User Manual

Reporting 151274-L8
9-4
Water release circuit has been
disabled
Trouble pi Exp. ID SS Point # 1 203 Exp. ID Point #
Water release circuit has been re-
enabled
Trouble pi Exp. ID SR Point # 3 203 Exp. ID Point #
Walk test end Test TE 0 3 607 00 000
Walk test begin Test TS 0 1 607 00 000
Zone Events Note: Zone events are reported only when “Report by Zone” is selected.
Auxiliary power trouble Trouble FT 0000 1 320 00 000
Auxiliary power trouble restore Trouble FJ 0000 3 320 00 000
CO Detector Alarm Alarm GA Zone # 1 162 00 Zone #
CO Detector Alarm Restore Restore GH Zone # 3 162 00 Zone #
CO Detector Trouble Trouble GT Zone # 1 373 00 Zone #
CO Detector Trouble Restore Trouble GJ Zone # 3 373 00 Zone #
CO Supervisory Condition Trouble GS Zone # 1 200 00 Zone #
CO Supervisory Condition Restore Trouble GR Zone # 3 200 00 Zone #
Detector Trouble Trouble FT Zone # 1 373 00 Zone #
Detector Trouble Restore Trouble FJ Zone # 3 373 00 Zone #
Detector Alarm Alarm FA Zone # 1 110 00 Zone #
Detector Alarm Restore Restore FH Zone # 3 110 00 Zone #
Emergency Notification Trouble
1
Trouble QT 1000 +
Group #
1 320 00 Group #
Emergency Notification Trouble
Restored
1
Trouble QJ 1000 +
Group #
3 320 00 Group #
Emergency Switch Trouble
1
Trouble QT 0 1 242 00 000
Emergency Switch Trouble Restore
1
Trouble QJ 0 3 242 00 000
External Reset/Silence/Fire Drill
switch trouble
Trouble UT 0000 1 373 00 000
External Reset/Silence/Fire Drill
switch trouble restore
Trouble UJ 0000 3 373 00 000
LOC Mic Activated Emergency
Alarm
1
Alarm QA 0 1 220 00 000
LOC Mic Activated Emergency Alarm
Restore
1
Restore QH 0 3 220 00 000
LOC/Point Emergency # Alarm
1
Alarm QA Emergency # 1 220 +
Emer-
gency
#
00 Emergency #
LOC/Point Emergency # Alarm Re-
store
1
Restore QH Emergency # 3 220 +
Emer-
gency
#
00 Emergency #
Manual Pull switch alarm Alarm FA Zone # 1 115 00 Zone #
Manual Pull switch alarm restore Restore FH Zone # 3 115 00 Zone #
Manual Pull switch trouble Trouble FT Zone # 1 373 00 Zone #
Manual Pull switch trouble restore Trouble FJ Zone # 3 373 00 Zone #
SIA Reporting Format Contact ID Reporting Format
Event Description
Event
Family
Module
ID #
(if any)
SIA
Event
Code
Parameter (if
any)
Qualifier
Event
Code
Group
#
Contact
#