User Manual

IntelliKnight 5808 Installation Manual 151274-L8
4-3
4.3.1 RBB Accessory Cabinet
The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries
that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size.
The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See figure Figure 4-3 for the four cabinet mounting holes.
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is neces-
sary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull
away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a piece of ¾”” plywood to
the concrete surface and then attach the RBB cabinet to the plywood.
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18"
away from the main control panel cabinet. This will ensure that the battery cables reach the battery ter-
minals.
Figure 4-3 RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-4.
Figure 4-4 Splicing Control Panel Battery Cable to RBB Battery Cable Extenders
Cabinet
Mounting Holes