3600I MODEL 3600I TRIPLE IR (IR3) FLAME DETECTOR APPLICABILITY & EFFECTIVITY Effective for all Model 3600I Detectors manufactured after June 1, 2010. Instruction Manual Part Number T15014 Rev.
3600I ABOUT THIS GUIDE This guide describes the Model 3600I Triple IR (IR3) Flame Detector and its features and provides instructions on how to install, operate and maintain the detector. This guide includes the following chapters and appendixes: • Chapter 1, Introduction, provides a general overview of the product, principles of operation, and performance considerations.
600I ABBREVIATIONS AND ACRONYMS Abbreviation Meaning ATEX Atmosphere Explosives AWG American Wire Gauge BIT Built In Test EMC Electromagnetic Compatibility EOL End of Line FOV Field of View HART Highway Addressable Remote Transducer-communication protocol IAD Immune at Any Distance IECEx International Electrotechnical Commission Explosion IPA Isopropyl Alcohol IR Infrared JP4 Jet Fuel Latching Refers to relays remaining in the ON state even after the ON condition has been remove
3600I TABLE OF CONTENTS 1 INTRODUCTION.......................................................................................................................... 1 1.1 OVERVIEW ......................................................................................................................... 1 1.2 MODEL AND TYPES .......................................................................................................... 2 1.3 FEATURES AND BENEFITS .................................................
3600I 2.7 2.7.1 2.8 3 VERIFYING THE DETECTOR WIRING ....................................................................... 25 CONFIGURING YOUR DETECTOR................................................................................. 27 2.8.1 SENSITIVITY................................................................................................................. 28 2.8.2 ALARM DELAY ............................................................................................................. 28 2.
3600I APPENDICES ................................................................................................................................... 37 A B C SPECIFICATIONS ..................................................................................................................... 38 A.1 TECHNICAL SPECIFICATIONS ....................................................................................... 38 A.2 ELECTRICAL SPECIFICATIONS ..............................................................
3600I LIST OF FIGURES Figure 1: Horizontal Field of View ....................................................................................................... 8 Figure 2: Vertical Field of View ........................................................................................................... 9 Figure 3: Indication LED: Indication LED .......................................................................................... 11 Figure 4: Detector with Tilt Mount ...................................
3600I LIST OF TABLES Table 1: Wiring Options ....................................................................................................................... 3 Table 2: Sensitivity Range Levels ....................................................................................................... 7 Table 3: Fuel Sensitivity Ranges ......................................................................................................... 8 Table 4: Immunity to False Alarm Sources ......................
3600I 1 INTRODUCTION ➣ In this chapter… 1.1 Overview page 1 Model and Types page 2 Features and Benefits page 4 Principles of Operation page 4 Performance Considerations page 6 Internal Detector Tests page 14 OVERVIEW The Model 3600I is a flame detector that utilizes improved IR3 technology to provide state-of-the-art fire protection.
3600I 1.2 MODEL AND TYPES The 3600I is provided in various configurations depending on: • Wiring options • Temperature ranges • Type of cable entries • Housing type • Required approval The configuration detail is included in the product part number on the product label and takes the form: 3600I XXXXX, where XXXXX defines the model according to the above requirements.
3600I Table 1: Wiring Options Wiring Option Connections Provided 1 Power Manual BIT Fault Relay N.C. Alarm Relay N.O. 0-20mA Sink RS-485 - 2 Power Manual BIT Fault Relay N.C. Alarm Relay N.O., N.C. 0-20mA Source RS-485 HART 3 Power Manual BIT Fault Relay N.O. Alarm Relay N.O., N.C. 0-20mA Source RS-485 HART 4 Power Manual BIT Fault Relay N.C. Alarm Relay N.O. Auxiliary N.O. RS-485 - 5 Power Manual BIT Fault Relay N.O. Alarm Relay N.O. Auxiliary N.O.
3600I 1.3 1.4 FEATURES AND BENEFITS • Detection Range: Up to 215 ft. (65m) for a 1 ft2 (0.1m2) n-heptane fire. • Ultra High Immunity to False Alarms: See Table 4 on page 10. • Advanced Digital Processing of the Dynamic Characteristics of Fire: Flickering, threshold correlation and ratio. • Multi IR Channels: Between 3-5 microns • Field Programmable Sensitivity: Four ranges to avoid zone crossover. • Built In Test (BIT): Manual and Automatic (see Built-In-Test (BIT) on page 15).
