User Manual

Control Panel Installation 151274-L8
4-8
4.5 5860 Remote Annunciator Installation
The optional Model 5860 Remote Annunciator, shown in Figure 4-8, performs the same functions as the on-
board annunciator as well as initiate and end fire drills with a single key press and view event history by alarms,
supervisories, or troubles.
Up to 12 annunciators can be added to the 5808 system.
Figure 4-8 Model 5860 Remote Annunciator, Front View
5860 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the 5860 in the desired location (see Section 4.5.1).
3. Connect the 5860 to the panel (see Section 4.5.2).
4. Use the DIP switches on the back of the 5860 to assign an ID# to the 5860 (see Section 4.9.1).
5. The new 5860 module must be added to the system through programming. JumpStart will add the module
automatically (see Section 6.1). You can also add it manually (see Section 7.2.2). Select a name, if desired
(see Section 7.2.1.1).