User Manual

SIERRA FRYERS INSTALLATION
SIERRA OPERATORS MANUAL 170911 PAGE 10
INSTALLATION
Step 4: Check Clearances and Ventilation
Select a firm, level location for your fryer. Leave clearance, whenever possible, so that access from the rear
is possible to permit cleaning. If the unit is to be set on non-combustible flooring, such as a concrete slab, 3
inches minimum toe room must be provided to prevent restriction of the air opening in the bottom of the unit.
Due to the variety of problems that can be caused by outside weather conditions, venting by canopies or wall
fans is preferred over any type of direct venting. It is recommended that a canopy extend 6" past the
appliance and the bottom edge be located 6'6" from the floor. Filters should be installed at an angle of 45° or
more from the horizontal. This position prevents dripping of grease and facilitates collecting the run-off
grease in a drip pan, unusually installed with a filter. A strong exhaust fan tends to create a vacuum in the
room and may interfere with burner performance or may extinguish pilot flames. Fresh air openings
approximately equal to the fan area will relieve such a vacuum. In case of unsatisfactory performance on
any appliance, check the appliance with the exhaust fan in the “OFF” position. Do this only long enough to
check equipment performance, then turn hood back on and let it run to remove any exhaust that may have
accumulated during the test.
The exhaust fan should be installed at least 2 feet above the vent opening at the top of the fryer.
Make sure all ventilation meet local code requirement
This unit is not intended to be connected directly to an outside flue.