TC12 Installation, Commissioning & Maintenance Handbook SIEMENS TRAFFIC CONTROLS Sopers Lane POOLE Dorset BH17 7ER SYSTEM: TC12 TC12 Installation, Commissioning and Maintenance Handbook PREPARED: A Pickering FUNCTION: Engineer This document is electronically held and approved in Meridian © Siemens plc. 1997 - 2004 All rights reserved. The information contained herein is the property of Siemens plc. and is supplied without liability for errors or omissions.
TC12 Installation, Commissioning & Maintenance Handbook Appendix A consists of the latest issue of 667/HB/26628/000.
TC12 Installation, Commissioning & Maintenance Handbook SAFETY WARNING In the interests of health and safety, when using or servicing this equipment the following instructions must be noted and adhered to: Only skilled or instructed personnel with relevant technical knowledge and experience, who are also familiar with the safety procedures required when dealing with modern electrical/electronic equipment are to be allowed to use and/or work on the equipment.
TC12 Installation, Commissioning & Maintenance Handbook TELECOMMUNICATIONS APPROVAL WARNING The Siemens TC12 Modems 667/1/22669/000, 667/1/22668/000 and 667/1/22668/001 and the TC12 OTU/LMU PCB Assemblies 666/1/02262/001 and 666/1/02262/021 are Approved for connection to British Telecommunications Private Circuits in a Multipoint or Point to Point configuration as defined in BS6328: Part 1: 1982, subject to the conditions set out in the instructions for use.
TC12 Installation, Commissioning & Maintenance Handbook This Handbook must be supplied with the apparatus. Validity of the approval depends on this information being supplied including the User Guide in the General Handbook 666/HB/43100/000.
TC12 Installation, Commissioning & Maintenance Handbook TABLE OF CONTENTS 1 INTRODUCTION ................................................................................................. 1 1.1 PURPOSE ........................................................................................................... 1 1.2 SCOPE ................................................................................................................ 1 1.3 RELATED DOCUMENTS ...............................................
TC12 Installation, Commissioning & Maintenance Handbook 2.4.11 2.4.12 Digital Output PCB ......................................................................................... 61 Recommended Spares................................................................................... 61 3 TC12 OUTSTATION.......................................................................................... 62 3.1 SPECIFICATION ...........................................................................................
TC12 Installation, Commissioning & Maintenance Handbook 4.3 OVERVIEW OF THE TC12 INSTATION TEST SET SETTINGS/SELECTIONS AND CONNECTIONS................................................................................................. 139 4.3.1 4.3.2 4.3.3 Introduction .................................................................................................. 139 Connection to Unit Under Test ..................................................................... 139 Front Panel Switches ...............
TC12 Installation, Commissioning & Maintenance Handbook 6.3.1 6.3.2 6.3.3 6.3.4 6.4 6.4.1 6.4.2 6.4.3 6.4.4 6.5 6.5.1 6.5.2 6.5.3 6.5.4 6.5.5 General ........................................................................................................ 167 Configuring the Integral OTU PCB ............................................................... 167 Connectors and Cables................................................................................
TC12 Installation, Commissioning & Maintenance Handbook FIGURE 29 - PHASES IN STAGES FOR EXAMPLE 6 .............................................. 125 FIGURE 30 - OUTSTATION PCB STATUS LEDS ..................................................... 131 FIGURE 31 - OUTSTATION PSU VOLTAGE CHECKS............................................. 134 FIGURE 32 - OUTSTATION TEST SET FRONT PANEL........................................... 157 FIGURE 33 - OUTSTATION TEST SET CONNECTIONS .......................................
TC12 Installation, Commissioning & Maintenance Handbook 1 INTRODUCTION 1.1 PURPOSE This document is a guide for professional Installation and Maintenance personnel. It describes how to install, commission and maintain the TC12 Instation and Outstation. 1.2 SCOPE Section 2 covers the Instation cabinet and all the equipment contained within the TC12 Instation. Section 3 covers all equipment associated with the TC12 Outstation. Sections 4 and 5 describe the Instation and Outstation test sets.
TC12 Installation, Commissioning & Maintenance Handbook 1.5 ISSUE STATE AND AMENDMENTS Issue 1 - First formal issue Issue 2 - Significant changes this issue are listed below: Table 3 and Table 6 Modem PCB and OTU PCB Receive threshold switch settings for –39 dBm and –33 dBm were reversed in issue 1. Instation recommended spares, PSU PCB and PSU added. Modem PCB, Transformer PCB and OTU PCB all have covers - the part numbers have been corrected.
TC12 Installation, Commissioning & Maintenance Handbook Example of lamp monitoring on a more complex junction added. Drawing of OTU input, and reply bytes added. Replacement current sensor part number added. (667/7/25171/000) • Replacement voltage monitoring transformer part number added. (667/7/25172/000) Issue 4 - Significant changes for this issue listed below. • Handbook converted to Word v6. • 667/HB/26628/000 OTU Serial Environmental Monitor handbook added. • Remote Handset details added.
TC12 Installation, Commissioning & Maintenance Handbook • Equipment is CE marked and self-certified to RTE Directive 99/5/CE R&TTE. BABT approval no longer appropriate. References to BABT removed throughout document. • Clarification to battery change procedures, sections 3.4.5 and 6.5.4. • Instation Power Supply replacement procedure added to section 2.4.10. • General updates to formatting and spelling. • Preface removed, since the information it gave is available from the table of contents.
TC12 Installation, Commissioning & Maintenance Handbook The Outstation test set is used in place of the controller to both set Reply bits and monitor Control bits at the OTU.
TC12 Installation, Commissioning & Maintenance Handbook Instation The Instation comprises of one or more Traffic control computers (TCC) and one or more Instation Transmission Units (ITUs). The ITU cabinets are 32U high with grey panelling and a smoked glass front door. Traffic Control Computer The TCC is a system containing a minimum of one machine and one PC per ITU cabinet. The UTC TCC system communicates with the PC(s) via an Ethernet link.
TC12 Installation, Commissioning & Maintenance Handbook Digital Output Rack The Digital output rack contains one Instation rack Power Supply Card and between one and sixteen Digital Output boards, each capable of driving 64 LEDs at up to 30 V 25 mA. There are two variants of Digital Output board, one sources current and the other sinks current. The system could be used for any application requiring digital output, not just wallmap driving.
TC12 Installation, Commissioning & Maintenance Handbook Figure 1 - System Diagram for Digital Output Rack connection to a Wall Map 666/HE/43100/000 Page 8 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook Figure 2 - System Connection for two ITU Racks 666/HE/43100/000 Page 9 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook 2 TC12 INSTATION 2.1 SPECIFICATION 2.1.1 Mains voltage ranges The Instation will work over: 98 – 132 V RMS 198 – 264 V RMS Note. The voltage range of the PC used in the Instation should be checked in the manufacturer's literature and note should be taken of any links/switches that need setting for different voltage ranges. 2.1.2 Mains frequency range All TC12 equipment will work from 47 Hz to 63 Hz 2.1.
TC12 Installation, Commissioning & Maintenance Handbook 2.1.5 Size and Weight Figure 3 - TC12 Cabinet - External Dimensions 585 875 1540 1625 SIDE FRONT All dimensions in mm Weight: Cabinet 111 Kg ITU Rack 8.4 Kg Digital Output Rack 8.3 Kg Note: The weight of the cabinet does not include any of the PC equipment, and the weights specified for the racks are with their full complement of PCBs.
TC12 Installation, Commissioning & Maintenance Handbook 2.2 INSTALLATION Safety Notes on TC12 Instation Only authorised/trained personnel are allowed to have access behind the doors/panels of the TC12 Instation Cabinet. Users/operators must not attempt to access anything behind these doors/panels.
TC12 Installation, Commissioning & Maintenance Handbook Unused 6U positions are fitted with a 6U blanking panel (561/4/20899/022) 2.2.2 PC The TC12 PC is not like most PCs in that it does not have a motherboard; instead the processor card and the other cards are plugged into a back plane. There are 2 types of TC12 PC which may be used and are described below: 2.2.2.1 Rack Mount PC The Rack Mount PC is a convention desktop style of PC which sits on a shelf in the TC12 cabinet.
TC12 Installation, Commissioning & Maintenance Handbook 2.2.2.4.2 Rack Mount Wall Map PC A rack mount PC which is to be used for driving the LEDs on a wall map would normally have the following, additional, cards installed in it. • Ethernet Card (Etherlink 3) (not needed if processor card has built-in Ethernet) • Digi I/O Card (1 per digital output rack) 2.2.2.4.
TC12 Installation, Commissioning & Maintenance Handbook keys are then used to select the items to change; only the Interrupt Request Level and the Base Address can be changed. The parameters should be set to the values shown below: I/O Base Address 300H Interrupt Request Level 3 Note: If an Etherlink 3 card is to be used in a PC with a built-in Ethernet connection the Etherlink 3 card settings must be those in 2.2.2.
TC12 Installation, Commissioning & Maintenance Handbook The second cable is attached from the connector labelled J2 or P2 on the DIGI I/O Card to connector PL3 on the PSU board, (the PSU board has a note on the silk screen next to PL3 which reads 'CONNECTION TO P2 DIGI I/O (PC)'. Note: The two 50-way ribbon cables are to be connected to the card before it is installed into the PC. WARNING Please ensure cables are connected correctly, as they are not polarised.
TC12 Installation, Commissioning & Maintenance Handbook Set the I/O Port addresses of the boards using DIP switch 1 (DS1) positions 9 to 11, as shown below: Board 1 2 3 4 SW9 ON ON OFF ON SW10 OFF ON OFF OFF SW11 OFF OFF ON ON Address 0x100 0x120 0x200 0x220 Set the interrupts using DIP switch 2 (DS2), positions 1 to 8, as shown below: Board 1 2 3 4 SW1 OFF OFF OFF OFF SW2 OFF OFF OFF OFF SW3 ON OFF OFF OFF SW4 OFF OFF OFF ON SW5 OFF OFF OFF OFF SW6 OFF ON OFF OFF SW7 OFF OFF OFF OFF SW8 OFF OF
TC12 Installation, Commissioning & Maintenance Handbook 2.2.2.9 IMD Distribution Modules (16i and 16e Units) The IMD distribution Units (part number 667/7/22609/010), which are part of the DIGI 16i and DIGI AccelePort 16e units are secured by clamps (667/2/22638/000) to the IMD Distribution Mounting Panel (667/2/22636/000, see TC12 cabinet assembly drawing 667/GA/22600/000 and TC12 IMD/Modem Panel assembly drawing 667/GA/22635/000).
