Installation Guide

Double throw switches
Standards and ratings
UL Listed under file #E4776
Meets UL98 for switches and UL50
for enclosures
Meets federal spec WS865C
Suitable for use as Transfer Equipment
on optional standby systems as defined by
Article 702 of the NEC
Meets NEMA Standard KS-1 for enclosed switches
Meets NEC wire bending space requirements
• AIC Ratings
General Duty & 4 Pole Heavy Duty
10,000 AIC when protected by Class H or
100,000 AIC when protected by Class R, J
or T fuses (fuse ampere rating must not exceed
switch ampere rating)
Heavy Duty
10,000 AIC with Class H or 100,000 AIC when
used with or protected by Class R, J or T fuses
(fuse ampere rating must not exceed switch
ampere rating)
1) Typical wiring diagrams for 30-200 amp switches are shown.
2) 100-400A fusible, 3 pole fusible switches (catalog numbers F353SSDTK, F354SSDTK and
F355SSDTK) are also available.
3) 200A, 4 pole stainless Type 4X switch, catalog number NF454SSDTK, is also available.
4) Move load side base.
Fuse capabilities of “DTF” type fusible switches
A mp
rating
Fuse type
H R T J
30 & 60A, 240V Std. Yes (kit) No No
30 & 60A, 600V Std. Yes (kit) No Yes
4)
100 & 200A Std. Std. Yes (kit) Yes
4)
400 & 600A No No Yes
4)
Std.
Fuse capabilities of “F” and “FR” type
fusible switches
A mp and volt
rating
Fuse type
H R T J
100A, 600V Std.
200A, 600V Std.
400A, 240V Std.
400A, 600V Std.
600A, 240V Std.
HNC264
Type 1
Indoor
Type 3R
Outdoor
System
1)
Voltage
Number
of poles Amps
Catalog
number
Catalog
number
Heavy duty fusible
2)
240 Volt AC
or
250 Volt DC
2 200 DTF224 DTF224R
3
30
60
100
200
400
600
DTF321
DTF322
DTF323
DTF324
DTF325
DTF326
DTF321R
DTF322R
DTF323R
DTF324R
FR325DTK
FR326DTK
600 Volt AC,
250 Volt DC
3
30
60
100
200
400
DTF361
DTF362
DTF363
DTF364
DTF365
DTF363R
DTF364R
FR355DTK
Heavy duty non-fusible
240 Volt AC
or
250 Volt DC
2
30
60
100
200
400
DTNF221
DTNF222
DTNF223
DTNF224
DTNF225
DTNF224R
DTNF225R
3
30
60
100
200
400
600
800
DTNF321
DTNF322
DTNF323
DTNF324
DTNF325
DTNF326
DTNF327
DTNF323R
DTNF324R
600 Volt AC
or
250 Volt DC
3
30
60
100
200
400
600
800
1200
DTNF361
DTNF362
DTNF363
DTNF364
DTNF365
DTNF366
DTNF367
DTNF368
DTNF361R
DTNF362R
DTNF363R
DTNF364R
DTNF365R
DTNF366R
DTNF367R
DTNF368R
4
3)
30
60
100
200
400
600
800
NF454DTK
NF455DTK
NF456DTK
NF457DTK
NFR451DTK
NFR452DTK
NFR453DTK
NFR454DTK
NFR455DTK
NFR456DTK
NFR457DTK
Heavy duty non-fusible
1)
Type 12/3R
Industrial
Type 4X
Stainless
steel
600 Volt AC,
250 Volt DC
3
30
60
100
200
400
DTNF361J
DTNF362J
DTNF363J
DTNF364J
NF355HDTK
DTNF361S
DTNF362S
DTNF363S
DTNF364S
NF355SSDTK
General duty non-fusible Type 3R – Outdoor
240 Volt AC
or
250 Volt DC
2
100
200
With neutral
DTGNF223NR
DTGNF224NR
Less neutral
DTGNF223R
DTGNF224R
3
100
200
DTGNF323NR
DTGNF324NR
DTGNF323R
DTGNF324R