3600I The IR3 technique utilizes few infrared sensors, each sensitive to its own wavelength range. The first sensor is sensitive to wavelengths within the emission peak of hot CO2. The other two sensors are sensitive to wavelengths above and below this peak. The fourth IR sensor is sensitive to a different band within the emission peak of hot CO2. In the event of fire, the signal measured in the first sensor is significantly higher than those measured in the second two sensors.
3600I 1.4.5 PRODUCT CERTIFICATION The 3600I Flame Detectors have the following certifications: 1.4.5.1 • ATEX, IECEX, page 6 • SIL-2 Approved, page 6 ATEX, IECEX The 3600I Flame Detector is certified to: • ATEX Ex II 2 GD per SIRA 07ATEX 1149 and IECEx SIR. 07.0085. • EExde IIB + H2. • T5 Ambient Temp. -55°C to +75°C. • T4 Ambient Temp. -55°C to +85°C. This product is suitable to use in hazardous zones 1 and 2 with IIB + H2 gas group vapors present. 1.4.5.
3600I 1.5.1.1 STANDARD FIRE Defined as a 1ft2 / 0.1m2 n-heptane pan fire, with maximum wind speed of 6.5 ft/sec (2 m/sec). 1.5.1.2 SENSITIVITY RANGES The detector has four user-selectable sensitivity ranges. For each range there are two response levels. • WARNING (Pre-alarm) • ALARM The detection distance, for the WARNING level, is approximately 10% higher than the ALARM distance. Alarm response times for a standard fire at a specified range are shown Table 2.
3600I Table 3: Fuel Sensitivity Ranges Type Of Fuel 1.5.2 Percent of Max.
3600I • Vertical: +50° (down) , -45° (up) Figure 2: Vertical Field of View Page: 9
3600I 1.5.3 FALSE ALARMS PREVENTION To prevent false alarms, the detector will not alarm or react to the radiation sources specified in Table 4.
3600I Table 5: Welding Immunity Distance Sensitivity Setting 1.5.4 Detection Range Immunity Distance 1 50 ft (15m) >6 ft (2m) 2 100 ft (30m) >12 ft (4m) 3 150 ft (45m) >17 ft (6m) 4 215 ft (65m) >25 ft (7.5m) VISUAL INDICATORS One 3-color LED indicator is located inside the detector window, as shown in Figure 3. The detector statuses are listed in Table 6.
3600I 1.5.5 OUTPUT SIGNALS Outputs are available according to the default configuration or the wiring options selected for the 3600I IR3 Detector. Determine the outputs for your model according to Table 7.
3600I 1.5.6 DETECTOR STATUS The possible detector function statuses are listed in Table 8. A more detailed fault analysis can be seen via HART or RS485. Table 8: Detector Status Status Normal BIT Warning Alarm Latched Alarm (Optional) BIT Fault Fault Description Normal operation. Built-In-Test being performed. Fire detected - changed to Warning (pre-alarm state). Fire detected - changed to Fire Alarm state.
3600I 1.5.6.1 OPTIONAL LATCHING Alarms are set as non-latching by default. However, the detector includes a latched alarm output capability, which operates according to the programmed function. If selected, upon detection of a fire, the detection signal is latched until a manual reset is performed (disconnecting the power supply or performing a manual BIT (see Manual BIT on page 16).
3600I Response to Fault Indication If a failure is found, the detector indicates by: • Fault relay: • Opens in wiring option 1, 2, and 4 • Closes in wiring option 3 and 5 • 0-20mA: indicates Fault (0mA or 2mA) in wiring option 1, 2, 3 • LED – Yellow flashes (4 Hz) Correcting the Fault The fault indications remain until the detector’s power is removed. The fault indications return if the fault is still found when power is restored. 1.6.
3600I 1.6.2.2 AUTOMATIC BIT The detector automatically performs a BIT every 15 minutes. A successful BIT sequence does not activate any indicator. The results of a successful and unsuccessful BIT are listed in Table 10 and Table 11.
