fusible Switches
Amp
Fuse Type
Rating H R T J
30 & 60A, 240V Std Yes (kit) No No
30 & 60A, 600V Std Yes (kit) No Yes
100 & 200A Std Yes (kit) Yes (kit) Yes
400 & 600A DTF No No Yes
Std
ON
OFF
ON
Number Type 1– Indoor Type 3R – Outdoor Type 12/3R Industrial Type 4X – Stainless Steel
System Voltage of Poles Amps Catalog Number Catalog Number Catalog Number Catalog Number
Use HS T
ype hubs for 30–200A switches; 400A and larger switches do not have hub provisions.
All Heavy Duty double throw switches with catalog numbers starting with “DT” are rated 200,000 AIC max. when protected by Class R, J or T fuses.
Fuse ampere rating must not exceed switch ampere rating.
Move load base.
Catalog No. F355SSDTK will accept Class T Fuse only
Four pole switches are not approved for service entrance.
Double Throw Switches
28
Double Throw Switches
Heavy Duty Fusible (30-200A with Class H fuse provisions)
2 200 DTF224 DTF224R
30 DTF321 DTF321R
240
60 DTF322 DTF322R
Volt AC
3
100 DTF323 DTF323R
or
200 DTF324 DTF324R
250
400 DTF325
Volt DC
600 DTF326
30 DTF361
600
60 DTF362
Volt AC,
3
100 DTF363 DTF363R F353SSDTK
250
200 DTF364 DTF364R F354SSDTK
Volt DC
400 DTF365 F355SSDTK
Heavy Duty Non-Fusible
30 DTNF221
60 DTNF222
2 100 DTNF223
200 DTNF224 DTNF224R
240
400 DTNF225 DTNF225R
Volt AC
30 DTNF321
or
60 DTNF322
250
100 DTNF323 DTNF323R
Volt DC
3 200 DTNF324 DTNF324R
400 DTNF325
600 DTNF326
800 DTNF327
30 DTNF361 DTNF361R DTNF361J DTNF361S
60 DTNF362 DTNF362R DTNF362J DTNF362S
3 100 DTNF363 DTNF363R DTNF363J DTNF363S
200 DTNF364 DTNF364R DTNF364J DTNF364S
400 DTNF365 DTNF365R NF355HDTK NF355SSDTK
600
600 DTNF366 DTNF366R
Volt AC
800 DTNF367 DTNF367R
or
1200 DTNF368 DTNF368R
250
4
30 NFR451DTK
Volt DC
60 NFR452DTK
100 NFR453DTK
200 NF454DTK NFR454DTK NF454SSDTK
400 NF455DTK NFR455DTK
600 NF456DTK NFR456DTK
800 NF457DTK NFR457DTK
ON
OFF
ON