User Manual

IntelliKnight 5808 Installation Manual 151274-L8
7-9
7.3.1.5 Zone Accessory Options
This option applies to detectors that are used with Sounder bases or Relay bases.
Fire Cadence_ _/ CO Cadence_ _ (choose from Patterns 00 to 23).
Note: The B200S Sounder bases is intended to be used along with the CO cadence setting.
Local Zone (choose Y or N, for Yes or No).
7.3.2 Add Zone
To add a zone, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 2 to enter zone menu.
4. Press 2 to add a zone.
A zone will be added. The system will assign the next available zone number. Options for this zone can now
be programmed through the Zone Edit sub-menu. Up to 125 zones can be used.
7.3.3 Delete Zone
To delete a zone, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 2 to enter zone menu.
4. Press 3 to delete a zone.
5. Select a zone to delete.
A warning screen will display. If you want to proceed with deleting the zone, select Yes. To cancel, select
No.
7.3.4 View Zone Points
To view the points in a zone, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 2 to enter zone menu.
4. Press 4 to view zone points.
5. Enter the number of the zone you wish to view, then press
ENTER.
Figure 7-7 View Zone Points Screen
Zone Number
Module or
Device Address
Point Number
Total Number of
Points in the Zone