TC12 Installation, Commissioning & Maintenance Handbook The software installation procedure is as follows: SAFETY NOTE The PC should be plugged directly into the mains, and not via the mains distribution panel on the Instation, since the Instation has not undergone on-site safety tests, described in the commissioning section, at this stage. Figure 4 - TC12 Instation PC Installation Screen (7.
TC12 Installation, Commissioning & Maintenance Handbook (1) Before starting the TC12 software installation the Ethernet connection should be configured using the instructions given in 2.2.2.5 or 2.2.2.6, as appropriate. (2) Insert the TC12 Software disk into the PC and then switch the PC On. The Installation software will auto-boot and 'SIEMENS' will be displayed for a short time followed by the TC12 Instation PC Installation Screen, which should look something like Figure 4 if the software is Version 7.
TC12 Installation, Commissioning & Maintenance Handbook (10) If the indications for the DIGI I/O and IMD cards are as expected, move across to the 'Install' menu, select the 'Yes' option and hit return. The TC12 Software will now be installed on the Hard disk of the PC. Should the DIGI I/O cards and/or IMD cards not be shown as expected then choose the ‘Quit’ option and correct the problem. (11) Exit the Installation software. Eject the TC12 Software disk and keep this as a backup.
TC12 Installation, Commissioning & Maintenance Handbook 2.2.3 Systems Fault Indication Panel (SIP) The SIP (part number 667/1/22667/000) is 6U high and is screwed to the Instation racking in front of the PC. If the Audible alarm on the system fault indication panel (SIP) sounds it should be cancelled as required from the UTC TCC terminal.
TC12 Installation, Commissioning & Maintenance Handbook 2.2.4.1 PSU PCB (inc. Digi I/O, SIP (local and remote), Watchdog and TC8 cables) See Figure 7 for a diagram of the board layout showing the position of connectors, LEDs, switches, volume control. SAFETY NOTE When installing the PSU PCB in the TC12 Instation cabinet the earth strap should be bolted on to the PCB before the mains cable is plugged into the PCB.
TC12 Installation, Commissioning & Maintenance Handbook S3 - Audio ON/OFF This switch should normally be set to on. If it is set off then LED LP2 will light once the board is powered up and the local SIP audio alarm will not sound in the event of any faults. If the Audible alarm on the system fault indication panel (SIP) sounds it should be cancelled as required from the UTC TCC terminal.
TC12 Installation, Commissioning & Maintenance Handbook Figure 7 - PSU Board Layout LP1 1 1 1 1 1 (TOP) S2 S1 PL5 14 S3 20 TP4 TP5 TP6 TP7 TP8 TP9 1 (TOP) PL1 LP2 PL6 50 50 50 14 +12V +5V +5V GND AGND -12V PL2 PL3 PL4 1 (TOP) 1 PL7 Variant 14 1 (TOP) Power Supply 26 1 Hole for attaching earth strap from TC12 cabinet PL8 PL9 14 10 PL10 MAINS SOCKET GND Mains Wires Ser. No.
TC12 Installation, Commissioning & Maintenance Handbook Figure 8 - PSU Board Switch Settings 666/HE/43100/000 Page 26 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook Setting the Voltage Range of the PSU The Power supply fitted to every PSU board used in the system (part number 667/7/22631/000, manufactured by Daren Electronics PLC type PP40-30). An internal link in this power supply needs to be set for the nominal mains voltage. See Figure 9 for link setting; set to 110 V position for 98 V to 132 V mains voltage range, set to 240 V for 198 V to 264 V mains voltage range.
TC12 Installation, Commissioning & Maintenance Handbook 1. SW1 - Mode Select switch Ensure that the Mode Select switch is set correctly; see Table 1 for settings. One of the modes shown is selected on a 7-way DIL switch. Note NO other settings are to be used in the UK. 2. SW2, SW3, SW6 and SW7 - Line Level switches Ensure that the Line Level switches are set correctly see Table 2 for settings). Table 2 shows switch settings corresponding to the different levels. Each modem PCB contains four DIL switches.
TC12 Installation, Commissioning & Maintenance Handbook Connector PL1 The 24-way cable connects the top header (PL1) on the Modem PCB to four 25way 'D' connectors on the IMD distribution panel, as follows: Modem PCB 1 -> Modem PCB 2 -> Modem PCB 3 -> Modem PCB 4 -> 'D' connectors 1-4 on the distribution panel 'D' connectors 5-8 on the distribution panel 'D' connectors 9-12 on the distribution panel 'D' connectors 13-16 on the distribution panel Note: Once installed the 24-way cables should be tagged with
TC12 Installation, Commissioning & Maintenance Handbook Figure 10 - Modem PCB Layout Mode Select S1 1 (TOP) PL1 24 Way to IMD panel 0 1 S2 Line Level S3 Line Level 4 Wire S4 Level Off PCB ‘0’ S5 Level S6 Line Level S7 Line Level 24 Variant PL2 14 Way to PSU card 2/4 Wire 2 Wire Selector Level Level Transformer On PCB ‘1’ Select Level 1 (TOP) 14 37 PL3 37 Way ‘D’ to MDF or Transformer PCB. 1 (TOP) 0 1 For switches SW1, SW2, SW3, SW3, SW5, SW6 and SW7 the switch is: OPEN i.e.
TC12 Installation, Commissioning & Maintenance Handbook Table 1 - Modem PCB Mode Select Switch (SW1) SWITCH NUMBER MODE 1 2 3 4 5 6 !MC0 !MC1 !MC2 !MC3 !MC4 0 1 0 0 1 1 0 0 0 0 0 1 1 0 0 1 1 1 0 1 0 0 1 0 0 1 0 0 0 0 0 0 1 0 0 0 1 1 1 0 0 0 0 1 1 0 1 1 0 (Eng use only) CCITT V.23 M2 7 1200 BPS HALF DUPLEX CCITT V.23 M2 1200 BPS HALF DUPLEX WITH EQUALIZER CCITT V.23 M1 600 BPS HALF DUPLEX CCITT V.23 M2 1200 BPS FULL DUPLEX CCITT V.
TC12 Installation, Commissioning & Maintenance Handbook Table 2 - Modem PCB Line Level Switches (SW2, 3, 6 and 7) SWITCH NUMBER OUTPUT 1 2 3 4 5 6 7 8 POWER 0dBm 1 0 0 0 - - 1 1 -3dBm 1 0 0 1 - - 1 1 -6dBm 0 1 0 0 - - 1 1 -9dBm 0 1 0 1 - - 1 1 -10dBm 0 0 1 0 - - 1 1 -13dBm 0 0 0 0 - - 1 1 -16dBm 0 0 0 1 - - 1 1 RECEIVE THRESHOLD -42dBm - - - - 0 0 1 1 -39dBm - - - - 0 1 1 1 -33dBm - - - - 1 0 1 1 ↑ ↑ Switch
TC12 Installation, Commissioning & Maintenance Handbook Table 3 - Modem PCB 2/4 Wire Select Switch (SW4) 2 - Wire Operation Switch 1 → 2 - Wire Switch 2 → 2 - Wire Switch 3 → 2 - Wire Switch 4 → 2 - Wire MODEM 1 MODEM 2 MODEM 3 MODEM 4 4 - Wire Operation Switch 1 → 4 - Wire Switch 2 → 4 - Wire Switch 3 → 4 - Wire Switch 4 → 4 - Wire 1 2 4 - WIRE 2 - WIRE 3 4 SW4 Table 4 - Modem PCB Transformer Select Switch (SW5) Switch numbers (Corresponds to Modem with same number) 1 2 3 4 Set switch to 1 (Cl
TC12 Installation, Commissioning & Maintenance Handbook 2.2.4.3 Transformer PCB and Modem/Transformer Cable Figure 10 shows the layout of the Transformer PCB. Ensure that the correct variant has been supplied e.g. 666/1/02245/000 for the UK. 666/1/02245/000 or 666/1/02245/002 for non-UK. The PCB is fitted with a cover (part number 667/2/22647/000 top, /001 rear).
TC12 Installation, Commissioning & Maintenance Handbook Figure 11 - Transformer PCB Layout 37 S1 PL1 37 Way ‘D’ to MDF. Variant 1 (TOP) S2 PL2 14 Way to Modem PCB 1 (TOP) 14 S3 37 PL3 37 Way ‘D’ to MDF. S4 1 (TOP) Figure 12 - ITU 19" Rack (Rear View) ITU Rack 6U , System 24 Way connector to PC PSU Telephone line I/F 37 way ‘D’.
TC12 Installation, Commissioning & Maintenance Handbook 2.2.5 Digital Output Rack, PCBs and PSUs The digital output rack is the same size as the ITU rack except that 17 card guides are fitted. These take one PSU PCB and between 1 and 16 Digital Output PCBs. The assembly drawing for the rack is 667/GA/22626/001. One or two racks may be fitted to an Instation. 2.2.5.1 PSU PCB The PSU PCB is identical to the ITU rack PSU PCB so see section 2.2.4.1 for configuration details.
TC12 Installation, Commissioning & Maintenance Handbook Switch S1 PCB Address Set the switch on the card closest to the PSU PCB to 0, the next card to 1 and so on up to F if 16 boards are fitted. Connectors PL1 and PL2 These connectors are used to take the digital outputs out of the cabinet. Either a ribbon cable kit (667/1/22742/000) or a discrete wire cable kit (667/1/22742/001) are used to make up the cables on installation.
TC12 Installation, Commissioning & Maintenance Handbook Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 PL1 Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 Output 18 Output 19 Output 20 Output 21 Output 22 Output 23 Output 24 Output 25 Output 26 Output 27 Output 28 Output 29 Output 30 Output 31 XVCC XVCC XVCC XVCC XGND X
TC12 Installation, Commissioning & Maintenance Handbook Connector PL4 Connect cable 667/1/22744/000, a 14 way cable with 17 sockets, to PL5 of the PSU PCB and to PL4 of all the Digital Output PCBs in the rack. Connector PL5 Connect cable 667/1/22717/000 to PL5. The other end wires into a terminal block on the wall map PSU mounting panel, the other side of which connects to the DC outputs of the power supply. 2.2.5.
