Product Overview

MXG461…U, MXF461…U Modulating Control Valves Technical Instructions
With Magnetic Actuators Document Number CA1N4455E-P25
May 8, 2009
Siemens Building Technologies, Inc. Page 5
Mounting,
Continued
Straight-through Valves
Only three-way MX.461...U valves are supplied. They may be used as straight-through
normally closed valves by closing off port "B":
Port "B" can be sealed with a Z155/65
blanking flange and gasket.
B
SVAL0008R1
BLANKING
FLANGE
Figure 4. MXF461...U Flanged Valves in
Straight-through Applications.
Port "B" can be sealed with the
accessories supplied (blanking disk,
gasket, and the nut).
B
Sval0007R1
Figure 5. MXG461...U Screwed Valves in
Straight-through Applications.
Installation
MXG461...U screwed valves are flat-faced to facilitate sealing with the gaskets
supplied.
Do not use hemp, tape or thread-sealing compound.
Do not insulate the actuator.
For notes on electrical installation, see Terminal Layout.
Maintenance
The valves and actuators require no maintenance or service. The valve stem is sealed
with a maintenance-free O-ring gland.
Should the valve electronics prove faulty, the electronics module should be exchanged
for a replacement part, part number ASE1 (1/2-inch to 1-1/4 inches) or ASE2
(1-1/2 inches to 2-1/2 inches). Mounting instructions are enclosed (Ref. 35678).
WARNING:
Under operating conditions within the limits defined by the application
data, the actuator will become hot, but this does not represent a fire risk.
Always maintain the minimum clearance specified (see Dimensions).