User Manual

Before You Begin Installing 151274-L8
3-12
Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart
assigns all switches as Manual Pull type.)
7.5
If the installation includes duct detectors, program detector type. (JumpStart does not
distinguish duct detectors from ordinary smoke detectors.)
7.5
Assign a name (or description) to the point.
7.5.4
Assign input points to zones, if necessary. (JumpStart assigns all input points to Zone 1.)
7.5.4
Zone Configuration
Add the zone to the system if it does not already exist. (Zone 1 created by JumpStart.)
7.3.2
Program a name (or description) for the zone.
7.3.1.1
Select alarm delay options (detection characteristics) for zone.
7.3.1.1
Select heat detector trip temperature and. (JumpStart selects 150°F for heat detectors
and.)
7.3.1.2
Output Point Configuration
Conventional notification circuits (circuits 1-6):
Enable circuits used for notification appliances through programming, if necessary.
(JumpStart enables circuits 1-6 as Notification.)
7.4.1
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always output
continuously (constant pattern), even if assigned to an Output Group that uses a different
output pattern.
7.4.1
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming.
7.5
Select type of power (door holder, constant, or resettable, or sounder sync)
7.5
Addressable relay modules
Assign addressable relay modules to output groups through programming. (JumpStart
assigns all relay modules to Group 1.)
7.5
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming.
7.5.3
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused output
circuits, they will cause a trouble condition (unless an EOL resistor is used).
7.5
Select a name for the point, if desired.
7.5.4
Output Group Configuration
Add the group to the system if it does not already exist.
7.4.2
Assign output points to the group.
7.5
Program a name (or description) for the group, if desired.
7.4.1.1
Select “group properties” (see below).
Latching / non-latching
7.4.1.2
Silencing option
7.4.1
Select options for activation with system switches.
7.4.1
Map zones to output groups that will activate when zone goes into alarm.
7.3.1.3
Select a cadence pattern for outputs in the zone.
7.3.1.4
Task
See Sec.
(for more info.)