User Manual

IntelliKnight 5808 Installation Manual 151274-L8
7-21
5. Select the characters for the point name by pressing the or arrow until the desired character is
shown then press . Or Enter the Numerical Designator for the character you want, then press . See
Appendix B of this manual for a list of available characters and their numeric designators.
6. Repeat step 5 until the name is complete.
7. Press
ENTER when the name is complete.
7.6 System Options
This section of the manual explains how to customize software options that affect general operation of the
system. This includes such items as: AC loss hours, system clock options, telephone and reporting account
options. Refer to each individual subsection for complete instructions.
7.6.1 Reporting Account
Up to four reporting accounts can be used with the control panel. Events in accounts are reported by zone.
Each account is assigned an up-to-6-digit account number. Each account is also assigned a unique ID (1-4) which
determines the priority for reporting (“1” has the highest priority; “4” has the lowest).
Disable any unused accounts by selecting “N” for all events (see Figure 7-13, next page). If the system is local
only (does not connect to a central station), disable all events for all four reporting accounts.
Options for each account can be customized. These options appear on the Reporting Accounts screen. Some
related options appear on the Phone Lines screen (see Section 7.6.2).
To access the Reporting Accounts screen:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. From the Program Menu, select 5 for System Options.
4. From the next menu, select 0 for Reporting Accounts.
7.6.1.1 Edit Accounts
5. From the next menu, select 1 for Edit Account.
A screen similar to one shown in Figure 7-13 will display. The following subsections describe the options on
each field.
Figure 7-13 Reporting Account Editing Screen