System Operation 151274-L8
8-10
Note: Detector status can also be viewed and printed using the 5660 or 5670 (facility monitoring only) SKSS.
8.6 Operation Mode Behavior
The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm,
Supervisory, Trouble, Silenced, and Reset. Table 8-1describes the behavior of the panel in each of these modes.
Sample Event History
Print-Out
3 = Print Detector Status Prints the current status of all detectors in the system. This is a method for finding out if any
detectors are out of NFPA compliance or any detectors need maintenance (are approaching an
out of compliance condition).
Sample Detector Status
Print-Out
4= Print System Cfg Prints the current system configuration of the panel. The entire configuration can be printed, or just
specific sections.
Table 8-1: Operation Mode Behavior
Operation
Mode
Occurs
When
System Behavior In This Mode You Can
Normal No alarm,
supervisory or
trouble con-
dition exists
and menus are
not in use.
SYSTEM POWER LED is on.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
Enter the appropriate code, or rotate the key to activate
the Main Menu.
EVENT HISTORY:
PRINTED: 02/28/97 13:35
02/20/97 09:05 Event 2 of 10: System Reset
02/28/97 13:31 Event 2 of 10: Walk Test End
02/20/97 09:02 Event 3 of 10: System Silenced
02/22/97 08:47 Event 4 of 10: Printer Off Line 4
02/22/97 08:52 Event 4 of 10: Printer On Line 4
02/25/97 15:54 Event 5 of 10: Local Programming Begin
02/25/97 16:10 Event 5 of 10: Local Programming Ended Successfully
02/28/97 12:50 Event 6 of 10: Walk Test Begin
.
.
.