User's Manual
Table Of Contents
- SIMATIC RF300
- Legal information
- Table of contents
- 1 Introduction
- 2 Safety information
- 3 System overview
- 4 Planning the RF300 system
- 4.1 Fundamentals of application planning
- 4.1.1 Selection criteria for SIMATIC RF300 components
- 4.1.2 Transmission window and read/write distance
- 4.1.3 Width of the transmission window
- 4.1.4 Impact of secondary fields
- 4.1.5 Setup help of the readers of the second generation
- 4.1.6 Permissible directions of motion of the transponder
- 4.1.7 Operation in static and dynamic mode
- 4.1.8 Dwell time of the transponder
- 4.1.9 Communication between communications module, reader and transponder
- 4.2 Field data for transponders, readers and antennas
- 4.3 Installation guidelines
- 4.4 Chemical resistance of the transponders
- 4.5 Guidelines for electromagnetic compatibility (EMC)
- 4.1 Fundamentals of application planning
Planning the RF300 system
4.2 Field data for transponders, readers and antennas
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x
57
4.2.3
Field data of ISO transponders (MDS E)
The limit distances (S
g
) and operating distances (S
a
) along with the length of the
transmission window for each reader-transponder combination are listed in the tables below.
Observe the following information for field data of ISO transponders:
● A maximum median deviation of ±2 mm is possible in static mode (without affecting the
field data).
● In dynamic mode, make sure that rectangular transponders cross the antenna field in the
longitudinal direction.
Note
Relenace of the MDS E transponders
The MDS E transponders are
products that will be discontinued. These are relevant for
migration projects in which existing RFID systems are replaced by SIMATIC RF300.
Table 4- 18 Field data RF310R reader
Length of the transmission
window (L)
Operating distance (S
a
)
Limit distance (S
g
)
MDS E600
40
2...93
105
MDS E611
40
2...93
105
MDS E624
30
2...64
72
All values are in mm
The values relate to the RF310R reader as of version "D".
Table 4- 19 Field data RF340R reader
Length of the transmission
window (L)
Operating distance (S
a
)
Limit distance (S
g
)
MDS E600
90
5...110
140
MDS E611
90
20...50
70
MDS E624
60
2...60
75
All values are in mm