3600I Table 12: Results of a Successful Manual BIT Output Result FAULT relay • • Wiring options 1, 2, and 4: remains CLOSED (Normal) Wiring options 3 and 5: remains OPEN (Normal) ALARM relay Activated for 3 sec (only when the function Alarm BIT is set to YES) AUXILIARY relay For wiring options 4 and 5: is activated for 3 sec (only when the function Auxiliary BIT is set to YES) 0-20mA output Wiring option 1, 2, 3: • Initiates 20 mA only when the function Alarm BIT is set to YES • Initiates 16 mA wh
3600I 2 INSTALLING THE DETECTOR ➣ In this chapter… General Guidelines page 18 Unpacking the Product page 19 Required Tools page 19 Certification Instructions page 20 Installation Cables page 21 Installing the Tilt Mount (part no. 3600 page 22 Connecting the Detector page 24 Configuring your Detector page 27 This chapter provides basic guidelines for installing the detector. It does not attempt to cover all of the standard practices and codes of installation.
3600I • • The presence of high intensity flickering IR sources may affect sensitivity. Aiming the Detector: • The detector should be aimed toward the center of the detection zone and have a completely unobstructed view of the protected area. • Whenever possible, the detector face should be tilted down at a 45º angle to maximize coverage and prevent accumulation of dust and dirt.
3600I 2.4 CERTIFICATION INSTRUCTIONS Warning: Do not open the detector, even when isolated, when flammable atmosphere present. Use the following certification instructions: • The cable entry point may exceed 167°F (75°C). Suitable precautions should be taken when selecting the cable. • The equipment may be used with flammable gases and vapors with apparatus groups IIA and IIB + H2: • T5 in the ambient temperature range: –67°F (–55°C) to +167°F (+75°C).
3600I 2.5 INSTALLATION CABLES Follow the following guideline for the cable installation: 2.5.1 • All cables to the detector must be well shielded in order to comply with EMC requirement (see Technical Specifications on page 52). • Ground the detector to the nearest ground point (not more than 3m from the detector location). • Install the detector with the cable entries placed downwards.
3600I 2.6 INSTALLING THE TILT MOUNT (PART NO. 3600-001) The Tilt Mount enables the detector to be rotated up to 60º in all directions. Figure 4 shows the Detector mounted on the Tilt Mount. Figure 4: Detector with Tilt Mount 2.6.1 TILT MOUNT SPECIFICATIONS Table 15: USA Version Item Qty Type Location Tilt Mount 1 3600-001 Screw 4 ¼" 20 UNC x ¾" Detector – Holding plate Spring Washer 4 No.
3600I 2.6.2 TILT MOUNT ASSEMBLY Figure 5 shows the Tilt Mount Assembly. Tilt Holding Plate Tilt Mount Horizontal Locking Screw Vertical Locking Screw Detector Holding Plate Figure 5: Tilt Mount Assembly Figure 6 shows the Tilt Mount Assembly with dimension in both millimeters and inches.
3600I ➣ To install the Tilt Mount and Detector: 1 Place the tilt mount in its designated location and secure it with four (4) fasteners through four (4) holes 7 mm in diameter. Use the 4 screws and spring washers according to the kit (see Table 15 and Table 16). Note: Removing the detector for maintenance purpose does not require the Tilt Mount to be removed). 2.7 2 Unpack the detector. 3 Place the detector with its conduit/cable entries pointing downwards on the holding plate of the tilt mount.
3600I Terminal Chamber Terminals Internal Earth Terminal Earth Terminal Detector Holding Screw Conduit / Cable Inlet Figure 7: Detector with Cover Removed 2.7.1 5 Connect the wires to the required terminals on the Terminal Board according to the wiring diagram (Figure 7) and Table 17. 6 Connect the grounding (earth) wire to the ground (earth) screw outside the detector (Earth Terminal). The detector must be well grounded to earth ground. 7 Verify the wiring. Improper wiring may damage the detector.