TC12 Installation, Commissioning & Maintenance Handbook (2) System with multiple PCs using Thinwire Cable Fit an Ethernet cable T piece (part number 667/7/22609/007) to the UTC TCC and the Ethernet card on each PC. Fit an Ethernet cable terminator (part number 667/7/22609/008) to the T piece on the UTC TCC. Fit the UTC TCC to PC Ethernet cable (part number 667/7/22609/006) between the Ethernet cable T pieces at the UTC TCC and the first PC.
TC12 Installation, Commissioning & Maintenance Handbook Figure 14 - Modem PCB - MDF Connections MODEM PCB - PL3 PIN 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37.
TC12 Installation, Commissioning & Maintenance Handbook 2.2.7.4 Transformer PCB to BT cable Figure 14 shows the cable terminations for connection to the MDF. Two identical cables are used (part number 667/1/22654/001). These connect to PL1 and PL3 on the appropriate Transformer PCB. The cable connected to PL1 connects all the OTUs associated with modems 1 and 2. The cable connected to PL3 connects all the OTUs associated with modems 3 and 4.
TC12 Installation, Commissioning & Maintenance Handbook Figure 15 - Transformer PCB - MDF Connections TRANSFORMER PCB PL1 and PL3 PIN 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37.
TC12 Installation, Commissioning & Maintenance Handbook 2.3 COMMISSIONING 2.3.1 Safety Tests on the TC12 Instation 2.3.1.1 Test Equipment Required Multimeter (e.g. Fluke 77 or similar). Comark Insulation Meter 1905 (or similar capable of 1000 V). Clare R133R10 Earth Continuity Tester (or similar). RCD Tester (e.g. Seaward RC500). 2.3.1.2 Safety Considerations Statutory and Company legislation relating to safety must be followed.
TC12 Installation, Commissioning & Maintenance Handbook Cabinet Side Cover stud left hand side Cabinet Side Cover stud right hand side Cabinet Top Cover Cabinet rear door Metal Part of front door along hinged side SIP Panel IMD Panel Master Switch Panel at the rear of the cabinet Master Switch panel cover (aluminium plate behind the master switch panel).
TC12 Installation, Commissioning & Maintenance Handbook 2.3.1.8 RCD Tests Turn the Instation master Switch OFF. Connect the Instation to the mains. Switch the Instation master Switch ON. Plug the RCD Tester into a mains socket at the front of the Instation. Set the trip current on the tester to 30 mA. Press the button on the tester. Check on the RCD tester display that the RCD has tripped within 200 ms. Reset the RCD. Set the trip current on the tester to 150 mA. Press the button on the tester.
TC12 Installation, Commissioning & Maintenance Handbook 2.4 MAINTENANCE 2.4.1 Status LEDs LEDs are provided on the front edge of the Modem Board and PSU Board to provide basic status information. The position of these LEDs and their functions are shown in Figure 16. Modem PCB All power LEDs on the modem PCB should be ON. The yellow transmit LEDs indicate that the particular modem has received a request to send. In normal working this means that the control signal is being transmitted on the line.
TC12 Installation, Commissioning & Maintenance Handbook Figure 16 - Modem and PSU PCB Status LEDs MODEM BOARD STATUS LEDs LP1 (RED LED) - +12v LP2 (RED LED) - -12v LP3 (RED LED) - +5v LP4 (YELLOW LED) - MODEM 1 TRANSMIT (TX1) LP5 (GREEN LED) - MODEM 1 RECEIVE (RX1) LP6 (YELLOW LED) - MODEM 2 TRANSMIT (TX2) LP7 (GREEN LED) - MODEM 2 RECEIVE (RX2) LP8 (YELLOW LED) - MODEM 3 TRANSMIT (TX3) LP9 (GREEN LED) - MODEM 3 RECEIVE (RX3) LP10 (YELLOW LED) - MODEM 4 TRANSMIT (TX4) LP11 (GREEN LED) - MODEM 4 RECEIVE (RX4
TC12 Installation, Commissioning & Maintenance Handbook This controls what signals can cause the low frequency audio alarm to sound. If it is incorrectly set, the alarm may sound for reasons other than those expected or may not sound when expected. (3) S3 - Audio ON/OFF If the audio alarm does not sound when expected check that this switch is set correctly. If it is set to off the audio off LED, on the front of the PCB, will be illuminated.
TC12 Installation, Commissioning & Maintenance Handbook b) 2 wire system but with 4 wire selected in error: No reply message will be received. Only the yellow LED for the modem will come on. (4) SW5 - Transformer Select Switch a) On board transformers required but off board set in error. No Control signal on the line and therefore no received signal. The yellow LED will be on and the green LED off. b) Off board transformers required but on board set in error.
TC12 Installation, Commissioning & Maintenance Handbook 2.4.6.2 PC Failure Symptom PC not Powered SIP PC 1 LED ON Possible Reason PC Switched off. Power cable disconnected/faulty. Mains plug fuse blown Master switch panel off/fuse blown. PC faulty. Digi I/O card card/cables installed incorrectly. Digi I/O card faulty. PC Not running TC12 software. Check software installation and re-boot PC. Software has failed - ignore all other SIP LEDs/audio (software driven). Re-boot PC.
TC12 Installation, Commissioning & Maintenance Handbook Symptom Watchdog Fail LED ON for only one Digital Output PCB of several Digital Outputs Not Driven Possible Reason PSU to Digital Output PCB watchdog ribbon cable faulty/not connected Watchdog ribbon cable faulty Digital Output PCB faulty Watchdog Failure Digital Output PCB fuse(s) blown Incorrect/faulty wiring Digital Output PSU not connected Digital Output PSU fuse blown/faulty 2.4.
TC12 Installation, Commissioning & Maintenance Handbook The remaining characters on each line are the hexadecimal representation of the reply bytes (__ means no data) for that OTU, each line is the correct length (number of characters) for the number of reply bytes for the OTU. 2.4.8.3 First 22 TC8 OTUs on an Instation, Key to Press '8' This screen displays the replies received from the first 22 TC8 OTUs on an Instation. It displays each OTUs reply on a separate line on the screen OTU 0 at top.
TC12 Installation, Commissioning & Maintenance Handbook 2.4.8.4 Active tasks, RX/TX packets and time events, Key to Press 'A' This screen, as its name suggests, shows the processes going on within the Instation against time, each dot represents 400ths of a second and the screen shows processes in any one second.
TC12 Installation, Commissioning & Maintenance Handbook 7= Low priority message ready from UTC TCC to output e.g. digital outputs 6= Replies to a particular host UTC TCC where the Instation is only handling digital Output for the particular host UTC TCC, with delays on answering to maintain communication timings. 5= Configuration processing i.e. processing of configuration packets from host UTC TCC to setup Instation. 4= Sumchecking IMDs done at beginning of every second (top left hand corner of display.
TC12 Installation, Commissioning & Maintenance Handbook 2.4.8.7 Digital Outputs states, Key to Press 'D' This screen displays the output states, of the first 24 TC12 digital output boards; each line represents 64 digital outputs i.e. one board. As there is the possibility of 16 boards in a rack the first 16 lines therefore would represent first rack. This display is in colour and CTERM should be switched into the colour mode to gain any information from this screen Press CNTRL K.
TC12 Installation, Commissioning & Maintenance Handbook 2.4.8.11 IMD Information Screen, Key to Press 'I' This provides information about the Intelligent Modem Driver boards in the PC as follows. Top Line: Address of the dual ported RAM through which the PC communicates with the IMDs. Below this there are details of each of the four possible IMDs, as follows. Status of the IMD: Either OK / NOT INSTALLED / FAULTY / SUM CHECK ERROR. Followed by a series of digits.
TC12 Installation, Commissioning & Maintenance Handbook 2.4.8.12 Link Statistics, Key to Press 'L' This screen gives details of the Ethernet link to the host UTC TCC. The addresses of the Instation on the Ethernet The type of driver card being used Thin wire, Thick wire or both as detected by the driver software Type of Ethernet card selected when installation programme used The type of communication being used NB The count increments against the form of communication being used.
TC12 Installation, Commissioning & Maintenance Handbook 2.4.8.15 Received Characters IMD, Key to Press 'R' This screen displays the data received from OTUs on IMD 0 port 0. It displays each OTUs reply on a separate line on the screen OTU 0 at top. This screen only shows the OTUs on IMD 0 port 0 but can be used to obtain indication of the health of the system.
TC12 Installation, Commissioning & Maintenance Handbook Figure 17 - Master Switch Panel Fuses MASTER SW CABINET RCD FS1 FS2 FS3 FS4 FS5 FS6 FS7 5A FRONT 13A SKT 5A REAR 13A SKT 5A MAINS SKT B 5A MAINS SKT C 5A MAINS SKT D 5A MAINS SKT E 10A WALL MAP PSU Master Switch and RCD. The diagram above shows the layout of the fuses on the Master Switch Panel assembly. The position of the fuses FS1 to FS7 is shown along with the fuse value. Fuse FS1 protects the front Mains sockets.
TC12 Installation, Commissioning & Maintenance Handbook The voltage between TP8, AGND and TP4, +12 V should be between 12.6 V and 11.4 V. The voltage between TP8, AGND and TP9, -12 V should be between -12.6 V and 11.4 V. 2.4.11 Digital Output PCB The digital output PCB is fitted with four 3.15 A, 250 V Quick Blow fuses (part number 518/4/97023/007), FS1 to FS4. These protect the power supply to the digital outputs. 2.4.12 Recommended Spares The TC12 Family Tree part number is 667/DZ/22600/000.
TC12 Installation, Commissioning & Maintenance Handbook 3 TC12 OUTSTATION 3.1 SPECIFICATION 3.1.1 Mains voltage ranges The Outstation will work over: 85 – 264 V RMS Note the power supply used is auto-ranging over the above voltage range. 3.1.2 Mains frequency range All TC12 equipment will work from 47 Hz to 63 Hz. 3.1.3 Mains current OTU rack including four Detector cards 250 mA at 240 V 3.1.4 Temperature and humidity requirements The OTU will work over -15 °C to 75 °C.
