Data Sheet for Product

Controllers
5 |
22
Siemens
Controllers, HMI, and accessories
CE1S2359en
Building Technologies
-
04
-
02
ALBATROS2 HEATPUMP CONTROLLER
RVS61.843 (as of series C)
Inputs, number Outputs, number
Mains 10 EX Relay 12 QX
Sensor 11 BX Triac 1 ZX
Digital-/0..10V 2 HX 0..10V/PWM 2 UX
Connection to Designation With/on Designation
Operator units AVS37, AVS74 Ribbon cable AVS82.490/109, ...491/109
Extension modules AVSx5.39x (max. 3 modules) Ribbon cable AVS82.490/109, ...491/109
Service tool OCI700.1 (including ACS790) "BSB" slot Cable included in delivery
Radio module AVS71.390 (for BSB-RF) "X60" slot
BSB devices e.g. room units QAAxx Terminals CL-, CL+
Service tool OCI700.1 (including ACS790) "LPB" slot Cable included in delivery
LPB devices RVS is a cascade or zone controller Terminals MB, DB
Modbus devices RVS is a Modbus slave or master Modbus clip-in OCI351.01
Various plugs AGP4S..., AGP8S...
Power Voltage 230 V ~, 50/60 Hz
IP class as per EN 60529 IP 00
Climatic conditions
(operation)
As per EN 60721-3-3 class 3K5, -20...50 (non-condensing)
Dimensions Length x Width x Height 281 x 121 x 70 mm
Weight Excl. packaging 650 g
Packaging units Contents 1 piece or 20 pieces
User Manual CE1U2355en_05x
Plant diagram Selection of 24 preset diagrams of complete plants.
Compilation of partial diagrams as per CE1P2359_20.
Examples Plant diagram 5: Brine-to-water heat pump with buffer storage tank, DHW storage tank with charging pump
Q3, and mixing or pump heating circuit.
BX1
BX2
BX7
BX8
BX9
BX10
BX11
BX12
BX13
Buffer storage tank sensor B4
Buffer storage tank sensor B41
Hot-gas sensor B81
DHW sensor B3
Outside sensor B9
HP flow sensor B21
B1
HP return sensor B71
Source inlet sensor B91
etc.