User Manual

Programming 151274-L8
7-14
5. Select output group number. See Figure 7-10.
Figure 7-10 Output Group Template Programming Screen
7.5 Point
You may need to change characteristics of individual input points (detectors and switches) even after using
JumpStart. This section explains how to change options for: type of point, latching/non-latching, silenceable/
non-silenceable, zone assignment (input points), detector accessory base options, group assignment (output
points), and point name.
7.5.1 Point Programming for the SLC
To program for points, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 4 to enter point menu.
4. Press the or arrows to select the desired module, then press
ENTER. Refer to Section 6.5 Quick Ref-
erence Table for available choices.
5. Enter the number of the point you wish to edit, then press
ENTER.
6. Select the type of device by pressing the or arrows. Refer to Table 7-5 under column heading “Type
Selection” for a list of choices.
7. Press ENTER.
Output
Group #
Yes = Include the selected
output group in this template
No = Do Not include output
group in this template
Select the
Cadence Pattern