TC12 Installation, Commissioning & Maintenance Handbook - Connect the cabling - Configure the Outstation using the Handset terminal The items that need configuring include: Output Power Level (Switch S3) Receive Threshold (Switch S3) 2 or 4 Wire Line Connection (Switch S4) 600 Ω / High Impedance Line Termination (Switch S6) Instation Communications Method (Jumpers) Baud Rate / Mode (GMM) Outstation Address (GAD) Number of Outstations on the Line (GNO) Number of Control Bytes for all Outstations on the line
TC12 Installation, Commissioning & Maintenance Handbook Figure 18 - OUTSTATION PCB LAYOUT LP7 +5V LED Firmw are PRO M SK1 25 Way Connector to Handset terminal PL1 50-Way connector to LMU inputs 1 1 (TOP) PL2 40 Way for 32 buffered inputs 40 LP2 LP3 LP4 Status LEDs 50 Lithium Battery S2 ON / OFF 14 LP 5 SK2 FS2 Fuse for Buffered inputs, +24V Line Level S3 S4 SK3 2/4 Wire Selector 1 (TOP) PL3 14-Way connector to PSU B1 Battery Line Jack Sockets 1 PL4 34 Way for 16 Relay outputs & Trans
TC12 Installation, Commissioning & Maintenance Handbook 3.2.2.1 Safety Warning The TC12 Outstation PCB contains a lithium battery, B1 on Figure 18 and Figure 19. Care must be taken with the use and disposal of this battery. The handling precautions in code of practice CP526 must be followed. 3.2.2.2 Cover The PCB is fitted with a cover (part number 667/2/22610/000 front, /001 rear). UK Usage 0 WARNING 0 FOR UK USAGE THERE ARE NO USER ACCESSIBLE PARTS UNDER THE COVER.
TC12 Installation, Commissioning & Maintenance Handbook For UK use the output power is always set to -13dBm and the receive threshold is set to –39dBm. No other setting except for –13dBm is to be used in the UK for the output power setting. 4. S4 - 2 / 4 Wire Select Switch Set the 2/4 Wire Select Switch to the setting indicated on the installation sheet for the Outstation (see Figure 21 for switch positions). 5.
TC12 Installation, Commissioning & Maintenance Handbook BATTERY ON ON S2 BAT BATTERY OFF OFF Information on the silk screen Figure 20 - OTU Lithium Battery On / Off Switch (S2) 4W 2 - WIRE OPERATION 1 A 4 - WIRE 2W S4 OPERATION Information on Silk Screen Figure 21 - OTU 2/4 WIRE SELECT SWITCH (S4) 600 OHM LINE TERMINATION HI-Z S6 600 Information on the silk screen HIGH IMPEDANCE LINE TERMINATION Figure 22 - OTU 600 Ω High Impedance Switch (S6) 666/HE/43100/000 Page 67 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook Table 5 - OTU Line Level Switch (S3) OUTPUT POWER SWITCH NUMBERS 3 4 1 0 dB 1 0 0 0 -3 dB 1 0 0 1 -6 dB 0 1 0 0 -9 dB 0 1 0 1 -10 dB 0 0 1 0 -13 dB 0 0 0 0 -16 dB 0 0 0 1 2 5 6 SEE BELOW Å Æ RECEIVE THRESHOLD -42 dB 0 0 -39 dB 0 1 1 0 SEE ABOVE -33 dB = Setting for the UK 0 = Switch Open 1 = Switch Closed 3.2.2.
TC12 Installation, Commissioning & Maintenance Handbook The GRX handset command (see section 3.3.3.8) must be used together with the above jumper positions in order to activate the desired communications interface. 3.2.3 Connectors and Cables 3.2.3.1 PSU Cable - OTU and Detectors Connect the PSU cable (part number 667/1/22690/000) to the Outstation PCB. This cable connects from the power supply to the 14-way connector, PL3 on the PCB.
TC12 Installation, Commissioning & Maintenance Handbook The ferrite core should be cable tied to a suitable point in the traffic controller, or a suitable place on the OTU mechanics (e.g. on top of the detector racking), if it is likely to interfere with the controller door or any other installed equipment.
TC12 Installation, Commissioning & Maintenance Handbook 3.2.3.4 RS232 Cable The RS232 cable (667/1/22611/000) supplied with the OTU has flying leads at the data transmission end of the cable and a keyed 14-way Berg connector at the OTU end of the cable. The OTU to data transmission system serial interface complies with RS232 at the OTU connector using the signals and pin allocations defined in the following table.
TC12 Installation, Commissioning & Maintenance Handbook 3.2.3.5 Input/Output Cable Connect the Input/Output Cable (part number 667/1/22693/000) to 40-way connector PL2 and 34-way connector PL4. Note. When pushing the connectors into PL2 and PL4 the OTU PCB must be supported from underneath to stop the board from bending and possible damage being caused. Refer to Drawing 667/GA/22693/000 for wire colours of particular inputs and outputs (inputs are labelled R1, R2, etc. and outputs are labelled C1, C2, etc.
TC12 Installation, Commissioning & Maintenance Handbook Figure 25 - Outstation Input Connections OUTSTATION PROCESSOR PCB - PL2 40-way connector to buffered inputs.
TC12 Installation, Commissioning & Maintenance Handbook Figure 26 - Outstation Output Connections OUTSTATION PROCESSOR PCB - PL4 34-way connector to Relay Outputs. PIN 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 NAME Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Transmit Confirm Relay Output 3.2.3.
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 75 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook Figure 27 - Freestanding Outstation Inputs 666/HE/43100/000 Page 76 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook 666/HE/43100/000 Page 77 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook 3.2.4 Lamp Monitor Unit Connections NOTE.RED LAMP MONITORING is not approved by the Department of Transport and should not be used. If the installation uses the lamp monitoring facility then Current and voltage monitoring transformers are connected to PL1 on the OTU PCB via a 54-way connector housing (part number 508/4/26138/004).
TC12 Installation, Commissioning & Maintenance Handbook Table 6 - Outstation Processor PCB - PL1 50-way connector to LMU inputs.
TC12 Installation, Commissioning & Maintenance Handbook 3.2.5 Current Transformer Ratings Each controller phase or illuminated indicator that is to be monitored requires one current sensor 667/7/25171/000 as detailed below. The table also indicates which lamp feeds are passed through the current sense transformer for each type.
TC12 Installation, Commissioning & Maintenance Handbook maximum loads when a 50-0-50 V RMS mains supply is used. The limits are only reduced if the actual voltage being monitored is at the lower level, i.e. if a 50-0-50 V RMS supply (derived from a transformer) is used but the monitoring is on the 240 V RMS side of the transformer, then the limits do not need to be reduced. If the nominal load current (including red/ambers) of a particular controller output exceeds 4.
TC12 Installation, Commissioning & Maintenance Handbook Voltage Monitoring Transformer A Voltage monitoring transformer (part number 667/7/25172/000) is used per Outstation when equipped with LMU facilities. The red and black wires connect to the lamp supply mains live and neutral being monitored (Red to Live and Black to Neutral). The orange and white output wires connect to PL1. Referring to Figure 35 the orange wire connects to pin 49 (ZXO Input +) and the white wire connects to pin 50 (ZXO Input -.
TC12 Installation, Commissioning & Maintenance Handbook Leaving phase delays. Use of phases that are not fixed in the stage. b) Using voltage sense transformers to produce a suitable logic signal direct from the lamp drive voltage. Note: If voltage sensors are used to monitor a dimmed 50-0-50 V RMS supply (on the 50-0-50 V RMS side of the transformer), they will only work down to the first dim voltage tapping (i.e. dimming to 66% of the nominal undimmed voltage).
TC12 Installation, Commissioning & Maintenance Handbook Number of Current Sensors Number of phases (include vehicle, green arrow and pedestrian phases Number of pedestrian phases with wait indicators +___ Number of switched sign drives +___ Number of separately monitored regulatory sign drives +___ Add one for each monitored load above 4A rms +___ Subtract one for each wait indicator to be monitored by the same current sensor as the pedestrian phase Subtract one for each pedestrian phase to be monit
TC12 Installation, Commissioning & Maintenance Handbook 3.2.7 TC12 Outstation Mechanical Modules and Number of Detectors Supported There are five separate mechanical modules available for the TC12 Outstation.
TC12 Installation, Commissioning & Maintenance Handbook 3.3 COMMISSIONING 3.3.1 Safety Tests on the TC12 Outstation 3.3.1.1 Test Equipment Multimeter (e.g. Fluke 77 or similar). Comark Insulation Meter 1905 (or similar capable of 1000 V). Clare R133R10 Earth Continuity Tester (or similar). RCD Tester (e.g. Seaward RC500). 3.3.1.2 Safety Considerations Statutory and Company legislation relating to safety must be followed.
TC12 Installation, Commissioning & Maintenance Handbook PCB Mounting plate PCB Frame Rack Cross members Rack Side plate Case of power supply Power supply 0 V (pin 4 on OTU PSU 14-way connector, see Figure 18). All earthed points on any other equipment that may have been attached to the OTU mechanics. 3.3.1.7 Insulation Resistance Test Procedure Safety Note Personnel should take care that they do not come into contact with the high voltages generated by the Test Instrument.
TC12 Installation, Commissioning & Maintenance Handbook terminal connected to the Controller are in the correct position and are the correct value. Checking OTU Input wiring: Attach a handset to the controller and enter controller handset commands to set the status of the 16 controller outputs. Set different output bit patterns on the controller handset terminal. Attach a handset to the OTU and enter commands to display the status of the OTU inputs.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.2 OTU reset (CNN, LRN, TKE) (1) CNN=??? (2) LRN=??? (3) TKE=??? Comment: The above reset commands may be entered in any order, the reset is actioned by switching the OTU power off for a few seconds then re-applying power. On restart the default OTU configuration data will replace all existing configuration data. Commands to set up communication with the Instation GAD, GMM, GNO, GCW, GRW 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook Comment: The above command is repeated for each OTU on the telephone line. For each OTU enter its address and the number of reply words it uses. 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook normal direction loop connects (the reverse direction loop is connected to the next input after the normal direction loop). Note. The 32 inputs are numbered 1 to 32 in section 3.2.3.5, corresponding to the associated pin on the 40 way input connector, however the handset command numbers the inputs from 0 to 31, for the 32 inputs. The controller provides U/D for an Integral OTU. See the Controller Handset Commands CUD and UDT.