3600I Table 17: Model 3600I Wiring Options Wire Terminal No. 1 2 3 4 5 6 7 8 Option 1 Default +24 VDC 0 VDC Manual BIT Option 2 Option 3 Option 4 Option 5 +24 VDC 0 VDC Manual BIT +24 VDC 0 VDC Manual BIT +24 VDC 0 VDC Manual BIT +24 VDC 0 VDC Manual BIT Fault Relay N.C. Fault Relay N.C. Fault Relay N.O. Fault Relay N.C. Fault Relay N.O. Alarm Relay N.O. Alarm Relay C Alarm Relay N.O. Alarm Relay C Alarm Relay N.C. 0-20mA Out* RS-485+ (1) RS-485(1) RS-485 GND Alarm Relay N.O.
3600I 2.8 CONFIGURING YOUR DETECTOR You can reprogram the function setup using the RS-485 connection or using the Hart Protocol as follows: • Sierra Monitor Host Software: The Sierra Monitor Host Software is for use on a PC or laptop. Refer to Manual TM777050 for programming instructions. The Host software enables you to change the functions. • Handheld Unit: Refer to Manual 777060 for programming instructions when using the Handheld Unit. The connection to the Handheld is fast and intrinsically safe.
00I 2.8.1 SENSITIVITY The detector offers four (4) sensitivity settings. The settings refer to an n-heptane or gasoline fire of 1ft² (0.1m²), from low sensitivity of 50 ft (15m) to 215 ft (65m). For other types of fuel sensitivity, refer to Table 3. Table 18: Sensitivity Settings Sensitivity Setting 15 30 (default) 45 60 2.8.
3600I 2.8.4 FUNCTION SET-UP You can select the desired functions as detailed in the following table. Table 19: Functions Function Setting Alarm Latch • • Auxiliary Relay** • • Automatic BIT • • Alarm BIT • • Auxiliary BIT** • • EOL** • • Yes: Enable Alarm latching. No: Disable Alarm latching (default). Yes: Activate Auxiliary Relay at Warning level. No: Activate Auxiliary Relay at Alarm level (default). Yes: Perform Automatic & Manual Bit (default). No: Perform Manual Bit only.
3600I 3 OPERATING THE DETECTOR ➣ In this chapter… Powering Up page 30 Safety Precautions page 31 Testing Procedures page 32 This chapter describes how to power up and test the detector. It also includes some very important safety checks that you should make before operating the detector. 3.1 POWERING UP This section describes how to power up the detector.
3600I 3.2 SAFETY PRECAUTIONS After powering-up, the detector requires almost no attention in order to function properly, but the following should be noted: 3.2.1 • Follow the instructions in this guide and refer to the drawings and specifications. • Do not expose the detector to radiation of any kind unless required for testing purposes. • Do not open the detector housing, while power is applied. • Do not open the electronic compartment.
3600I 3.3 TESTING PROCEDURES This section describes the proof testing procedure for proper operation of the detector. The detector can be tested using the Manual Built-in-Test or the Sierra Monitor IR3 Fire Simulator - 20/20-310. The detector performs internal test continuously and automatic BIT test every 15 minutes for more details refer to Built-In-Test (BIT) on page 15. This section includes the following topics: 3.3.
3600I Table 21: Results of Successful Fire Simulator Test Component Action Notes 0-20mA Turn to 20mA For a few seconds and then return to 4mA Alarm Relay Activated for a few seconds and then returns to Normal Auxiliary Relay Activated for a few seconds and then returns to Normal Fault Relay Remains active during the test LED Red, steady The detector is now ready for operation.
3600I 4 MAINTENANCE AND TROUBLESHOOTING ➣ In this chapter… Maintenance page 34 Troubleshooting page 36 This chapter deals with preventive maintenance, describes possible faults in detector operation and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty. Whenever a unit requires service, please contact Sierra Monitor or its authorized distributor for assistance. 4.
3600I 4.1.2 PERIODIC PROCEDURES In addition to preventive cleaning and maintenance, the detector should be functionally tested every six months or as dictated by local codes and regulations. These tests should also be carried out if the detector has been opened for any reason. 4.1.2.1 POWER-UP PROCEDURE Perform Power-Up procedure every time power is restored to the system. Follow the instructions described in Powering Up on page 30. 4.1.2.
