User Manual

IntelliKnight 5808 Installation Manual 151274-L8
8-3
8.4 Menu System
The control panel is easy to operate from Main Menu. To view the Main Menu press the ENTER or button on
the control panel or remote annunciator, then turn the firefighters key clockwise or enter your access code. The
Main Menu will appear as shown in Section 8.4.1. Select the desired option. If you have entered a code or
firefighters key does not have access to the menu item you have selected the following display message will
appear:
-Access denied.-
Entered PIN does not
allow access to this
function.
You must enter an access code with the correct profile settings to gain access to that menu item.
The control panel supports up to 20 access codes. The profile for each access code (or user) can be modified
through the programming menu option (see Section 7.9 for access code programming).
8.4.1 Main Menu Overview
The chart below is a brief overview of the Main Menu. These options are described in greater detail throughout
this section of the manual.
Main Menu Options Description
1 - System Tests From here you can access Fire Drill and Indicator Test.
2- Point Functions From here you can enable / disable points.
3 - Event History Display event history on the LCD. See Section 8.5.6 for more information.
4 - Set Time and Date Set time and date for the system.
5 - Printer Options Options for controlling a printer if attached to the system. If a printer is used, the
Model 5824 serial/parallel interface module must be used.
6 - Reset Items Cancel any attempt to call the central station. Any calls awaiting additional attempts
will be aborted.
7 - Program Menu Brings up a set of menus for programming the panel, including changing access
codes. These options are described in detail in Section 7.
8 - System Info View system information, including model and serial numbers and revision number
and date.
9 - Up/Download Initiate communication from the panel site between the panel and a computer
running the Silent Knight Software Suite.