3.3 Electrical Specifications
Table 3-1 list the terminal block on the 5808 as well as a description of the each individual terminal and their
respective electrical rating.
* Regulated/special application when used for releasing.
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal No.
Label
Description
Rating
Group Individual Voltage Current
Terminal Block 1 AC INPUT B AC input (hot) 120 VAC, 60 Hz 3.6 A
Earth Earth Ground N/A N/A
W AC input (neutral) 120 VAC, 60 Hz 3.6 A
Terminal Block 2 SLC IN Used for Class A installations 32 VDC 150 mA
+
SLC OUT SLC terminals 32 VDC 150 mA
+
SLC PROG Used for programming SLC
Detectors
32 VDC 150 mA
+
Terminal Block 3 TELCO 1 RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1 RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2 RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2 RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
Terminal Block 4 TROUBLE NC Normally closed relay contact 24 VDC 2.5 A, resistive
COM Common terminal
NO Normally open relay contact
RELAY 1 NC Normally closed relay contact 24 VDC 2.5 A, resistive
COM Common terminal
NO Normally open relay contact
RELAY 2 NC Normally closed relay contact 24 VDC 2.5 A, resistive
COM Common terminal
NO Normally open relay contact
NAC1* Notification Appliance Circuit/
Auxiliary power
24 VDC 3.0 Amp NAC or Aux
power
+
NAC2* Notification Appliance Circuit/
Auxiliary power
24 VDC 3.0 Amp NAC or Aux
power
+
NAC3* Notification Appliance Circuit/
Auxiliary power
24 VDC 3.0 Amp NAC or Aux
power
+
NAC4* Notification Appliance Circuit/
Auxiliary power
24 VDC 3.0 Amp NAC or Aux
power
+
Terminal Block 5 SBUS B SBUS Communication 5 VDC 100 mA
A
+ SBUS Power 24 VDC 1.0 A
BATTERY + To Positive battery terminal 24 VDC Up to 35 Ah (see Section
4.3 for details)
To Negative battery terminal