3600I 4.2 TROUBLESHOOTING This section is intended to be a guide to correct problems which may happen during normal operation. Table 22: Troubleshooting Table Problem Cause Corrective Action LEDs Off Fault Relay at N.O 020mA at 0mA No power at the unit • • • • Yellow LED flashes at 4 Hz Fault Relay at N.O 020mA at 0mA Fault Detector • Low Voltage • Faulty Detector • Yellow LED flashes at 4 Hz Fault Relay at N.
3600I APPENDICES Page: 37
3600I A SPECIFICATIONS ➣ In this appendix… A.
3600I A.2 ELECTRICAL SPECIFICATIONS Table 23: Electrical Specifications Operating Voltage Status All Outputs Without 020mA Power Consumption (Max. 24VDC) Normal 1.61W 1.56W Normal when Heater On 2.28W 2.16W Alarm 2.64W 2.28W Alarm when Heater On 3.24W 2.88W Normal 70mA 65mA Normal when Heater On 95mA 90mA Alarm 110mA 95mA Alarm when Heater On 135mA 120mA Normal 1.95W 1.85W Normal when Heater On 2.56W 2.45W Alarm 3.04W 2.56W Alarm when Heater On 3.68W 3.
3600I • • Electrical Outputs • Option 4: Power, RS-485, Fault Relay (N.C), Auxiliary Relay (N.O), Alarm Relay, (N.O). Option 5: Power, RS-485, Fault Relay (N.O), Auxiliary Relay (N.O), Alarm Relay, (N.O). Dry Contact Relays Table 24: Contact Ratings • Relay Name Type Normal Position Maximum Ratings Alarm DPST N.O., N.C. 2A at 30 VDC or 0.5A at 250 VAC Auxiliary SPST N.O. 5A at 30 VDC or 250 VAC Fault * SPST N.C. or N.
3600I • Headed Optics A.4 Communication Network: The detector is equipped with an RS-485 communication link that can be used in installations with computerized controllers. The communications protocol is Modbus compatible. • This protocol is a standard and widely used. • It enables continuous communication between a standard Modbus controller (Master device) and a serial Network of up to 247 detectors. The front window can be heated to improve performance in icing, condensation and snow conditions.
3600I A.7 ENVIRONMENTAL SPECIFICATIONS The 3600I is designed to withstand harsh environmental conditions. • Designed to meet MIL-STD-810C, method 501.1 High Temperature procedure II • Operating temperature: +167°F (+75 °C) • Storage temperature: +185 °F (+85 °C) • Designed to meet MIL-STD-810C, method 502.1, Low Temperature procedure I • Operating temperature: -57°F (-50°C) • Storage temperature: -65°F (-55°C) • Designed to meet MIL-STD-810C, method 507.
3600I B WIRING INSTRUCTIONS ➣ In this appendix… B.1 General Instructions for Electrical Wiring page 43 Typical Wiring Configurations page 44 GENERAL INSTRUCTIONS FOR ELECTRICAL WIRING Follow the instructions detailed in this section for determining the correct wire gauge to be used for the installation. 1 Use Table 27 to determine the required wire gauge /size for general wiring, such as relay wiring.
3600I B.2 TYPICAL WIRING CONFIGURATIONS This section describes examples of typical wiring configurations.
3600I Table 29: Wiring Connections Wiring Option Detector Model Terminals 5 8 9 1 3600I-1XXXX Fault Relay (N.C) 0-20mA (Sink) 0-20mA (Sink) 2 3600I-2XXXX Fault Relay (N.C) Alarm Relay (N.C) 0-20mA Duct Source 3 3600I-3XXXX Fault Relay (N.O) Alarm Relay (N.C) 0-20mA Duct Source 4 3600I-4XXXX Fault Relay (N.C) Auxiliary Relay (N.O) Auxiliary Relay (C) 5 3600I-5XXXX Fault Relay (N.O) Auxiliary Relay (N.
3600I Figure 10: 0-20mA Wiring Option 1 (Sink 4-Wire) - Default Figure 11: 0-2mA Wiring Option 1 (Converted to Source 3-Wire) Page: 46
3600I Figure 12: 0-20mA Wiring Option 1 (Unisolated Sink 3-Wire) Figure 13: 0-20mA Wiring Option 2 and 3 (Source 3-Wire available with the HART protocol) Note: There are no 0-20mA outputs in wiring options 4 and 5.
