Regulation of the PV plant according to BDEW Guideline and the current amendment of the Renewable Energy Act (EEG) by means of
SINVERT PVS ControlBox 300 displayed with WinCC
The "Generating Plants in the Medium-Voltage Grid" BDEW
guideline stipulates this requirement for all systems feeding
in at the medium-voltage level. Its primary benefit is that it
enables grid operators to limit the output of the plant by
remote means in accordance with § 6 of the Renewable Energy
Act 2009.
The ControlBox 300 offers a wide range of open-loop and
closed-loop control functions, e.g.:
Specification of a fixed active power for all individual
SINVERT PVS inverters in the PV plant, e.g. setpoint
value = 2 MW (active power fixed value)
Specification of a fixed reactive power for all individual
SINVERT PVS inverters in the PV plant, e.g.
setpoint value = 100 kvar inductive (reactive power
fixed value)
Specification of a fixed power factor cos ϕ for all
individual SINVERT PVS inverters in the PV plant, e.g.
setpoint value = -0.95
Regulation of the active power for the individual
SINVERT PVS inverters in the PV plant as a function of
the active power actually measured at the grid infeed
point, to 0%, 30%, 60%, and 100% of the rated active
power of the PV plant. (Active power reduction in
accordance with § 6 of the Renewable Energy Act
Regulation according to Q(U) characteristic
Regulation according to Q(t) characteristic
Regulation according to P(f) characteristic
Ramps for system ramp-up and ramp-down, i.e. con-
tinuously approaching the setpoint
The SINVERT PVS ControlBox 300 offers the following
connection options:
SIMATIC components with digital inputs
SENTRON PAC3200 Power Monitoring Device for
measuring actual values at the grid feed-in point
–4 x RJ45 ports
2 x fiber-optic ports, for cable lengths up to 5 km