User Manual

IntelliKnight 5808 Installation Manual 151274-L8
7-25
7.6.2.4 Rotary Format
9. Press the or arrow to select the pulse ratio for rotary dialing option, then press ENTER. Options are:
7.6.2.5 Line Monitor
Enable the line monitor for each phone line that will be used. See Figure 7-15 for location of this field on the
phone lines screen. When the phone line monitor has been enabled for a phone line, a trouble condition will
occur if the line is not connected. If a phone line will not be used, it must be disabled.
10. Select Y (monitor line) or N (don’t monitor line) by pressing the or arrow, then press
ENTER.
7.6.2.6 Answering Machine Bypass
This option is used in conjunction with the Silent Knight Software Suite 5660. This feature ensures that an
answering machine will not interfere with communication between the panel and the computer. If an answering
machine is used at the panel site, enable this feature; if an answering machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication Configuration
dialog box of the 5660 software. See the manual for the software (p/n 151240) if you need more information.
11. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the
or arrow, then press
ENTER.
7.6.3 System Event Outputs
1. Enter the installer code.
2. Select 7 for Program Menu.
3. From the Program Menu, select 5 for System Options.
4. From the System Options Menu, select 2 for System Event Outputs.
7.6.3.1 Trouble Events
You can map certain system trouble events to an output group. To access the screen for selecting output groups
and cadence patterns for system trouble events.
5. Press 1 for Trouble Events. A screen similar to the one in Figure 7-16 will display. Select a group and a
cadence pattern for each event as needed for your application. The U: field is for a user-specified trouble
condition. You can program an output group and cadence pattern for any of the following events:
TT TouchTone dialing. If this option is selected, only TouchTone dialing will be used for this
phone line.
TT/PL TouchTone alternating with pulse. If this option is selected, the dialer will first attempt to use
TouchTone. It will switch to pulse if TouchTone is not successful on the first attempt. It will
continue to alternate between TT and pulse for additional attempts.
U U.S. standard format. Uses the 60 msec / 40 msec make/break ratio.
E European format. Uses the 66 msec / 34 msec make/break ratio.
Battery Low battery condition.
Phone Ln Phone Line 1 or 2 trouble.
Account Account trouble; cannot report to account.
Printer Printer trouble. (Currently not supported; do not select.)