TC12 Installation, Commissioning & Maintenance Handbook 45 = 46 = Any lamp failure Any Red failure Note: These bits are also set if the lamps are switched off at the controller. If dual controller monitoring is configured switching either controller lamps off will set these bits. If independent monitoring is required use separate group outputs allocated to each controller.
TC12 Installation, Commissioning & Maintenance Handbook 3) There will be a separate bit allocated for each loop monitored by HIOCC. There is a maximum of eight loops in total. Eight new reply bit functions have been allocated, as above. 3.3.3.14 OTU output bit source (GOL, KOL) GOL {Output bit number: 0 - 15} = { Output function: 0 - 255 } (0) Comment: Defines the function of the OTU hardware outputs. The output function is as described for the GRL command above.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.17 Queue unit inactive time (Cancel time) (GIQ) GIQ{Count/Occupancy/Queue unit no.:0 to 5}={Queue inactive time.:0 to 255} (0) Comment: To specify the time in seconds that a configured queue unit input must be inactive before its output which was previously active is cleared. 3.3.3.18 Count weighting factor (GCF) GCF{Count unit no.:0 to 5} = {Count weighting factor code.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.20 Input sense control (GIS) GIS{Group of 8 inputs: 0 to 3} = {Binary byte to indicate polarity of each Input, 1 = inverted (default 0), see below} Comment: Enables any of the 32 buffered inputs to be inverted. This facility is required to cater for detectors with normally open output contacts.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.24 DFM time limit (GMG) GMG {input byte select: 0-11} {input bit select: 0-7} = {group select: 0-7,255} Comment: Used to select the DFM time limits set up by GMA and GMI for the input specified. The default value for all inputs is 255, which indicates that no DFM is required on those inputs. To start the monitoring of an input, use this command to allocate an input to a DFM group.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.27 Display Fault Flags (GLF) GLF (Fault flag number : 0-31) Comment: When the OTU detects a recognised fault the system error led is illuminated and an entry made in the fault log. The majority of the fault flags are set to 1 (i.e. bit 0 set) to indicate a fault, however flags 0,1 and 2 are a special case where each bit represents a lamp fault for a particular current sensor.
TC12 Installation, Commissioning & Maintenance Handbook 13 Hardware fault 14 OTU battery switch off Comment: Configuration data will be lost Reset OTU and re-enter configuration data 15 DFM failure 16 [PB392] Facility not available (The facility is not allowed on this board. See GAF/KAF and GPV/KPV commands) 17 Controller configuration changed Integral OTU only. See the Controller Handset Handbook information on the Integral OTU for more information.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.28 Display Fault Data (GLD) GLD (Fault data index : 0 - 227) Comment: To examine fault data associated with certain fault flags Fault data index 0 - 215 Lamp Fault Data (Fault flags 0 - 3 Lamp Faults) If the KLP command is supported this information is also available using KLP.
TC12 Installation, Commissioning & Maintenance Handbook Phase types 19 to 22 (Pedestrians with 40 Watt Waits) may report two lamp faults for only one lamp failure. Consequently these types will automatically clear all the faults when one lamp is replaced.
TC12 Installation, Commissioning & Maintenance Handbook es await 20ms/100ms tick error es sp list empty error es ready range error es task range error es aa event range error es event range error es image range error es dummy load task case error interrupt in-service stack overflow errors – ZXO interrupt in-service stack overflow errors – tick interrupt in-service stack overflow errors – peak interrupt in-service stack overflow errors – UTC RX interrupt in-service stack overflow errors – UTC TX interrupt in
TC12 Installation, Commissioning & Maintenance Handbook Free Standing OTU interface task errors - Function Group 7: free standing interface task case out of range 1 free standing interface task port verify error 2 LMU task errors - Function Group 8: LMU task case out of range LMU RLM data fault RAM fault 1 2 3 Interrupt Function errors - Function Group 9: local port verify error ADC failure error 1 2 DFM Task error - Function Group A DFM task case out of range 1 Fault data index 227 Hard Error Code (F
TC12 Installation, Commissioning & Maintenance Handbook Indexes can be used as follows: KLP [ [aspect ID: 0-6>]] If no index is used the lowest value is used as default, hence, ‘KLP’ on its own is the same as ‘KLP 1’ and ‘KLP 1 0’. If a sensor is not configured (or configured as type ‘0’), or the aspect pattern requested is not used by the phase type, then KLP displays just the sensor number and aspect ID number followed by the number of faults, i.e. “KLP S A: +I -F” 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook For sensors monitoring a phase or wait indicator, the value entered defines the phase identity, i.e. 0=phase A, 1=phase B, 2=phase C etc. For sensors monitoring a vehicle and a pedestrian phase together, the value entered defines the vehicle phase identity and the pedestrian phase is by default allocated the next phase identity, e.g. a value of 0 allocates the vehicle to phase A and by default the pedestrian is allocated phase B.
TC12 Installation, Commissioning & Maintenance Handbook KFD 1 = (input number: 0 - 31) (255 to disable). This allocates a mains state input driven by the actual flashing supply. Note 1.Only one of the above input types must be configured. Note 2.The 32 inputs are numbered 1 to 32 in section 3.2.3.5, corresponding to the associated pin on the 40 way input connector, however the handset command numbers the inputs from 0 to 31, for the 32 inputs.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.37 Mains states input configuration (KMS) L KMS {mains state input: 0-2 }{ sensor: 1 - 23 }= Input line number: {0 - 31} (255) This item defines the digital inputs that provide the mains state(s) for the associated current sensor. Up to three input line numbers are required depending on the phase type being monitored (see table below).
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.38 Phase type for current sensor (KPT) L KPT {sensor number: 1 - 23} = {phase type no.: 0 - 255} Comment: To specify the lamp or phase type for a current sensor as defined in the table below. See GLD command for further information on how lamp faults are reported.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.41 Disable/enable Lamp Monitor (KLE) KLE = 0 or 1 Comment: To enable or disable the Lamp Monitor facility (1 = enabled) 3.3.3.42 Lamp Monitor reset (KLR) KLR = 1 Comment: Causes LMU to reset and relearn the lamp characteristics. This command must always be used before enabling the LMU for the first time. 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.48 Enable 50-0-50 V rms LMU Operation (KLV) KLV=1 (0) Comment: Set to 1 to enable LMU operation when a 50-0-50 V rms mains supply is being monitored. The default value is 0 for a 240 V rms mains supply. Note. This facility is included in PB391 issue 2 firmware (and above). Diagnostic Display Commands 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.53 Display PLD Variant (GPV, KPV) GPV Comment: Displays PLD Reference Number and Issue State. 3.3.3.54 Display Reply Data (GRD) GRD (reply byte number: 0 - 14) Comment: Enables the reply data currently being transmitted to the instation to be displayed in binary format. Note: GRD 0 displays the first byte of the reply message that is the OTU address, MT bit etc. The first byte of reply data is accessed using GRD 1.
TC12 Installation, Commissioning & Maintenance Handbook The meaning of each bit is listed below: Bit 0 - AWAIT_DIM - Aspect not yet appeared in DIM Set if current dim/bright state is known to be bright and AWAIT_DIM_CHANGE is set. Cleared when dim/bright state is dim and AWAIT_DIM_CHANGE is clear Bit 1 - AWAIT_BRIGHT - Aspect not yet appeared in BRIGHT Set if current dim/bright state is known to be dim and AWAIT_DIM_CHANGE is set. Cleared when dim/bright state is bright and AWAIT_DIM_CHANGE is clear.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.62 Display Mains State Inputs (KDI) KDI (input port number: 0 - 3) Comment: Enables the state of the LMU mains state inputs to be displayed in binary format. The state of the input is only sampled at mains peaks so that the value displayed indicates whether the particular mains supply is on or off (because the voltage sensor output fluctuates depending on the point in the mains cycle, if the input was sampled at other times e.g.
TC12 Installation, Commissioning & Maintenance Handbook Test / Maintenance Commands 3.3.3.66 Flow Counters (GCU) GCU (Unit number: 0 - 5) Comment: Enables the flow counters to be displayed. Note: The counts are stored as words, so only the least significant byte is displayed. 3.3.3.67 Occupancy Counters (GOU) GOU (Unit number: 0 - 5) Comment: Enables the occupancy counters to be displayed. Note: The counts are stored as words, so only the least significant byte is displayed. 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.72 Override Digital Outputs Timeout (GOT) GOT=(1-254 minutes, 255 disable timecount) Comment: Displays the current timeout value, normally one minute. With a special PLD (667/1/12399/106 - VMS + LMU), the value can be changed. Without the special PLD, the value will always return one minute for reasons of safety. Note The timeout facility is only present on PB392 issue 6 or later firmware.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.3.78 High Occupancy, timed zero occupancy (GHZ) GHZ = {time in seconds: 0-255} (8) Comment: Zero occupancy will be assumed after the pre-set time. 3.3.3.79 High Occupancy, smoothed occupancy high value (GHV) GHV = {percentage smoothed occupancy high level: 0-100} (90) Comment: Smoothed occupancy high value used for alarm detection. 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook Engineering and Special Function Commands The following commands are for engineering diagnostic use only and would not normally be required for maintenance operations. Refer to Siemens Engineering for further information. 3.3.3.86 Scheduler Dummy Routine Control (GDC, KDC) 3.3.3.87 Engineering Display Base (GEB, KEB) 3.3.3.88 Display Engineering data Items (GEG, KEG) 3.3.3.89 Display Engineering RAM data (GER, KER) 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.4 Examples of Lamp Monitor Unit Configuration Using the Handset NOTE.RED LAMP MONITORING on the Freestanding OTU is not approved by the Department of Transport and should not be used. The LMU is configured via the handset and there are several example configurations detailed on the following pages.
