User Manual

IntelliKnight 5808 Installation Manual 151274-L8
3-11
3.7 Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5808
system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks.
Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Task
See Sec.
(for more info.)
Main Panel Hardware Installation
Mount the control panel cabinet.
4.1
Connect AC.
4.2
Install 5860 Remote Fire Alarm Annunciator modules if used.
4.5
Install 5865 or LED Annunciator modules if used.
4.8
Install 5880 LED I/O module if customized LED annunciation will be used.
4.7
Connect phone lines.
4.10
Install notification appliances.
4.11
Install auxiliary power devices (if used).
4.11.2
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.
4.6
Connect batteries (typically last step).
4.3
SLC Device Hardware Installation
Perform these steps before running JumpStart.
Connect device bases to the loop.
SK 5.5
SD 5.7
Set device addresses.
SK 5.6
SD 5.8
Physically connect detectors to their bases. Connect relay and contact monitor modules.
5.4 & see device
install instructions
JumpStart
JumpStart is for initial system programming. JumpStart automatically selects some options for SLC
devices. See “Input Point Configuration” section of this chart for other options. JumpStart makes selections
for the following options. You can customize options, if necessary.
6.1 & 7.7
Device type (detector or switch) configured by JumpStart. To change, see 7.5
Program type of detector (heat, photoelectric, or ionization) selected by JumpStart. To change, see 7.5
System Software Configuration
Select low AC hours report time (3 hours by default).
7.6.4.3
Select Auto Test Time (2:00 AM by default).
7.6.1.2
Enable/disable automatic DST adjustment feature (enabled by default).
7.6.4.4
Change clock display format (12-hour with AM/PM by default).
7.6.4.4
Set up reporting accounts.
7.6.1
Select options for phone lines.
7.6.2
Select system-wide response to trouble conditions, if desired.
7.6.3
Select system-wide cadence patterns for special conditions (fire drill, Aux1 and Aux2
alarms) if desired.
7.6.3.2
Customize banner message (message that displays on LCD in normal mode) if desired.
7.6.7
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart). You can change options
selected by JumpStart, if necessary and further customize input point options.