Planning the RF300 system
4.3 Installation guidelines
SIMATIC RF300
System Manual, 07/2016, C79000-G8976-C345-0x
81
Reader RF350R with ANT 18 and with ISO transponders (MDS D)
Table 4- 47 Reduction of field data due to metal, range as %: Transponder and RF350R with ANT 18
Transponder
ANT 18 without metal
ANT 18 mounted in met-
al
(10 mm all-round)
MDS D124
1)
Without metal
100
85
On metal, distance 15 mm 85 75
Flush-mounted in metal;
distance all round 15 mm
85 45
MDS D127
Without metal 100 90
On metal, distance 0 mm
95
85
Flush-mounted in metal;
distance all round 0 mm
60 60
MDS D160
1)
Without metal
100
80
On metal, distance 10 mm
85
75
MDS D324
1)
Without metal
100
80
On metal; distance 15 mm
90
75
Flush-mounted in metal;
distance all round 25 mm
80 65
MDS D421
Without metal
100
85
On metal, distance 0 mm
90
65
Flush-mounted in metal;
distance all round 0 mm
40 20
MDS D422
Without metal
100
85
On metal, distance 0 mm
95
85
Flush-mounted in metal;
distance all round 0 mm
90 80
MDS D424
1)
Without metal
100
85
On metal 15 mm
85
80
Flush-mounted in metal;
distance all round 25 mm
75 75
MDS D425
Without metal
100
85
On metal, distance 0 mm
100
85
MDS D428
Without metal
100
95
On metal, distance 0 mm
95
95
MDS D460
1)
Without metal
100
95
On metal, distance 15 mm
95
95
MDS D521
without metal
??
??
on metal, distance 0 mm
??
??
flush-mounted in metal;
distance all round 0 mm
?? ??