IntelliKnight 5808 Installation Manual 151274-L8
2-3
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used. Minimum system requirements are one
Silent Knight addressable initiating device.
2.2.4 Requirements for Remote Station Protected Fire Alarm
Systems
Minimum system requirements are one Silent Knight addressable initiating device and either a 5220, Keltron
3158 or the built-in Digital Alarm Communicator Transmitter (DACT).
1. Do not exceed the current load restrictions shown in Section 3.6.1.3.
2. The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for Auxiliary Protected Fire Alarm Systems
for Fire Alarm Service
The Model 5220 Direct Connect module must be installed (see Section 4.13.3.1 for wiring).