3600I C RS-485 COMMUNICATION NETWORK ➣ In this appendix… RS-485 Overview C.1 page 48 RS-485 OVERVIEW By using the RS-485 network capability of the IR3 detector and additional software, it is possible to connect up to 32 detectors in an addressable system with four (4) wires only (2 for power and 2 for communication). Using repeaters, the number of detectors can be much larger (32 detectors for each repeater) up to 247 on the same four (4) wires.
3600I D ACCESSORIES ➣ In this appendix… Long Range IR3 Fire Simulator page 49 Tilt Mount - P/N 3600-001 page 52 Weather Protection - P/N 777163 page 53 Laser Detection Coverage Pointer - P/N 777166 page 54 Air Shield - P/N 777161 page 54 This appendix describes the accessories that can help you maximize fire detection with the IR3 flame detector: D.1 LONG RANGE IR3 FIRE SIMULATOR The IR3 Long Range Fire Simulator 20/20-310 is designed specifically for use with IR3 flame detectors.
3600I D.1.2 • Fire Simulator with integral batteries • Battery charger • Optional Beam Collimator • Storage case OPERATING INSTRUCTIONS Warning: Do not open the Fire Simulator to charge the batteries or for any other reason in a hazardous area. Caution: The following test simulates a real fire condition and may activate the extinguishing system or other alarms. If this is not desired, disconnect/inhibit them before the test and reconnect after the simulation.
3600I D.1.3 RANGE Table 30: Sensitivity Ranges Sensitivity Detection Range (ft / m) Standard Test Range (ft / m) Extended Test Range (ft / m) 1 (Low) 50 / 15 3.8 / 1.2 7 / 2.2 2 100 / 30 7 /2.2 14.5 / 4.5 3 150 / 45 10 / 3.2 22 / 7 4 (High) 215 / 65 14.5 / 4.5 29 / 9 Notes: • The minimum distance from the detector is 20 inches (50 cm). • The optional beam collimator is fitted for Extended Range. At extreme temperatures, there is a 15% maximum reduction in the range.
3600I D.1.5 TECHNICAL SPECIFICATIONS Mechanical • • • • • • Electrical • • • • Environment • • • Physical • • D.2 Explosion Proof Enclosure: NFPA (designed to meet) Class I, Division 1 & 2 Groups B, C and D Class II, Division 1 & 2 Groups E, F and G ATEX EX II2G NEMKO 02ATEX255 EExd IIB T5 50°C per En 50-014 & EN50-018 Power: 8 VDC Max. 6 x Rechargeable 1.2 VDC NiCd Batteries Current: 2.5A Avg.
3600I D.3 WEATHER PROTECTION - P/N 777163 The weather protector protects the detector from different weather conditions, such as snow and rain.
3600I D.4 LASER DETECTION COVERAGE POINTER - P/N 777166 The Laser Detection Coverage Pointer evaluates detector coverage on-site. The device is an add-on accessory that enables designers and installers to optimize detector location and assess the actual coverage of installed detectors. The device is universal and can be used with all 3600 Optical Flame Detectors. Figure 19: Laser Detection Coverage Pointer D.
3600I E SIL-2 FEATURES ➣ In this appendix… 3600I Flame Detector E.1 page 55 3600I FLAME DETECTOR This appendix details the special conditions to comply with the requirements of EN 61508 for SIL 2. The 3600I Flame Detector can only be used in low or high demand mode applications, see IEC 61508.4, Chapter 3.5.12. E.1.1 SAFETY RELEVANT PARAMETERS Perform the following functional checks of the detector: • • E.1.2 Alternative 1: Functional check of the detector every 180 days: • HFT: 0 • PFD: 3.
3600I 4 E.1.2.2 USING THE 0-20MA INTERFACE FOR ALERTING 1 2 E.1.2.3 The following parameters shall be set: • AUTOMATIC BIT test = on • Connected to 0-20mA Terminals The following allowed output current must be supervised with an accuracy of ± 5%: • Normal State = 4mA • Warning State = 16mA • Alarm State = 20mA 3 The output current must be supervised regarding the over-and under run of the 020mA. 4 The 0-20mA can be used as low and high demand mode.
3600I LIMITED WARRANTY SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.