Agency Listings, Approvals, and Requirements 151274-L8
2-2
installer.
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements. The following subsections list specific requirements for each
type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and
so on). See Section 8.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 5of this manual and or conventional detectors
listed in the compatibility chart. (See Appendix A.)
3. Use UL listed notification appliances compatible with the 5808from those specified in the Appendix A at the
back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL
certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in
commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding
applications, and hotel/motel room applications.
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL certified installations
the setting must be a minimum of 60 seconds.
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.
P.A.S feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
Minimum system requirements are one Silent Knight addressable initiating device.
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5808 sends an automatic daily test to the cen-
tral station.
3. The AC Loss Hours option must be set from 1-3 hours.
4. The Attempts to Report option must be set for 5.