User's Manual

SINVERT PVS 600Series central inverters8
Technical data of the SINVERT PVS600 inverter (according to IEC)
1)
1)
Detailed technical information can be found at:
http://support.automation.siemens.com
2)
With the 1 000 V option, expandable to 1 000 V (see page 10 and 24).
Inverter type PVS600 PVS1200 PVS1800 PVS2400
Input DC
MPP voltage V 570 ... 750 570 ... 750 570 ... 750 570 ... 750
Maximum input voltage
2)
V 820 820 820 820
Minimum input voltage V 570 570 570 570
Rated input power kW 613 1 226 1 839 2 452
Maximum input current A 1 104 2 208 3 312 4 416
Number of DC inputs 3 6 9 12
Maximum current per DC input A 368 368 368 368
Surge arrester Type 2 Type 2 Type 2 Type 2
Output AC
Grid connection 50/60 Hz 370 V 3 AC 50/60 Hz 370 V 3 AC 50/60 Hz 370 V 3 AC 50/60 Hz 370 V 3 AC
Rated power kW 600 1 200 1 800 2 400
Maximum output current A 936 1 872 2 808 3 744
Line voltage V 314.5 ... 407 314.5 ... 407 314.5 ... 407 314.5 ... 407
Power factor, inductive 0.8 0.8 0.8 0.8
Power factor, capacitive 0.8 0.8 0.8 0.8
Efficiency
European efficiency factor % 98.4 98.6 98.6 98.6
CEC efficiency factor % 98.5 98.6 98.6 98.6
Maximum efficiency factor % 98.7 98.7 98.7 98.7
Further data
Number of subunits 1 2 3 4
Dimensions (H/W/D) per subunit mm 2 100 x 2 700 x 730 2 100 x 2 700 x 730 2 100 x 2 700 x 730 2 100 x 2 700 x 730
Weight per subunit kg 2 085 2 085 2 085 2 085
Ambient temperature
- during operation
- during storage and transport
°C
°C
0 ... +50
-25 ... +70
0 ... +50
-25 ... +70
0 ... +50
-25 ... +70
0 ... +50
-25 ... +70
Relative humidity % 0 ... 95 0 ... 95 0 ... 95 0 ... 95
Installation altitude
- maximum permissible
- at rated power
m
m
2 000
0 ... 1 000
2 000
0 ... 1 000
2 000
0 ... 1 000
2 000
0 ... 1 000
Data interface Ethernet Ethernet Ethernet Ethernet
Order number
Order number (grid frequency 50 Hz) 6AG3111-1AH00-
0AB0
6AG3111-1AH10-
0AB0
6AG3111-1AH20-
0AB0
6AG3111-1AH30-
0AB0
Order number (grid frequency 60 Hz) 6AG3111-2AH00-
0AB0
6AG3111-2AH10-
0AB0
6AG3111-2AH20-
0AB0
6AG3111-2AH30-
0AB0
SINVERT_PVS.book Seite 8 Donnerstag, 24. Mai 2012 3:01 15
© Siemens AG 2012