User Manual

Programming 151274-L8
7-28
6. Enter the desired number of seconds for the alarm verification time.
7. Press
or ENTER to make your selection and move to the next programming option.
7.6.4.3 Low AC Report Delay
Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a Low AC report will be sent to the central station.
To program low AC report delay, follow these steps:
Note: Steps continued from step 7 of Section 7.6.4.1.
Figure 7-20 Low AC Report Delay Programming Screen
8. Enter the number of hours before a low AC report will be sent to the central station, then press
ENTER. Refer
to Figure 7-20.
7.6.4.4 Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
9. Select AMPM (for AM/Pm display format) or MIL (for military or 24 hr display format) by pressing the
or arrow, then press
ENTER.
7.6.4.5 Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Neither. AC Frequency feature dictates how the
control panel will calculate time based on the AC line frequency used in the installation site. The “Neither”
option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate
time from the internal crystal. The internal crystal is not as accurate as the AC power source and either 60 Hz or
50 Hz should normally be selected. The panel defaults to the 60 Hz. selection
To change the AC line frequency, continue programming from step 9 above:
10. Select 50, 60 or Neither, by pressing the or arrow, then press
ENTER.
7.6.5 Miscellaneous Options
Through this programming option you can turn on or off strobe synchronization during silence, display status at
idle (auto display event), report by zone or point, plexiglass door, and single key ack.
To edit Miscellaneous Options:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Select 5 for System Options.
4. Select 6 for Misc. Options.
7.6.5.1 Synchronize Strobes Active During Silence
When “SYNC Strbs w/ Sil:” is Selected as Y (Yes) then strobes will continue to flash when the system is silenced
and will stop flashing when the system is reset.
Low AC Report
Delay in Hours
(00 - 30)