TC12 Installation, Commissioning & Maintenance Handbook Allocate function of each current sensor: KPT 1 = 1 KPT 2 = 1 :current sensor 1 monitors a vehicle phase :current sensor 2 monitors a vehicle phase Allocate mains state inputs for each current sensor: Note: Input numbers 1 to 32 on the buffered input connector are referenced as 0 to 31 on the handset commands.
TC12 Installation, Commissioning & Maintenance Handbook KPT 1 = 1 KPT 2 = 1 KPT 3 = 3 KPT 4 = 3 KPT 5 = 5 KPT 6 = 5 KPT 7 = 8 KPT 8 = 9 KPT 9 = 7 :a vehicle phase :a vehicle phase :a pedestrian phase :a pedestrian phase :40 Watt wait indicators :40 Watt wait indicators :switched sign (bulb type) :switched sign (tube type) :regulatory sign Allocate the mains state inputs associated with each current sensor: Note: Input numbers 1 to 32 on the buffered input connector are referenced as 0 to 31 on the handset
TC12 Installation, Commissioning & Maintenance Handbook KRE 2 = 0 :sensor 2 Turn off dim/bright checks: KDP = 0 Example 3 - 4 phase controller Description: Four phase intersection controller with two vehicle and two pedestrian phases. Each pedestrian phase is monitored with a single current sensor (see example 2 for separate wait and pedestrian monitoring using two current sensors per phase) The configuration commands are detailed below.
TC12 Installation, Commissioning & Maintenance Handbook KAD 3 = 2 KAD 4 = 3 :sensor 3 is phase C :sensor 4 is phase D Select normal lamp monitoring (not RLM) on vehicle phases: Note: Sensors 3 and 4 do not monitor vehicle phases and so their configuration does not need to be changed. KRE 1 = 0 KRE 2 = 0 :sensor 1 :sensor 2 Example 4 - Pelican (single current sensor) Description: This is a pelican controller with dimming.
TC12 Installation, Commissioning & Maintenance Handbook In this example, the pelican is monitored with three current sensors (see example 4 for combined wait, pedestrian and vehicle monitoring using a single current sensor). The configuration commands are detailed below.
TC12 Installation, Commissioning & Maintenance Handbook Phase D green cannot be monitored using a standard UTC 'G' bit because it will stay at green when the phase appears in successive stages. It must monitored using a voltage sensor. Other phases in the stage with phase D may still be monitored (i.e. Phase F) using 'G' bits, providing that they meet the normal requirements. Note that voltage sense transformers are normally assigned sequentially starting at digital input 31 and working back through 30 etc.
TC12 Installation, Commissioning & Maintenance Handbook Allocate aspect drive identity to each current sensor: NOTE: No aspect drive required for regulatory sign.
TC12 Installation, Commissioning & Maintenance Handbook Figure 29 - Phases in Stages for Example 6 PHASE STAGE 1 STAGE 2 STAGE 3 STAGE 4 A (Traffic) B (Traffic) C (Traffic) D (Traffic) E (Traffic) F (Traffic) G (G/Arrow) H (PED) UTC REPLY G1 G2 G3 G4 Phases A to F are Vehicle phases of Type 0 appearance and termination. Phase G is a Green Arrow of Type 2 appearance, terminating when E gains ROW Phase H is a Pedestrian phase of Type 1 appearance. 3.3.4.
TC12 Installation, Commissioning & Maintenance Handbook Note: If dimming is fitted to the controller, force the signals to dim and allow the LMU to learn the lamps in the dim state. A more detailed description of junction learning and lamp failure checking is provided in the following sections. 3.3.4.2 Junction Self Learning during Commissioning Force the controller to cycle round all the stages (e.g. by switching into fixed time mode) and initiate learning using the KLR and KLE commands.
TC12 Installation, Commissioning & Maintenance Handbook junction have been learnt in that state. If the learning of the second state is left to occur automatically at the next dim/bright change, and the lamp failure occurs during or just after the change, it will not be detected by the LMU until the controller reverts back to the original state in which the junction learning was invoked. 3.3.4.
TC12 Installation, Commissioning & Maintenance Handbook 3.3.5 TCSU TC12 OTU Commissioning Procedure Reset OTU and select TCSU default configuration data. Enter the following commands: GME=249 (Access code) LRN=53 } CNN=117 } (Reset Codes) TKE=191 } Remove Mains power from the OTU, wait for a few seconds, then re-apply power. Note: The value of 191 for TKE selects TCSU default configuration data but only when used to perform a complete OTU reset as detailed above.
TC12 Installation, Commissioning & Maintenance Handbook The following table shows the TCSU default configuration values: Table 7 - TCSU default configuration values SUMMARY OF DEFAULT CONFIGURATION DATA CHANGES FOR TCSU TC12 OTU Handset Item GNO Standard 1 TCSU 6 GRW0 → GRW5 GSA0 → GSA11 4 No SCOOT loops allocated (255) GRL2 0 etc From OTU input (0) 6 GSA0 = 16 GSA1 = 17 GSA2 = 18 GSA3 = 19 GSA4 = 20 GSA5 = 21 GSA6 = 22 GSA7 = 23 GRL2 0 =21 GRL2 4 =22 GRL3 0 =23 GRL3 4 =24 GRL4 0 =25 GRL4 4 =26 GRL5
TC12 Installation, Commissioning & Maintenance Handbook 3.4 MAINTENANCE 3.4.1 Status LEDs LEDs are provided on the front edge of the board to provide basic status information. The position of these LEDs and their functions are shown in Figure 30. The +5 V LED should be on. If the system fail LED is on, information about the type of fault that has occurred can be accessed using a handset terminal (see section 3.3.3.27 on handset commands).
TC12 Installation, Commissioning & Maintenance Handbook Figure 30 - Outstation PCB Status LEDs LP7 (GREEN LED) - +5v LP2 (RED LED) - SYST EM FAIL LP3 (RED LED) - WAT CHDOGFAIL LP4 (GREEN LED) - T RANSMIT CONFIRM LP5 (GREEN LED) - CARRIER DET ECT / RX DATA 666/HE/43100/000 Page 131 Issue 9
TC12 Installation, Commissioning & Maintenance Handbook 3.4.2 Effect of Incorrect Switch Settings on the OTU PCB (1) S2 - Lithium Battery On/Off Switch If this switch is off the system fail LED will illuminate on the OTU PCB the OTU will not communicate with the Instation. (2) S3 - Line level switch A 6-way DIL switch is used to set line levels. If switch positions 1 to 4 of the DIL switch are set incorrectly the OTU will transmit at the wrong output power.
TC12 Installation, Commissioning & Maintenance Handbook Symptom No power to handset terminal Possible Reason Check handset fuse 3.4.4 Fuses 3.4.4.1 Outstation PCB Fuses The outstation PCB is fitted with two fuses - FS1 and FS2; see Figure 18 for the position of the fuses. Fuse FS1 is used to protect the +5 V supply for the handset terminal. Fuse FS2 is used to protect the +24 V for the 32 Digital Inputs. Both fuses are 500 mA 250 V Quick Blow 20x5 mm, part number 518/4/90285/004. 3.4.4.
TC12 Installation, Commissioning & Maintenance Handbook retaining screws line up with large holes in the slots for the screws. The power supply can be taken off by moving it sideways. Power Supply Tests If the power supply is suspected as being faulty, check the output voltage of the power supply on the Outstation. Make sure the Outstation is powered down. Disconnect the 13-way connector from the end of the power supply. Power up the Outstation. Check the +5 V output is between 4.75 V and 5.
TC12 Installation, Commissioning & Maintenance Handbook 3.4.7 Recommended Spares The TC12 Family Tree part number is 667/DZ/22600/000. This shows the structure of part numbers within the TC12 system. The top level part number for the TC12 Freestanding OTU is 667/1/22670/000. Outstation PCB Fuses FS1 and FS2 are 500mA 250 V 20x5 mm Quick Blow fuse 518/4/90285/004. 5 V Supply Fuse on the OTU Module Assembly: The 5 V signal from the PSU is fitted with a 5 A 32 V 1.
TC12 Installation, Commissioning & Maintenance Handbook 4 TC12 INSTATION TEST SET 4.1 SPECIFICATION 4.1.1 Mains voltage and frequency ranges The Instation test set will work over: 98 – 132 V RMS @ 47-63 Hz 198 – 264 V RMS @ 47-63 Hz Note. The voltage range of the PC used in the Instation Test Set should be checked in the manufacturer's literature and note should be taken of any links/switches that need setting for different voltage ranges. 4.1.2 Mains Current Instation test set 400 mA at 240 V 4.1.
TC12 Installation, Commissioning & Maintenance Handbook 4.2 INSTALLATION 4.2.1 Setting the Working Voltage Range Of the Instation Test Set The power supply for the modem PCB and Instation Test Set Logic PCB is the same type as used on the Instation PSU PCB. Refer to section 2.2.4.1 for a description of how to set the voltage range of this power supply. Note.
TC12 Installation, Commissioning & Maintenance Handbook Check that the mains switch on the test set is on and illuminated, indicating mains supply is reaching the test set. Check that low voltage DC is present on the PCBs. Look at power monitor LEDs etc on test set modem PCB, by looking down at the rear of the PC where the LEDs are visible below the edge of the PC. The power monitor LEDs on the modem PCB should indicate that power is reaching the logic PCB, as the modem PCB is powered via the logic PCB.
TC12 Installation, Commissioning & Maintenance Handbook 4.3 OVERVIEW OF THE TC12 INSTATION TEST SET SETTINGS/SELECTIONS AND CONNECTIONS 4.3.1 Introduction The TC12 Instation test set (part number 667/1/22702/000) is used to monitor and test the operation of the TC12 system. It can be used at all the TC12 baud rates and at any signal level between 0dBm and -63dBm. There is a pair of headphones that may be connected to the ITS to allow the user to listen to both control and reply messages.
TC12 Installation, Commissioning & Maintenance Handbook 4.3.2.3 Connection to OTU PCB There are two sockets on the front of the OTU PCB. The sockets are labelled on the silk screen. The top socket is reply and the bottom socket is control. 4.3.3 Front Panel Switches 4.3.3.1 Mains Switch Mains switch and PC switch Switching the Test Set off, using the rocker switch on the front panel, does NOT guarantee isolation from the mains. 4.3.3.
