User Manual

IntelliKnight 5808 Installation Manual 151274-L8
8-15
8.7 Releasing Operations
This control panel supports two types of releasing: Double Interlock Zone and Single Interlock Zone. The
Double Interlock Zone operation requires an interlock switch input in the system, and the Single Interlock does
not. An interlock switch is typically a dry-contact pressure switch.
When a Single or Double Interlock Zone releasing is selected the system will automatically default the following
system parameters:
Note: The defaults created can be modified through programming if desired.
Output Group 2 is created. Output Group 2 will be defaulted as an “Alarm” output group for all releasing
zones. NAC [34:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as an “Pre-Alert” output group for all releasing
zones. NAC [34:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as a “Release” output group for all releasing
zones. NAC circuit [34:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches.
Figure 8-5 Wiring Configuration for Solenoid
Table 8-2: Approved Releasing Solenoids
Manufacturer Part Number Rating
Asco
T8210A107 24 VDC, 3A
8210G207 24 VDC, 3A
Important!
Detectors must be installed at 0.7 times the linear spacing as described in NFPA 72, Chapter 2.