User Manual

Programming 151274-L8
7-16
SLC Loop
CO SMOKE
DETECTOR
ALRM CO/
ALRM FIRE
SUP CO/
ALRM FIRE
ALRM CO/
SUP FIRE
SUP CO/SUP
FIRE
Latching Supervisory switches can be latching or non-
latching.
Non Latching
SWITCH
MAN_PULL Use this switch type for manual pull stations.
This input is always latched. The switch can
clear only when an alarm is reset.
WATER-
FLOW
Use this switch type for monitoring water flow
in a sprinkler system. Switch closure will
cause a sprinkler alarm. Water flow switches
can be programmed as latching or non-
latching.
You can program a delay of up to 90 seconds
to be used with a water flow switch. The delay
allows for normal, brief changes in sprinkler
system water pressure. The water flow alarm
will not activate unless the switch is active for
the programmed delay time.
Note: Waterflow delay of the FACP and
the waterflow device shall not exceed 90 sec-
onds.
If a delay is used, the system begins counting
down when the switch closes. If the switch
opens (restores) before the timer expires, a
water flow alarm is not generated. If the water
flow switch remains closed after the timer
expires, a water flow alarm will be generated.
SUPERVISY Non Latching Use this switch type for tamper monitoring of
sprinklers and other fire protection devices. If
a contact closes, a sprinkler supervisory
event will be generated. Supervisory switches
can be latching or non-latching.
FIREDRILL System-level, non latching switch. This switch
is an alternative way of causing a fire drill. It
has the same operation as the fire drill option
available from the annunciator. When the
switch is activated, a fire drill begins; when
the switch is de-activated, a fire drill ends.
SILENCE System-level switch provides an alternate
way to silence the system; same effect as
pressing the Silence key.
RESET System-level switch provides an alternate
way to reset the system; same effect as
pressing the Reset key.
Table 7-5 Point Programming
Module Type
Type
Selection
Function
Latching
Option
Comments