6. Select the holiday schedules you wish to edit (1- holidays 1 - 9, 2- holidays 10 - 18).
Figure 7-18 Edit Holidays Screen
7. Enter the month of the Holiday, then press
ENTER.
8. Enter the day of the month for the Holiday, then press
ENTER.
9. Repeat steps 6 and 7 for any remaining holidays you wish to program.
7.6.4 Time Options
Through this programming option you can set the water flow delay time, low AC report delay, Alarm
verification, AMPM/Military time and AC Frequency.
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Select 5 for System Options.
4. Select 5 for Time Options.
7.6.4.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Select 5 for System Options.
4. Select 5 for Time Options.
A screen similar to the one shown in Figure 7-19 will display.
Figure 7-19 Water Flow Delay Programming Screen
5. Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press
ENTER.
7.6.4.2 Alarm Verification Time
You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).
To set the alarm verification:
Pre-programmed
Holidays
Programmable
Holiday locations
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)