TC12 Installation, Commissioning & Maintenance Handbook 4.3.3.3 Carrier Detect Level Switch This switch selects the carrier detect sensitivity when: The test set is in Instation mode and is receiving Reply messages from OTUs. The test set is in Outstation Mode and is receiving Control messages from the Instation.
TC12 Installation, Commissioning & Maintenance Handbook and the appropriate cable connected from the test set HANDSET socket to the TC12 Instation PC serial port 1.
TC12 Installation, Commissioning & Maintenance Handbook 4.4 OVERVIEW OF TEST SET SOFTWARE SETTINGS/SELECTIONS AND OPERATION 4.4.1 Modes of Operation 4.4.1.1 Monitor Mode Monitor mode allows control and reply messages to be monitored at either the Instation or at an OTU. When the ITS is operating in this mode, the operation of any key (except the mode selection key) has no effect on the data being transmitted between the Instation and the OTU.
TC12 Installation, Commissioning & Maintenance Handbook MONITOR MODE monitors i.e. receives both control and reply messages from the line picking out the particular parts/messages associated with the selected/OTU under test. Whilst continuing to allow free communications between Instation and Outstations. INSTATION MODE Simulates the Instation.
TC12 Installation, Commissioning & Maintenance Handbook 4.5 USING THE TEST SET FOR FAULT FINDING ON TC12 SYSTEM 4.5.1 General By connecting the test set into the TC12 system both at the Instation and Outstation and using the three modes available, it should be possible to isolate the item causing the problem i.e. the Instation, Outstation or the line between the two. 4.5.
TC12 Installation, Commissioning & Maintenance Handbook "RECALL" and enter relevant filename or choose from directory of "DATA" directory, and recall it (Press enter whilst on filename field). ELSE Go to "SYSTEM SET UP" and select "OTU INFO". Now enter the number of OTUs on the line, and then for each of those OTUs enter its number of control and reply bytes in the appropriate fields.
TC12 Installation, Commissioning & Maintenance Handbook IOR MTS SCM/SRM CNL1/CNL2 CMSL / RMSL RSE RTE Address of OTU in message received whilst expecting reply from OTU under test, was not address of OTU under test. MT bit set in reply message received from OTU under test. Short Control / Reply Message, i.e. insufficient bytes received. Port1 / Port2 Carrier not low when expected.
TC12 Installation, Commissioning & Maintenance Handbook If ONLY any of the following faults are recorded when in Outstation or Monitor mode, Whilst OTUs respond with out faults to test set in Instation mode: RTS (amber led) on Instation modem board not lighting On test set, both Control and Reply Idle or only Control Idle, and/or CD indicator not showing carrier being detected. POSSIBLE FAULT: Instation not transmitting.
TC12 Installation, Commissioning & Maintenance Handbook If ONLY any of the following faults are recorded when in Outstation or Monitor mode, Whilst OTUs respond with out faults to test set in Instation mode: BIC, CMS If Instation not transmitting sufficient bytes and OTU is last on the line RCRC If OTU replying with too many of to few control bytes POSSIBLE FAULT: Due to Control data errors e.g. incorrect numbers for OTU or incorrect numbers of OTUs on the line.
TC12 Installation, Commissioning & Maintenance Handbook CMSL Control not starting on time more then one second between control messages. BIC, CMS If Instation not transmitting sufficient bytes for this OTU if last OTU on line. CCRC If Instation transmitting too many or too few control bytes for this OTU. POSSIBLE FAULT: Minor incorrect timing / configuration for this OTU at Instation.
TC12 Installation, Commissioning & Maintenance Handbook By checking each OTU in turn and checking the errors it should be possible to determine where the fault lies or what the next step to take is. If errors are detected in monitor mode it is best to obtain authority to take all OTUs on that line off line and re test in Outstation mode. If the fault appears to lie with the OTUs in the field or the line, then testing at the OTU using the test will determine if it is the line, the OTU or other OTUs.
TC12 Installation, Commissioning & Maintenance Handbook 4.6 USING THE TEST SET AS A MONITOR FOR THE INSTATION PC Exit from any software currently being used on the test set PC. At the C: prompt, type TERM . This will activate the batch file TERM.BAT (which should be in the top level directory C:\ when copied from the ITS software master disk), which in turn will activate the STC terminal emulator CTERM.
TC12 Installation, Commissioning & Maintenance Handbook 4.7 USING THE TEST SET AS HANDSET Exit from any software currently being used on the test set PC. At the C: prompt, type TERM . This will activate the batch file LITEMNS.BAT (which should be in the top level directory C:\ after installation of PITS software), which in turn will activate the STC handset software.
TC12 Installation, Commissioning & Maintenance Handbook 4.8 MAINTENANCE OF INSTATION TEST SET 4.8.1 Recommended Spares Switching the Test Set off, using the rocker switch on the front panel, does NOT guarantee isolation from the mains. The mains plug must only be fitted with a 3 A or 5 A fuse.
TC12 Installation, Commissioning & Maintenance Handbook 5 TC12 OUTSTATION TEST SET 5.1 SPECIFICATION 5.1.1 Mains voltage and frequency ranges The Outstation test set will work over: 100/120/220/230/240 VAC all +10%,-13% Different internal connections are necessary for different voltage ranges. The outstation test set will work over the frequency range 47 Hz - 63 Hz. 5.1.2 Mains Current Outstation test set 100 mA at 240 V 5.1.
TC12 Installation, Commissioning & Maintenance Handbook 5.2 USING THE OUTSTATION TEST SET The Outstation Test Set (part number 667/1/22657/000) is supplied with six cable forms (part number 667/1/22658/000 to /005). The Outstation Test Set is designed to simulate an OTU (OTU Mode) or traffic control equipment (Controller Mode) and is connected into the system via special test cables. Note: THE SPECIAL TEST CABLES MUST ALWAYS BE USED WHEN CONNECTING THE OTS TO EITHER AN OTU OR TRAFFIC CONTROL EQUIPMENT 5.
TC12 Installation, Commissioning & Maintenance Handbook A CONNECTION FAULT indicator is lit if the test cable is incorrectly connected. The mains lead is connected directly to the OTS.
TC12 Installation, Commissioning & Maintenance Handbook Figure 33 - Outstation Test Set Connections OTU Input/Output Cable 667/1/22693/000 40 Way Plug OTU CONTROLLER 34 Way Plug a) Normal Equipment connection OTU to Controller Test Set Cable 667/1/22658/000 OR 667/1/22658/001 OTU 25 Way Socket OUTSTATION TEST SET 34 Way Plug 37 Way Socket 40 Way Plug b) OTU to Outstation Test Set connection - Controller Mode Test Set Cables 667/1/22658/002 & 667/1/22658/003 OTU Input/Output Cable 667/1/22693/000
TC12 Installation, Commissioning & Maintenance Handbook Switch operation: Word Selector If this switch is set to 1 word, only the 37 way plug (OTU mode) or 37 way socket (controller mode) can be attached. Only the first eight data switches then operate. Generally this switch should be left in the 2 word position. Both the 37 way and 25 way plug (OTU mode) or 37 and 25 way socket (controller mode) must be connected up. All 16 data switches then function.
TC12 Installation, Commissioning & Maintenance Handbook The above conditions are automatically checked when the appropriate plug/socket is inserted because the connectors incorporate links that activate the inputs to the Connection Check Logic. If any condition proves faulty, operation of the rest of the circuit is inhibited and the Connection Fault LED is lit. 5.2.1.
TC12 Installation, Commissioning & Maintenance Handbook 5.3 OPERATION 5.3.1 General Set the MODE and TRANSMISSION CONFIRM (TC) switches to the OFF positions. Connect the mains supply. Procedure is now according to the operating mode required. 5.3.2 OTU Mode (Simulating an Outstation) 5.3.2.1 Operation Note. Using the OTS in OTU mode will affect transmission since the OTU input/output cable is detached from the OTU. This forces all OTU inputs to the "1" state and this will be transmitted to the Instation.
TC12 Installation, Commissioning & Maintenance Handbook Return MODE and TC switches to the OFF position. Switching the TC switch OFF at any time simulates the word fail condition on the reed interface of the OTU, thus causing the traffic controller to revert to local operation independent of the test unit. Transmission Confirm does NOT indicate that the controller is under Computer control.
TC12 Installation, Commissioning & Maintenance Handbook Set the Mode switch to the CONTROLLER position. (If the connection fault is lit return the switch to OFF and check that the plugs are fully inserted before proceeding). Set up the required patterns for words 0 and 1 output to the desired 16 inputs of the OTU. The OTU responds to the data and transmits reply bits back to the Instation. The LED indicators on the OTS display the control data from the Instation.
TC12 Installation, Commissioning & Maintenance Handbook 5.4 MAINTENANCE A 1 A mains input fuse (part number 518/4/98042/001) is located within the front panel fuseholder. A 2 A fuse (part number 518/4/98009/004) within the chassis unit provides protection against certain types of traffic control equipment fault, e.g. a supply rail wrongly connected to the common signal return wire.
TC12 Installation, Commissioning & Maintenance Handbook 6 6.1 INTEGRAL OUTSTATION TRANSMISSION UNIT (OTU/LMU) GENERAL OVERVIEW This section describes the Integral OTU/LMU. This is an additional PCB that can be used in the TC12 System. It can be fitted in T400 or ST800 traffic controllers or the ST700 pelican controller and used to communicate with a central office Instation Transmission Unit.
TC12 Installation, Commissioning & Maintenance Handbook 6.2 SPECIFICATION 6.2.1 Mains voltage and frequency ranges The Integral OTU PCB is powered from the Controller power supply unit. The working voltage and frequency ranges are equal to those specified for the Controller. 6.2.2 Mains Current Integral OTU 20 mA at 240 V 6.2.3 Temperature and Humidity Requirements The OTU will work over the temperature range -15 to 75 °C. 96% at 40 °C. non condensing Humidity 6.2.
TC12 Installation, Commissioning & Maintenance Handbook 6.3 INSTALLATION 6.3.1 General Installation and commissioning of the Outstation is carried out in the following order: - Configure the Outstation PCB via PCB switches - Install PCB in Controller and Connect the cabling - Configure the Outstation using the Handset terminal The parameters that need configuring include: Output power level. Warning - for use in the UK the power level must not be set to greater than -13 dBm.
TC12 Installation, Commissioning & Maintenance Handbook The cover must ALWAYS be fitted before any cables are installed, and should NEVER be removed whilst the telephone cable (from socket SK1 on the PCB) is connected to the telephone network. Figure 34 - Integral OTU PCB Layout and Switch Settings Status LEDs LP2 - Carrier Detect PLA Processor LP3 - Transmit confirm LP4 - Watchdog Fail Firmware SK2 - Reply Line Jack Sockets Closed ‘1’ when pushed up. Open ‘0’ when pushed down.
TC12 Installation, Commissioning & Maintenance Handbook 2. S2 - Lithium Battery On/Off Switch Set the Lithium Battery Switch (S2) to ON (see Figure 34). 3. S3 - Line Level Switch Ensure that the Line Level switch (S3) is set to the required line levels. These are stated on the installation information sheet for the Integral OTU. Table 8 shows switch settings corresponding to the different levels. Switch S3 is a 6-way DIL switch.
TC12 Installation, Commissioning & Maintenance Handbook Table 8 - Integral OTU Line Level Switch (S3) ← SW 1 Switch SW 2 Number SW 3 SW 5 → SW 6 SW 4 1 0 0 0 -3 dBm 1 0 0 1 -6 dBm 0 1 0 0 -9 dBm 0 1 0 1 -10 dBm 0 0 1 0 -13 dBm 0 0 0 0 -16 dBm Receive Threshold -42 dBm 0 0 0 1 0 0 -39 dBm 0 1 -33 dBm 1 0 Output Power 0 dBm 0 = Switch Open 1 = Switch Closed Warning - For use in the UK the power level must not be set to greater than -13 dBm.
TC12 Installation, Commissioning & Maintenance Handbook 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 ADDRESS BIT 5 ADDRESS BIT 6 ADDRESS BIT 7 0V ADDRESS BIT 8 ADDRESS BIT 9 ADDRESS BIT 10 ADDRESS BIT 11 ADDRESS BIT 12 ADDRESS BIT 13 0V DATA BIT 0 DATA BIT 1 DATA BIT 2 DATA BIT 3 DATA BIT 4 DATA BIT 5 DATA BIT 6 DATA BIT 7 0V MEMORY WRITE 0V MEMORY READ 0V DATA TX / RX DATA ENABLE +5 V WATCHDOG FAIL POWER FAIL RESET OUT +5 V ZERO CROSS-OVER EXPANSION I/
TC12 Installation, Commissioning & Maintenance Handbook network termination unit). In order to prevent the cable being disconnected from the PCB by accident the PCB cover fits around the end of the plug on the cable in order to retain it. 6.3.3.3 Connection of SCOOT Detector Inputs to an Integral TC12 OTU On an integral TC12 OTU the SCOOT detector inputs to the controller should be connected to the normally open contacts on the detector backplane (make for vehicle presence).
TC12 Installation, Commissioning & Maintenance Handbook Figure 35 - LMU Input Connector PLB PIN 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 60 Way Connector to LMU Inputs SIG NAME BERG PLB SIG NAME PIN PIN LMU input 1 + 3* 25 LMU input 13 + LMU input 1 4 26 LMU input 13 LMU input 2 + 5 27 LMU input 14 + LMU input 2 6 28 LMU input 14 LMU input 3 + 7 29 LMU input 15 + LMU input 3 8 30 LMU input 15 LMU input 4 + 9 31 LMU input 16 + LMU input 4 10 32 LMU input 16 LMU input 5 + 11 33 LMU inpu
TC12 Installation, Commissioning & Maintenance Handbook Current Transformers Each controller phase or illuminated indicator that is to be monitored requires one current sensor as detailed below. The table also indicates which lamp feeds are passed through the current sense transformer for each type.
TC12 Installation, Commissioning & Maintenance Handbook Notes: These limits apply to 240 V RMS supply voltage and 50 W lamp loads (unless stated). Where the supply is lower or the lamp loads are higher the limits are reduced accordingly. For example the figures given in curly brackets {} are the maximum loads when a 50-0-50 V RMS mains supply is used. The limits are only reduced if the actual voltage being monitored is at the lower level, i.e.
TC12 Installation, Commissioning & Maintenance Handbook Voltage Monitoring Transformer A Voltage monitoring transformer (part number 667/7/25172/000) is used per Outstation when equipped with LMU facilities. The red and black wires connect to the lamp supply mains live and neutral being monitored (Red to Live and Black to Neutral). The orange and white output wires connect to PL1. Referring to Figure 35, the orange wire connects to pin 47 (LMU Input 24+ on PLB, i.e.
TC12 Installation, Commissioning & Maintenance Handbook 6.4 COMMISSIONING 6.4.1 Commissioning Procedure after Power Up 1. Initialisation The operator can initialise just the Integral OTU, just the Controller, or both together by using the appropriate handset command value: Initialising OTU only: Enter CNN=117, LRN=53 and TKE=199. The Integral OTU is initialised as soon as the commands have been entered. There is no need to power off and then back on.
TC12 Installation, Commissioning & Maintenance Handbook Check that the status LEDs illuminate correctly, see section 6.5.1. 6.4.2 Configuration Using the Handset With the Controller and OTU powered up, connect a handset terminal to the Controller Main Processor handset socket. The Integral OTU is configured using a subset of the commands used to configure the Freestanding OTU. Commands that apply (see below) are entered in exactly the same way as for the Freestanding OTU as described in section 3.3.3.
TC12 Installation, Commissioning & Maintenance Handbook Section 3.3.3 Subsection No 42 43 44 46 47 48 Command KRD KRE KRG KLV GCD GDI 3 Section 3.3.3 Subsection No. 92 93 94 Command GMC GBE GMO The PC in the TC12 Instation Test Set can be used as a handset terminal Refer to section 4.6. The PC keyboard makes entry of commands easier than with a conventional handset terminal.
TC12 Installation, Commissioning & Maintenance Handbook Functions available: 0 1 .. 23 Control Bit 0 (Bit 0 of Word 0) Control Bit 1 (Bit 1 of Word 0) ..........................
TC12 Installation, Commissioning & Maintenance Handbook The power is turned off and back on, or The OTU is re-initialised using the three reset commands. Bit 2: The Integral OTU/LMU has appeared to have failed or is not connected and integral RLM is configured. This will switch the lamps off and not allow them back on even if the OTU/LMU has come back on line. Bit 3: The controller has detected an inconsistency in the lamp fault indications generated by the OTU.
TC12 Installation, Commissioning & Maintenance Handbook ENG 200 0 to 31 OTUHFLG - Integral OTUs historic fault flags The Integral OTUs Historic Fault Log Flags - see OTU documentation. Normal examination of the OTU's fault logs should be made using the OTU commands 'GLF' and 'GLD' rather than these engineering commands. Note: This command can still be entered even if no Integral OTU is fitted or one is connected but has failed but will obviously not return the correct values.
TC12 Installation, Commissioning & Maintenance Handbook ENG 203 - 210 0 to 255 U OTUSRx - Integral OTUs shared RAM sections 0-7 U These eight codes can be used to display any byte within the shared RAM interface between the Integral OTU and the controller. For ease of use, it is recommended that the 'ENO' command is used rather than this one. For example, to access byte number 234 (hex): 2XX requires OTUSR2, i.e. ENG 205 34 hex is 52 in decimal, therefore the command will be: ENG 205 52 6.4.
TC12 Installation, Commissioning & Maintenance Handbook KPT 2 = 1 :current sensor 2 monitors a vehicle phase Allocate phase identity to each current sensor: KAD 1 = 0 :sensor 1 is phase A KAD 2 = 1 :sensor 2 id phase B Select normal lamp monitoring (not RLM) on vehicle phases: KRE 1 = 0 :sensor 1 KRE 2 = 0 :sensor 2 Reset the lamp monitor and enable lamp monitoring: KLR = 1 :reset lamp characteristics KLE = 1 :enable lamp monitoring Example 2 - 4 phase controller with signs U Description: Four phase inte
TC12 Installation, Commissioning & Maintenance Handbook KAD 8 = 20 :sensor 8 is phase E, amber drive Select normal lamp monitoring (not RLM) on vehicle phases: Note: Sensors 3 to 9 do not monitor vehicle phases and so they are configured for normal lamp monitoring by default - their configuration does not need to be changed.
TC12 Installation, Commissioning & Maintenance Handbook In this example, the pelican is monitored with a single current sensor (see example 5 for separate wait and pedestrian and vehicle monitoring using three current sensors) The configuration commands are detailed below.
TC12 Installation, Commissioning & Maintenance Handbook - Reset the lamp monitor and enable lamp monitoring (KLR and KLE) - With the junction signals on, check that the voltage and current readings are as expected on each input (KAC) - Check that all lamps are working, including wait indicators Allow the LMU to learn the lamps and check that learning is complete (KLS) Note: If dimming is fitted to the controller, force the signals to dim and allow the LMU to learn the lamps in the dim state.
TC12 Installation, Commissioning & Maintenance Handbook The learning of the second state is automatic once the controller has been switched to that state and requires no manual intervention. This means that it is not strictly necessary to manually switch the controller into the other state as the second learning sequence will be invoked automatically at the first dim/bright change, after the initial learning sequence was invoked.
TC12 Installation, Commissioning & Maintenance Handbook 6.5 MAINTENANCE 6.5.1 Status LEDs LEDs are provided on the front edge of the board to provide basic status information. The position of these LEDs and their functions are shown in Figure 34. A System fail on the Controller Main Processor PCB may indicate a fault on the Integral OTU PCB. If the system fail LED is on, information about the type of fault that has occurred can be accessed using a handset terminal (see section 6.4.2 on handset commands).
TC12 Installation, Commissioning & Maintenance Handbook (4) S4 - 600 Ohm/High Impedance Switch If the switch is set to high impedance when it should be set to 600 Ohms, the transmit signal for all OTUs on the line and the receive signal for the particular OTU will be up to 3dB higher than if the switch was set correctly. The characteristics of the line may also be affected.
TC12 Installation, Commissioning & Maintenance Handbook Appendix A – TC12 OTU Serial Environmental Monitor Sensor Interface Handbook U The following pages comprise the full handbook 667/HB/26628/000.